Order No. |
6EP1 234-1AA00 |
|
Technical specifications |
|
|
Product |
SITOP PSA100E |
|
Power supply, type |
24 V/12 A |
|
Input |
|
|
Input |
1-phase AC |
|
Supply voltage 1 at AC nominal value |
230 V |
|
Voltage range |
187 … 264 V |
|
Overvoltage resistance |
- |
|
Mains buffering at Iout rated, min. |
10 ms |
|
Rated line frequency |
|
|
50 Hz |
|
60 Hz |
|
Rated line range |
47 … 63 Hz |
|
Input current at nominal level of the input voltage 230 V nominal value |
2.5 A |
|
Switch-on current limiting (+25 °C), max. |
50 A |
|
I t, max. |
3.3 A ·s |
|
Built-in incoming fuse |
internal |
|
Protection in the mains power input (IEC 898) |
Recommended miniature circuit breaker: from 10 A, characteristic C |
|
Output |
|
|
Output |
controlled, isolated DC voltage |
|
Rated voltage Vout DC |
24 V |
|
Total tolerance, static ± |
3 % |
|
Static mains compensation, approx. |
0.1 % |
|
Static load balancing, approx. |
0.5 % |
|
Residual ripple peak-peak, max. |
0.15 V |
|
Spikes peak-peak, max. (bandwidth: 20 MHz) |
0.25 V |
|
Adjustment range |
23 … 26 V |
|
Product feature output voltage adjustable |
Yes |
|
Output voltage setting |
via potentiometer |
|
Status display |
Green LED for 24 V OK |
|
On/off behavior |
Overshoot of Vout < 5 % |
|
Startup delay, max. |
0.3 s |
|
Voltage increase time of the output voltage maximum |
0.5 s |
|
Rated current value Iout rated |
12 A |
|
Current range |
0 … 12 A |
|
Note |
12 A up to +45 °C, 6 A up to +70 °C |
|
delivered active power typ. |
288 W |
|
Parallel switching for enhanced performance |
Yes |
|
Numbers of parallel switchable units for enhanced performance |
2 |
|
Efficiency |
|
|
Efficiency at Vout rated, Iout rated, approx. |
88 % |
|
Power loss at Vout rated, Iout rated, approx. |
39 W |
|
Closed-loop control |
|
|
Dynamic mains compensation (Vin rated ±15 %), max. |
0.3 % |
|
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. |
3.5 % |
|
Load step setting time 50 to 100%, typ. |
0.1 ms |
|
Load step setting time 100 to 50%, typ. |
0.1 ms |
|
Protection and monitoring |
|
|
Output overvoltage protection |
< 35 V |
|
Current limitation, typ. |
13.2 A |
|
Characteristic feature of the output short-circuit protected |
Yes |
|
Short-circuit protection |
Electronic shutdown, automatic restart |
|
Enduring short circuit current Effective level maximum |
7.5 A |
|
Overload/short-circuit indicator |
- |
|
Safety |
|
|
Primary/secondary isolation |
Yes |
|
Potential separation |
Safety extra low output voltage Vout according to EN 60950-1 and EN 50178 |
|
Protection class |
Class I |
|
stray current |
|
|
3.5 mA |
|
0.8 mA |
|
CE mark |
Yes |
|
UL/CSA approval |
Yes |
|
UL/cUL (CSA) approval |
cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 |
|
Explosion protection |
- |
|
FM approval |
No |
|
FM approval |
- |
|
CB approval |
Yes |
|
Marine approval |
- |
|
Degree of protection (EN 60529) |
IP20 |
|
EMC |
|
|
Emitted interference |
EN 55022 Class B |
|
Supply harmonics limitation |
- |
|
Noise immunity |
EN 61000-6-2 |
|
Operating data |
|
|
Ambient temperature |
|
|
-10 … +70 °C |
|
with natural convection |
|
Ambient temparature |
|
|
-40 … +85 °C |
|
Ambient temparature |
|
|
-40 … +85 °C |
|
Humidity class according to EN 60721 |
Climate class 3K3, no condensation |
|
Mechanics |
|
|
Connection technology |
screw-type terminals |
|
Connections |
|
|
L, N, PE: Removable screw terminal, each 1 x 0.5 ... 2.5 mm |
|
+, -: Removable screw terminal each for 1 x 0.5 ... 2.5 mm |
|
- |
|
Width of the housing |
52 mm |
|
Height of the housing |
170 mm |
|
Depth of the housing |
110 mm |
|
Installation width |
52 mm |
|
Installation height |
230 mm |
|
Weight, approx. |
0.9 kg |
|
Product feature of the housing housing for side-by-side mounting |
Yes |
|
Type of mounting wall mounting |
Yes |
|
Type of fixing cap rail mounting |
Yes |
|
Type of mounting S7-300 rail mounting |
No |
|
Installation |
Snaps onto DIN rail EN 60715 35x7.5/15, wall mounting |