Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/new/cat.php on line 184
SIMATIC IPC427C (Microbox), SIMATIC PCS 7 OS Client 427C version |
|
Design and equipment features |
|
Design |
|
Degree of protection to EN 60529 |
IP20 |
CPU |
|
|
Intel Pentium Core 2 Duo 1.2 GHz |
|
800 MHz |
|
3 MB |
Chipset |
Intel GM45/ICH9M |
Main memory |
1024 MB DDR3-SDRAM SO-DIMM modules |
Graphic |
|
|
Intel GMA4500 integrated in the chipset |
|
32 ... 256 MB shared memory |
|
|
|
Up to 1920 x 1200, 60 ... 120 Hz |
|
Up to 1920 x 1200, 60 Hz |
Drives, alternative |
|
|
1 x 2.5" SATA-HDD |
|
1 x 2.5" SATA-SSD |
|
Connectable via USB (not included in scope of delivery) |
Interfaces |
|
|
2 x Ethernet port (RJ45) Intel 82574L |
|
4 x USB 2.0/high-speed |
|
1 x COM1 RS 232, 115 kbit/s max., 9-contact Sub-D connector |
|
|
|
1 x DVI-I (DVI/VGA combined)
|
|
Connectable via USB (not included in scope of delivery) |
LED displays |
|
Operating system / basic software |
|
Operating system |
Windows XP Professional MUI |
System-tested SIMATIC industrial software |
SIMATIC PC DiagMonitor integrated in preinstallation |
Monitoring / diagnostics functions |
|
Watchdog |
|
Temperature |
(via SIMATIC PC DiagMonitor and SIMATIC PCS 7 Asset Management) |
Runtime meter |
(via SIMATIC PC DiagMonitor and SIMATIC PCS 7 Asset Management) |
Safety |
|
Protection class |
Protection class I in accordance with IEC 61140 |
Safety directives |
EN 60950-1; UL 60950; CAN/CSA-C22.2 No. 60950-1; UL 508;CAN/CSA-C22.2 No. 142 or CAN/CSA-C22.2 No. 14-05 |
Noise level |
|
Operation |
< 40 dB (A) to DIN 45635 1 |
Electromagnetic compatibility (EMC) |
|
Radiated interference |
EN 61000 6 3 , EN 61000 6 4, CISPR22:2004 Class B; FCC Class A |
Immunity to conducted interference on the supply lines |
± 2 kV (to IEC 61000-4 4; burst) ± 1 kV (to IEC 61000-4 5; symmetrical surge) ± 2 kV (to IEC 61000-4 5; asymmetrical surge) |
Immunity to interference on signal lines |
± 1 kV (to IEC 61000-4 4; burst; length < 3 m) ± 2 kV (to IEC 61000-4 4; burst; length > 3 m) ± 2 kV (to IEC 61000-4 5; surge; length > 30 m) |
Immunity to static discharge |
± 6 kV contact discharge (to IEC 61000 4 2) ± 8 kV air discharge (to IEC 61000 4 2) |
Immunity to high-frequency irradiation |
10 V/m, 80 to 1 000 MHz and 1.4 to 2 GHz, 80 % AM (to IEC 61000 4 3) 1 V/m, 2 to 2.7 GHz, 80 % AM (to IEC 61000 4 3) 10 V, 10 kHz to 80 MHz, 80 % AM (to IEC 61000 4 6) |
Immunity to magnetic fields |
100 A/m rms value 50/60 Hz to IEC 61000 4 8 |
Climatic conditions |
|
Temperature |
Tested according to IEC 60068 2 1, IEC 60068 2 2, IEC 60068 2 14 |
|
|
|
|
|
|
|
|
|
-40 ... +60 °C (HDD) or |
|
Operation: Max. 10 °C/h; |
Relative humidity |
Tested according to IEC 60068 2 78, IEC 60068 2 30 |
|
5 ... 80% at 25 °C (no condensation) |
|
5 ... 95 % at 25 °C (no condensation) |
Mechanical environmental conditions |
|
Vibrations |
Tested according to IEC 60068-2-6 |
|
|
|
5 ... 9 Hz: 3.5 mm 9 ... 500 Hz: 9.8 m/s |
|
10 ... 58 Hz: 0.0375 mm 58 ... 200 Hz: 4.9 m/s |
|
Starting prohibited |
|
5 ... 9 Hz: 3.5 mm, |
Shock |
Tested according to IEC 60068 2 27 |
|
Without hard disk drive: 150 m/s , 11 ms; |
|
250 m/s , 6 ms |
Standards, specifications, approvals |
|
Residential area, business and commercial operations, and small businesses |
|
|
EN 61000-6-3: 2007 |
|
EN 61000-6-1: 2007 |
CE industrial environment |
|
|
EN 61000-6-4: 2007 |
|
EN 61000-6-2: 2005 |
cULus |
Underwriters Laboratories (UL) compliant with Standard UL 60950 1, File E115352 and Canadian National Standard CAN/CSA C22.2 No. 60950 1 (I.T.E) or with UL 508, File E85972 and Canadian National Standard CAN/CSA C22.2 No. 142 (IND.CONT.EQ) or with Canadian National Standard CAN/CSA C22.2 No. 14 05 |
Ship specifications for SIMATIC PCS 7 OS Client 427C (SSD) |
|
|
Yes |
|
Yes |
|
Yes |
|
Yes |
|
Yes |
|
Yes |
Special features |
|
Quality assurance |
according to ISO 9001 |
Power supply (electrically isolated) |
|
Supply voltage |
24 V DC (19.2 ... 28.8 V) |
Short-term voltage dip |
Min. 15 ms (at 20.4 V) Max. 10 events per hour; |
Max. current consumption (at 24 V DC) |
4 A (at 24 V) |
Dimensions and weights |
|
Dimensions (W x H x D in mm) |
262 x 142 x 47 |
Weight |
Approx. 2 kg |
1) RAL = Restricted Access Location: Installation of device in operating environment with restricted access, e.g. a locked switchgear cabinet