Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/new/cat.php on line 184
Order No. |
6EP1 621-2BA00 |
Technical specifications |
|
Product |
SITOP DC/DC |
Power supply, type |
12 V/2,5 A |
Input |
|
Input |
DC voltage PELV/SELV |
Supply voltage at DC |
24 |
Input voltage at DC |
18.5 … 30.2 V |
Input current at nominal level of the input voltage 24 V nominal value |
2.5 A |
Switch-on current limiting (+25 °C), max. |
20 A |
Duration of current limiting at 25 °C typical |
5 ms |
Built-in incoming fuse |
not accessible |
Protection in the mains power input (IEC 898) |
Recommended miniature circuit breaker: 10 A, characteristic B |
Output |
|
Output |
controlled, isolated DC voltage |
Rated voltage Vout DC |
12 V |
Total tolerance, static ± |
3 % |
Static mains compensation, approx. |
0.1 % |
Static load balancing, approx. |
0.4 % |
Residual ripple peak-peak, max. |
100 mV |
Residual ripple peak-peak, typ. |
50 mV |
Spikes peak-peak, max. (bandwidth: 20 MHz) |
200 mV |
Spikes peak-peak, typ. (bandwidth: 20 MHz) |
50 mV |
Adjustment range |
12 … 14 V |
Product feature output voltage adjustable |
Yes |
Output voltage setting |
via potentiometer |
Status display |
Green LED for 12 V OK |
Startup delay, max. |
0.5 s |
Voltage rise, typ. |
300 ms |
Rated current value Iout rated |
2.5 A |
Current range |
0 … 2.5 A |
short-term overload current at short-circuit during run-up typical |
3.3 A |
constant overload current at short-circuit during run-up typical |
3.3 A |
short-term overload current at short-circuit during operation typical |
3.3 A |
constant overload current at short-circuit during operation typical |
3.3 A |
Parallel switching for enhanced performance |
Yes |
Numbers of parallel switchable units for enhanced performance |
2 |
Efficiency |
|
Efficiency at Vout rated, Iout rated, approx. |
83 % |
Power loss at Vout rated, Iout rated, approx. |
6.1 W |
Closed-loop control |
|
Dynamic mains compensation (Vin rated ±15 %), max. |
0.5 % |
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. |
3 % |
Load step setting time 50 to 100%, typ. |
5 ms |
Load step setting time 100 to 50%, typ. |
2 ms |
Setting time maximum |
5 ms |
Protection and monitoring |
|
Output overvoltage protection |
< 24 V |
Current limitation |
3 … 3.6 A |
Current limitation, typ. |
3.3 A |
Characteristic feature of the output short-circuit protected |
Yes |
Short-circuit protection |
Constant current characteristic approx. 3.2 A |
Enduring short circuit current Effective level typical |
3.2 A |
Overload/short-circuit indicator |
LED red for "overload" |
Safety |
|
Primary/secondary isolation |
Yes |
Potential separation |
Safety extra low output voltage Vout according to EN 60950-1 |
Protection class |
Class II |
CE mark |
Yes |
UL/CSA approval |
Yes |
UL/cUL (CSA) approval |
cCSAus (UL 508, CSA22.2-107, UL60950-1, CSA22.2-60950-1) |
Explosion protection |
- |
FM approval |
No |
FM approval |
- |
CB approval |
No |
Marine approval |
- |
Degree of protection (EN 60529) |
IP20 |
EMC |
|
Emitted interference |
EN 55022 Class B |
Supply harmonics limitation |
- |
Noise immunity |
EN 61000-6-2 |
Operating data |
|
Ambient temperature |
|
|
0 … 60 °C |
|
with natural convection |
Ambient temparature |
|
|
-40 … +85 °C |
Ambient temparature |
|
|
-40 … +85 °C |
Humidity class according to EN 60721 |
Climate class 3K3, no condensation |
Mechanics |
|
Connection technology |
screw-type terminals |
Connections |
|
|
+, -: 1 screw terminal each for 0.5 ... 2.5 mm |
|
+, -: 2 screw terminals each for 0.5 ... 2.5 mm |
|
- |
Width of the housing |
32.5 mm |
Height of the housing |
125 mm |
Depth of the housing |
125 mm |
Installation width |
32.5 mm |
Installation height |
225 mm |
Weight, approx. |
0.32 kg |
Product feature of the housing housing for side-by-side mounting |
Yes |
Type of mounting wall mounting |
No |
Type of fixing cap rail mounting |
Yes |
Type of mounting S7-300 rail mounting |
No |
Installation |
Snaps onto DIN rail EN 60715 35x7.5/15 |