Модули DC-UPS с модулями батарей

The following timing diagrams show examples of the characteristic of the input and output voltage at the terminals of the DC-UPS module as well as the signal characteristic of the alarm signals (relays) and of the remote signal (port).

"Long" power failure with DC UPS without serial or USB port (Fig. 1)

Power restoration only once buffer time tp has expired (t3 follows t4):

Upon failure of the input voltage on the DC UPS module (time t1), the battery "Bat" immediately takes over the DC supply, and the output voltageVout is then retained absolutely without interruption.

The isolated changeover contact "OK/Bat" switches over to its off position "Bat".

At the same point in time t1, the buffer time tp set on the DIP switches is started automatically.

The fact that the DIP switch is set to "Interruption outputVout" in this example has no effect because the input voltage returns at time t3 only once the set buffer time (time t4) has expired.

"Short" power failure with DC UPS without serial or USB interface (Fig. 2)

Power restoration before buffer time tp has expired (t3 before t4):

Upon failure of the input voltage on the DC UPS module (time t1), the battery "Bat" immediately takes over the DC supply, and the output voltageVout is then retained absolutely without interruption.

The isolated changeover contact "OK/Bat" switches over to its off position "Bat".

At the same point in time t1, the buffer time tp set on the DIP switches is started automatically.

With the DIP switch set to "Interruption outputVout", the output voltageVout is automatically interrupted for 5 s once the set buffer time tp (time t4) has expired.

The battery has already been disconnected because the input voltage has returned at the time t3.

If the DIP switch is not set to "Interruption outputVout", there is no interruption in this example because the input voltage has already returned at time t3 prior to expiry of the set buffer time (time t4).

Figure 1 "Long power failure"

Figure 2 "Short power failure"

DC UPS without serial or USB port (6EP1 931-2DC21/-2EC21/-2FC21)

DIP switch settings on device: buffer time tp (from 5 s to 635 s with bottom row nos. 2 to 7) /
t = according to setting (with bottom row no. 1 to left) / xxxx = with setting for interruptionVout(with bottom row no. 8 to left)

Legend:

V in: Input voltage at terminals X1.1 – X1.2

V out: Output voltage at terminals X1.3 – X1.4 and X1.5 - X1.6

ok: Signal for input voltageVin OK or above the set battery connection threshold

Bat: signal for battery operation (batteries connected to output, batteries power the load)

Remote: Signal for remote timer start with signal level = 0 at pin 7 of 9-pin serial interface (pin 7 is usually the positive power supply for the interface)

t1: Input voltageVin missing or falls below set connection threshold

t2: Buffer time set on DIP switches is started by remote timer start (signal level = 0)

t3: Input voltageVin rises above set connection threshold

t4: End of set buffer time (output is switched off and/or battery is disconnected)

t5: Output is connected again 5 s after shutdown

tp: Buffer time set on the DIP switches (bottom row nos. 2 to 7)

"Long" power failure with DC UPS with serial or USB interface (Fig. 3)

Power restoration only once buffer time tp has expired (t3 follows t4):

Upon failure of the input voltage on the DC UPS module (time t1), the battery "Bat" immediately takes over the DC supply, and the output voltageVout is then retained absolutely without interruption.

The isolated changeover contact "OK/Bat" switches over to its off position "Bat".

The buffer time tp set on the DIP switches is started at the user-selectable time t2 by means of the signal "Remote timer start" (signal level = 0 at pin 7 of the 9-pin serial interface following previous signal chart according to operating instructions).

The fact that the DIP switch is set to "Interruption outputVout" in this example has no effect because the input voltage returns at time t3 only once the set buffer time (time t4) has expired.

Note: Without a remote signal level = 0 with a setting t = max. duration, there is no interruption to the output voltage in this case because the set buffer time is not started (or interruption only if the exhaustive discharge protection disconnects the accumulator and the input voltage has not returned by then).

"Short" power failure with DC UPS with serial or USB port (Fig. 4)

Power restoration before buffer time tp has expired (t3 before t4):

Upon failure of the input voltage on the DC UPS module (time t1), the battery "Bat" immediately takes over the DC supply, and the output voltageVout is then retained absolutely without interruption.

The isolated changeover contact "OK/Bat" switches over to its off position "Bat".

The buffer time tp set on the DIP switches is started at the user-selectable time t2 by means of the signal "Remote timer start" (signal level = 0 at pin 7 of the 9-pin serial interface following previous signal chart according to operating instructions).

With the DIP switch set to "Interruption outputVout", the output voltageVout is automatically interrupted for 5 s once the set buffer time tp (time t4) has expired.

The battery has already been disconnected because the input voltage has returned at the time t3.

The interruption to the output voltageVout for 5 s permits an automatic restart for many industrial PCs, even if the line voltage (or the input voltageVin on the DC UPS module) returns during shutdown of the PC, as in this example.

Note: Without a remote signal level = 0 with a setting t = max. duration, there is no interruption in the output voltage here because the set buffer time is not started.

Figure 3 "Long power failure"

Figure 4 "Short power failure"

DC UPS with serial or USB port (6EP1 931-2DC31/-2DC42/-2EC31/-2EC42/-2FC42)

DIP switch settings on device: buffer time tp (from 5 s to 635 s with bottom row nos. 2 to 7) /
t = max. time (with bottom row no. 1 to right) / interruption ofVout (with bottom row no. 8 to left)

Legend:

V in: Input voltage at terminals X1.1 – X1.2

V out: Output voltage at terminals X1.3 – X1.4 and X1.5 - X1.6

ok: Signal for input voltageVin OK or above the set battery connection threshold

Bat: signal for battery operation (batteries to output, batteries supply the load)

Remote: Signal for remote timer start with signal level = 0 at pin 7 of 9-pin serial interface (pin 7 is usually the positive power supply for the interface)

t1: input voltageVin missing or falls below set connection threshold

t2: Buffer time set on DIP switches is started by remote timer start (signal level = 0)

t3: input voltageVin rises above set connection threshold

t4: end of set buffer time (output is switched off and/or battery is disconnected)

t5: Output is connected again 5 s after shutdown

tp: buffer time set on the DIP switches (bottom row nos. 2 to 7)























































Каталог оборудования
Каталог продуктов Siemens Industry Приводная техника Техника автоматизации Системы автоматизации Системы визуализации SIMATIC HMI Системы идентификации Промышленные коммуникации SIMATIC NET Промышленные аппараты управления SIRIUS Промышленные информационные технологии Управление на базе РС Промышленные компьютеры SIMATIC Rack PC SIMATIC Box PC Обзор SIMATIC Panel PС Промышленные LCD мониторы RMOS3 real-time operating system SIMATIC Panel PC Компоненты для расширения Системы на флэш-дисках SIMATIC PC USB FlashDrive Дисковод 3,5", USB 1.0 Модули ввода/вывода PC IO Промышленный USB Hub4 Комплект дистанционного управления для SIMATIC Panel PC SIMATIC IPC Image & Partition Creator SIMATIC PC DiagMonitor SIMATIC IPC Remote Manager SIMATIC PC BIOS-Manager SIMATIC ADDM Блоки бесперебойного питания DC-UPS Модули DC-UPS с модулями батарей DC-UPS 6 А DC-UPS 15 DC UPS 40 A Модуль батарей 1.2 Ачас Модуль батарей 2.5 Ачас Модуль батарей 3.2 Ачас Модуль батарей 7 Ачас Модуль батарей 12 Ачас Модули DC-UPS со встроенными конденсаторами Блоки бесперебойного питания DC-UPS Принтеры/устройства ввода/аксессуары MASTERGUARD power supply Заказные продукты Заказные продукты Industrial Microcomputers SICOMP PC-based Automation SIMATIC PC-based Control Встраиваемые системы автоматизации Встраиваемые системы на базе SIMATIC PC Платформы PC/Embedded Управление Визуализация Приводы Распределенный ввод/вывод Компоненты для расширения Системы управления процессом Датчики Блоки питания Продукты для специальных требований Автоматизация зданий Низковольтная коммутационная техника Технология безопасности Системные решения и продукты для отраслей Сервис ... и все, что Вам еще необходимо