Pulser with inductive pick-up |
|
Slot initiator |
Sensor SJ 3,5-N-K37 |
Power supply (from SITRANS F RA110) |
8 V DC, Ri approx. 1 k (DIN 19234) Ci = 40 nF; Li = 160 µH |
Change in current consumption on pulse |
1 mA/ 3mA (DIN 19234) |
Permissible line resistance between pick-up and amplifier |
50 (DIN 19234) |
Number of pulses per revolution of the drive |
10 or 100 |
Phase position of the channels of the double pick-up |
180 ° : 180 ° ± 30 ° |
Duty factor |
1 : 1 ± 17 % |
Max. pulse frequency |
3000 Hz |
Pulse valence |
Dependent on value per revolution of the drive of the respective meter |
Permissible ambient temp. |
-25 ... +100 °C (-13 ... +212 °F) |
Degree of protection |
IP43 to EN 60529 with register |
P65 to EN 60529 with protective cover |
|
This pulser has the EC-Type Examination Certificate PTB 99 ATEX 2219X. |
|
Mounting position |
Any |
Weight approx. |
1.2 kg (2.65 lb) |
Ex approval |
IIG EEx ia IIC T6 |