SITRANS P300 for gauge and absolute pressure |
||||||
---|---|---|---|---|---|---|
HART |
PROFIBUS PA and FOUNDATION Fieldbus |
|||||
Gauge pressure input |
||||||
Measured variable |
Gauge pressure |
|||||
Spans (infinitely adjustable) or nominal measuring range and |
Span (min. ... max.) |
Max. perm. test pressure |
Nominal measuring range |
Max. perm. test pressure |
||
0.01 ... 1 bar g |
6 bar g |
1 bar g |
6 bar g |
|||
0.04 ... 4 bar g |
10 bar g |
4 bar g |
10 bar g |
|||
0.16 ... 16 bar g |
32 bar g |
16 bar g |
32 bar g |
|||
0.6 ... 63 bar g |
100 bar g |
63 bar g |
100 bar g |
|||
1.6 ... 160 bar g |
250 bar g |
160 bar g |
250 bar g |
|||
4.0 ... 400 bar g |
600 bar g |
400 bar g |
600 bar g |
|||
Depending on the process connection, the span may differ from these values |
Depending on the process connection, the nominal measuring range may differ from these values |
|||||
Lower measuring limit |
||||||
|
30 mbar a (0.44 psi a) |
|||||
Upper measuring limit |
||||||
|
100% of max. span |
100 % of the max. nominal measuring range |
||||
Absolute pressure input |
||||||
Measured variable |
Absolute pressure |
|||||
Spans (infinitely adjustable) or nominal measuring range and |
Span (min. ... max.) |
Max. perm. test pressure |
Nominal measuring range |
Max. perm. test pressure |
||
8 ... 250 mbar a |
6 bar a |
250 mbar a |
6 bar a |
|||
43 ... 1300 mbar a |
10 bar a |
1.30 bar a |
10 bar a |
|||
0.16 ... 5 bar a |
30 bar a |
5 bar a |
30 bar a |
|||
1 ... 30 bar a |
100 bar a |
30 bar a |
100 bar a |
|||
Lower measuring limit |
||||||
|
0 mbar a (0 psi a) |
|||||
Upper measuring limit |
||||||
|
100% of max. span |
100 % of the max. nominal measuring range |
||||
Input of gauge pressure, with flush-mounted diaphragm |
||||||
Measured variable |
Gauge pressure, flush-mounted |
|||||
Spans (infinitely adjustable) or nominal measuring range and max. permissible test pressure |
Span (min. ... max.) |
Max. perm. test pressure |
Nominal measuring range |
Max. perm. test pressure |
||
0,01 ... 1 bar g (0.15 ... 14.5 psi g) |
6 bar g |
1 bar g |
6 bar g |
|||
0,04 ... 4 bar g (0.58 ... 58 psi g) |
10 bar g |
4 bar g |
10 bar g |
|||
0,16 ... 16 bar g (2.32 ... 232 psi g) |
32 bar g |
16 bar g |
32 bar g |
|||
0,6 ... 63 bar g (9.14 ... 914 psi g) |
100 bar g |
63 bar g |
100 bar g |
|||
Lower measuring limit |
100 mbar a (1.45 psi a) |
|||||
Upper measuring limit |
||||||
|
100% of max. span |
100 % of the max. nominal measuring range |
||||
Input of absolute pressure, with flush-mounted diaphragm |
||||||
Measured variable |
Absolute pressure, flush-mounted |
|||||
Spans (infinitely adjustable) or nominal measuring range and |
Span (min. ... max.) |
Max. perm. test pressure |
Nominal measuring range |
Max. perm. test pressure |
||
43 ... 1300 mbar a |
10 bar a |
1300 mbar a |
10 bar a |
|||
0.16 ... 5 bar a |
30 bar a |
5 bar a |
30 bar a |
|||
1 ... 30 bar a |
100 bar a |
30 bar a |
100 bar a |
|||
Depending on the process connection, the span may differ from these values |
Depending on the process connection, the nominal measuring range may differ from these values |
|||||
Lower measuring limit |
0 bar a (0 psi a) |
|||||
Upper measuring limit |
||||||
|
100% of max. span |
100 % of the max. nominal measuring range |
||||
Output |
||||||
Output signal |
4 ... 20 mA |
Digital PROFIBUS PA signal |
||||
Physical bus |
- |
IEC 61158-2 |
||||
Protection against polarity reversal |
Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage. |
|||||
Electrical damping (step width 0.1 s) |
Set to 2 s (0 ... 100 s) |
|||||
Measuring accuracy |
According to IEC 60770-1 |
|||||
Reference conditions |
Rising characteristic curve, start-of-scale value 0 bar, stainless steel seal diaphragm, measuring cell with silicone oil, room temperature 25 °C (77 °F), span ratio (r = max. span / set span) |
|||||
Error in measurement at limit setting incl. hysteresis and reproducibility |
||||||
Gauge pressure |
Absolute pressure |
Absolute pressure, flush-mounted |
Gauge pressure |
Absolute pressure |
Absolute pressure, flush-mounted |
|
Linear characteristic |
0,075 % |
0,1 % |
0,2 % |
|||
|
(0.0029 · r + 0.071) % |
0,1 % |
0,2 % |
|||
|
(0.0045 · r + 0.071) % |
0,2 % |
0,4 % |
|||
|
(0.005 · r + 0.05) % |
- |
- |
|||
Step response time T63 |
approx. 0.2 NO |
|||||
Long-term stability at ± 30 °C (± 54 °F) |
(0.25 · r) %/5 years |
(0.1 · r) %/year |
0.25 %/5 years |
0.1 %/year |
||
Influence of ambient temperature |
||||||
|
(0.08· r + 0.1) % |
(0.2 · r + 0.3) % |
0,3 % |
0,5 % |
||
Conversion of temperature error per 28 °C. Valid for temperature range -3 ... +53 °C < (0.064. r + 0.08) % / 28 °C (50 °F). |
||||||
|
(0.1 · r + 0.15) %/10 K |
(0.2 · r + 0.3) %/10 K |
0.25 %/10 K |
0.5 %/10 K |
||
Influence of the medium temperature (only with flush-mounted diaphragm) |
||||||
|
3 mbar/10 K (0.04 psi/10 K) |
Rated conditions |
||
---|---|---|
Installation conditions |
||
Ambient temperature |
Observe the temperature class in areas subject to explosion hazard. |
|
|
-40 ... +85 °C (-40 ... +185 °F) |
|
|
-10 ... +85 °C (14 ... +185 °F) |
|
|
-20 ... +85 °C (-4 ... +185 °F) |
|
|
-30 ... +85 °C (-22 ... +185 °F) |
|
|
-50 ... +85 °C (-58 ... +185 °F) |
|
Climatic class |
||
Condensation |
Relative humidity 0 ... 100 % |
|
Degree of protection acc. to EN 60529 |
IP65, IP68, NEMA X, enclosure cleaning, resistant to lyes, steam to 150 °C (302 °F) |
|
Electromagnetic Compatibility |
||
|
Acc. to EN 61326 and NAMUR NE 21 |
|
Medium conditions |
||
Temperature of medium |
||
|
-40 ... +100 °C (-40 ... +212 °F) |
|
|
-40 ... +150 °C (-40 ... +302 °F) |
|
|
-10 ... +150 °C (-14 ... +302 °F) |
|
|
-40 ... +200 °C (-40 ... +392 °F) |
|
|
-20 ... +100 °C (-4 ... +212 °F) |
|
|
-10 ... +250 °C (14 ... 482 °F) |
|
Design (standard version) |
||
Weight (without options) |
Approx. 800 g (1.8 lb) |
|
Enclosure material |
Stainless steel, mat. no. 1.4301/304 |
|
Material of parts in contact with the medium |
||
|
Stainless steel, mat. no. 1.4404/316L or Hastelloy C276, mat. no. 2.4819 |
|
|
Stainless steel, mat. no. 1.4404/316L |
|
|
Stainless steel, mat. no. 1.4404/316L or Hastelloy C276, mat. no. 2.4819 |
|
|
|
|
Process connection |
|
|
Design (version with flush-mounted diaphragm) |
||
Weight (without options) |
approx. 1 ... 13 kg (2.2 ... 29 lb) |
|
Enclosure material |
Stainless steel, mat. no. 1.4301/304 |
|
Material of parts in contact with the medium |
||
|
Stainless steel, mat. no. 1.4404/316L |
|
|
Stainless steel, mat. no. 1.4404/316L |
|
|
|
|
Process connection |
|
|
Surface quality touched-by-media |
Ra-values 0.8 µm (32 µ-inch)/welds Ra) 1.6 µm (64 µ-inch) (Process connectionsaccording to 3A; Ra-values 0.8 µm (32 µ-inch)/welds Ra) 0.8 µm (32 µ-inch) |
|
Power supply UH |
||
Terminal voltage on transmitter |
10.5 ... 42 V DC |
Supplied through bus |
Separate power supply |
- |
Not necessary |
Bus voltage |
||
|
- |
9 ... 32 V |
|
- |
9 ... 24 V |
Current consumption |
||
|
- |
12.5 mA |
|
- |
Yes |
|
- |
15.5 mA |
Fault disconnection electronics (FDE) |
- |
Available |
Certificates and approvals |
||
Classification according to PED 97/23/EC |
For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of Article 3, paragraph 3 (sound engineering practice) |
|
Water, waste water |
In preparation |
|
Explosion protection |
||
Intrinsic safety "i" |
PTB 05 ATEX 2048 |
|
|
Ex II 1/2 G EEx ia/ib IIB/IIC T4, T5, T6 |
|
|
||
|
-40 ... +85 °C (-40 ... +185 °F) |
|
|
-40 ... +70 °C (-40 ... +158 °F) |
|
|
-40 ... +60 °C (-40 ... +140 °F) |
|
|
To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, |
To certified intrinsically-safe circuits with peak values: FISCO supply unit: Ui = 17.5 V, Ii = 380 mA, Linear barrier: Ui = 24 V, Ii = 250 mA, Pi = 1.2 W |
|
Ci = 6 nF |
Ci = 1.1 nF |
|
Li = 0.4 mH |
Li 7 H |
Explosion protection to FM for USAand Canada (cFMUS) |
||
|
Certificate of Compliance 3025099 CL I, DIV 1, GP ABCD T4 ... T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4 ... T6; CL I, DIV 2, GP ABCD T4 ... T6; CL II, DIV 2, GP FG; CL III |
|
|
Certificate of Compliance 3025099C CL I, DIV 1, GP ABCD T4 ... T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC 4 ... T6; CL I, DIV 2, GP ABCD T4 ... T6; CL II, DIV 2, GP FG; CL III |
|
Dust explosion protection for zone 20/21/22 |
PTB 05 ATEX 2048 |
|
|
Ex II 1D Ex ia D 20 T 120 °C Ex II 2D Ex ib D 21 T 120 °C Ex II 3D Ex ib D 21 T 120 °C |
|
|
||
|
-40 ... +85 °C (-40 ... +185 °F) (in the case of mineral glass windows only |
|
|
-40 ... +70 °C (-40 ... +158 °F) (in the case of mineral glass windows only |
|
|
-40 ... +60 °C (-40 ... +140 °F) (in the case of mineral glass windows only |
|
|
To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW |
To certified intrinsically-safe circuits with peak values: Ui = 24 V, Ii = 380 mA, Pi = 5.32 W |
|
Ci = 6 nF |
Ci = 5 nF |
|
Li 0.4 H |
Li = 10 H |
Type of protection Ex nA/nL/ic (Zone 2) |
PTB 05 ATEX 2048 |
|
|
II 2/3 G Ex ic IIB/IIC T4/T5/T6 II 2/3 G Ex nA T4/T5/T6 II 2/3 G Ex nL IIB/IIC T4/T5/T6 |
|
|
||
|
-40 ... +85 °C (-40 ... +185 °F) (in the case of mineral glass windows only -20 ... +85 °C (-4 ... +185 °F)) |
|
|
-40 ... +70 °C (-40 ... +158 °F) (in the case of mineral glass windows only -20 ... +70 °C (-4 ... +158 °F)) |
|
|
-40 ... +60 °C (-40 ... +140 °F) (in the case of mineral glass windows only -20 ... +60 °C (-4 ... +140 °F)) |
|
|
To certified intrinsically-safe circuits with peak values: Um = 45 V |
To certified intrinsically-safe circuits with peak values: Um = 32 V |
|
To certified intrinsically-safe circuits with peak values: Ui = 45 V |
To certified intrinsically-safe circuits with peak values: Ui = 32 V |
|
Ci = 6 nF |
Ci = 5 nF |
|
Li = 0.4 mH |
Li = 20 H |
HART communication |
|
---|---|
HART communication |
230 ... 1100 |
Protocol |
HART Version 5.x |
Software for computer |
SIMATIC PDM |
PROFIBUS PA communication |
|
---|---|
Simultaneous communication with master class 2 (max.) |
4 |
The address can be set using |
Configuration tool or local operation (standard setting Address 126) |
Cyclic data usage |
|
|
5 (one measured value) or 10 (two measured values) |
|
0, 1 or 2 (totalizer mode and reset function for dosing) |
|
|
Device profile |
PROFIBUS PA Profile for Process Control Devices Version 3.0, Class B |
Function blocks |
2 |
|
|
|
Yes, linearly rising or falling characteristic |
|
0 … 100 s |
|
Input /Output |
|
parameterizable (last good value, substitute value, incorrect value) |
|
Yes, one upper and lower warning limit and one alarm limit respectively |
|
Can be reset, preset, optional direction of counting, simulation function of register output |
|
parameterizable (summation with last good value, continuous summation, summation with incorrect value) |
|
One upper and lower warning limit and one alarm limit respectively |
|
1 |
Transducer blocks |
2 |
|
|
|
Yes |
|
Yes |
|
Max. 30 nodes |
|
Constant value or over parameterizable ramp function |
FOUNDATION Fieldbus communication |
|
---|---|
Function blocks |
3 function blocks analog input, 1 function block PID |
|
|
|
Yes, linearly rising or falling characteristic |
|
0 & 100 s |
|
Output/input (can be locked within the device with a bridge) |
|
parameterizable (last good value, substitute value, incorrect value) |
|
Yes, one upper and lower warning limit and one alarm limit respectively |
|
Yes |
|
Standard FOUNDATION Fieldbus function block |
|
1 resource block |
Transducer blocks |
1 transducer block Pressure with calibration, 1 transducer block LCD |
|
|
|
Yes |
|
Yes |
|
Constant value or over parameterizable ramp function |