Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/new/cat.php on line 184
Cross-duct sensor CD 6
General information |
|
Design |
Transmitter and detector units, connected by a sensor cable |
Materials |
Stainless steel |
Installation |
Horizontally to the optical axis, perpendicular or parallel to the gas flow |
Laser protection class |
Class 1, safe to the eye |
Explosion protection |
Optional, according to ATEX II 1 G Ex ia IIC T4, ATEX II 1 D Ex iaD 20 IP65 T135 °C A defined leak rate can only be guaranteed when using high-pressure window flanges. Otherwise it may be necessary for the owner to carry out an evaluation in accordance with ATEX (DEMKO 06 ATEX 139648X [17]). |
Design, enclosure |
|
Degree of protection |
IP65 |
Dimensions |
Diameter: 163, L: 395 mm |
Purging gas tube in mm |
400 (370 net) x 44 x 40 800 (770 net) x 44 x 40 1 200 (1 170 net) x 44 x 40 |
Weight |
2 x approx. 11 kg |
Mounting |
DN 65/PN 6 or ANSI 4"/150 |
Please note:
|
|
Electrical characteristics |
|
Power supply |
24 V DC, supply from central unit via hybrid cable |
Power consumption |
< 2 W during operation |
Climatic conditions |
|
Ambient temperature |
-30 ... +70 °C during operation, -40 ... +70 °C during storage and transportation |
Humidity |
< 95 % RH, above dew point |
Pressure |
800 ... 1 100 hPa |
Temperature range on the sensor side of the process interface (connection plate) |
-20 … +70 °C |
Measuring conditions |
|
Measurement path |
0.3 ... 12 m (other lengths on request) |
Gas temperatures |
0 ... 1 200 °C, application-dependent |
Gas pressure |
General: 1 013 ± 50 hPa With high-pressure window flanges: High-pressure O2 application AP: 950 ... 5 000 hPa |
Dust load |
The influence of dust is very complex and depends on the path length and particle size. The optical damping increases exponentially at longer path lengths. Smaller particles also have a large influence on the optical damping. With high dust load, long path length and small particle size, the technical support at Siemens should be consulted. |
Accessories
Purging |
|
Nitrogen is permissible as the purging gas for the sensor side. Nitrogen, steam, air and gases which are not subject to the pressure equipment directive Cat. 2 are permissible as purging gases for the process side. |
|
Purging with instrument air, N2 |
|
|
2 000 ... 8 000 hPa |
|
< 500 hPa |
|
|
|
Free of oil and water |
|
Purity better than 99.7 %. For oxygen measurements, and an O2 content < 0.01% in the purging gas (optical path length 1 m, min. 5% oxygen in the process gas) |
|
500 l/min |
|
Benchmark: < -10 °C, condensation on the optics must be avoided |
Blower purging |
|
|
40 hPa |
|
850 l/min |
|
370 W |
|
IP54, cover required to protect against rain |
Steam purging |
|
|
Overheated |
|
240 °C |
|
> 4 000 hPa |
|
16 000 hPa, refers to a volume flow of approx. 1 100 l/min |
Hybrid and sensor cables
General information |
|
Configuration hybrid cable |
Two optical fibers and two twisted copper wires in one cable for 24 V DC. Single-mode optical fiber configured at both ends with E2000 angle connectors. Multimode optical fiber configured at both ends with SMA connectors. |
Cable sheath |
Oil-resistant polyurethane |
Dimensions |
|
|
< 8 mm |
|
|
Impact resistance |
200 N/cm |
Maximum tensile strength |
500 N |
Minimum bending radius |
10 cm |
Climatic conditions |
|
Ambient temperature |
-40 ... +80 °C during operation |
Humidity |
< 95% rel. humidity, above dew point (in operation and storage) |