General technical data |
SICROWBAR AC overvoltage protection |
---|---|
Degree of protection |
IP00 acc. to EN 60529 |
Protection class |
I according to EN 50178 |
Overvoltage category |
III, corresponding to EN 60664 |
Dimensioning creepages and clearances |
Pollution degree 2 acc. to EN 50178 |
Rated insulation voltage |
725 V AC for rated supply voltage 400 ... 725 V |
Installation altitude |
2 000 m above sea level |
Permissible ambient temperature |
|
|
+5 ... +55 °C |
|
-40 ... +70 °C |
Climate class |
3K3 acc. to EN 60721-3-3 |
Fuse monitoring (microswitch at the fused disconnector, 1 changeover contact) |
Flat connector 6.3 mm 0.8 mm |
|
1/2 closed, 1/4 opened |
|
1/4 closed, 1/2 opened |
|
1/4 closed, 1/2 opened |
|
50 Hz 250 V AC, 3 A |
1) Installation altitudes above 2 000 m on request.
SICROWBAR AC overvoltage protection |
|||||
---|---|---|---|---|---|
7VV3002 3CD20 |
7VV3002 3AD20 |
7VV3002 3BD20 |
7VV3002 3GD20 |
||
Max. permissible rated supply voltageVN |
V |
460 |
550 |
||
Nominal response voltage of the BOD elementVAN |
V |
1 000 |
1 200 |
1 400 |
1 600 |
Min. limit voltage of BOD element at 5 °C |
V |
864 |
1 056 |
1 248 |
1 440 |
Max. limit voltage of BOD element at 55 °C |
V |
1 166 |
1 378 |
1 590 |
1 802 |
Max. permissible peak current,Imax |
A |
200 |
1 000 |
2 000 |
|
Rated insulation voltage (the insulation voltage is determined by the highest rated supply voltage of the relevant construction type)VISO |
V |
550 |
|||
Varistor voltage (breakdown voltage) atTA = 25 °C, 1 mA |
V |
720 |
860 |
||
Max. energy (for 2 ms) atTA = 85 °C |
Ws |
600 |
720 |
||
Energy that can be absorbed 100 times |
Ws |
350 |
419 |
||
Energy that can be absorbed 10 000 times |
Ws |
42 |
50 |
||
Version |
A |
||||
Dimensions |
|||||
|
mm |
265 |
|||
|
mm |
385 |
|||
|
mm |
237 |
|||
Weight, approx. |
kg |
7 |
SICROWBAR AC overvoltage protection |
||||||
---|---|---|---|---|---|---|
|
7VV3002 3DD20 |
7VV3002 3ED20 |
7VV3002 3JD20 |
7VV3002 3KD20 |
7VV3002 3LD20 |
|
Max. permissible rated supply voltageVN |
V |
770 |
920 |
1 100 |
||
Nominal response voltage of the BOD elementVAN |
V |
1 900 |
2 400 |
2 600 |
2 800 |
3 000 |
Min. limit voltage of BOD element at 5 °C |
V |
1 728 |
2 208 |
2 400 |
2 592 |
2 784 |
Max. limit voltage of BOD element at 55 °C |
V |
2 120 |
2 650 |
2 862 |
3 074 |
3 286 |
Max. permissible peak current,Imax |
A |
300 |
800 |
1 000 |
400 |
1 000 |
Rated insulation voltage (the insulation voltage is determined by the highest rated supply voltage of the relevant construction type)VISO |
V |
770 |
1 100 |
|||
Varistor voltage (breakdown voltage) atTA = 25 °C, 1 mA |
V |
1 240 |
1 500 |
1 820 |
||
Max. energy (for 2 ms) atTA = 85 °C |
Ws |
2 400 |
3 300 |
3 000 |
||
Energy that can be absorbed 100 times |
Ws |
986 |
1 196 |
1 027 |
||
Energy that can be absorbed 10 000 times |
Ws |
145 |
176 |
214 |
||
Version |
B |
C |
||||
Dimensions |
||||||
|
mm |
580 |
||||
|
mm |
305 |
||||
|
mm |
205 |
245 |
|||
Weight, approx. |
kg |
11 |
12 |