Siemens
СРЕДСТВА ПРОМЫШЛЕННОЙ АВТОМАТИЗАЦИИ
официальный партнер Сименс
Каталог СА01 2012
архивный
(4872) 700-366
skenergo@mail.ru
CP 343-1 Advanced

Bestell-Nr.

6GK7 343-1GX30-0XE0

Product type designation

CP 343-1 Advanced

Transmission rate

Transmission rate

  • at interface 1

10 … 1 000 Mbit/s

  • at interface 2

10 … 100 Mbit/s

Interfaces

Number of electrical connections

  • at interface 1 in accordance with Industrial Ethernet

1

  • at interface 2 in accordance with Industrial Ethernet

2

  • for power supply

1

Design of electrical connection

  • at interface 1 in accordance with Industrial Ethernet

RJ45 port

  • at interface 2 in accordance with Industrial Ethernet

RJ45 port

  • for power supply

2-pin plug-in terminal strip

Design of swap medium C-Plug

Yes

Supply voltage, current consumption, power loss

Type of power supply

DC

Power supply

  • 1 from backplane bus

5 V

  • External

24 V

Relative positive tolerance at 24 V DC

20 %

Relative negative tolerance at 24 V DC

15 %

Current consumed

  • from backplane bus at 5 V DC, typical

0.14 A

  • from external power supply with 24 V DC

    • Typical

0.48 A

    • Maximum

0.62 A

Effective power loss

14.7 W

Permitted ambient conditions

Ambient temperature

  • with vertical installation during operating phase

0 … 40 °C

  • with horizontal installation during operating phase

0 … 60 °C

  • During storage

-40 … +70 °C

  • During transport

-40 … +70 °C

Relative humidity at 25 °C without condensation during operating phase, maximum

95 %

IP degree of protection

IP 20

Design, dimensions and weights

Module format

Compact module S7-300 double width

Width

80 mm

Height

125 mm

Depth

120 mm

Net weight

0.6 kg

Type of mounting: S7-300 DIN rail mounting

-

Performance data

Performance dataOpen communication

Number of possible connections for open communication by means of SEND/RECEIVE blocks, maximum

16

Data volume

  • as user data per ISO connection for open communication by means of SEND/RECEIVE blocks, maximum

8 KB

  • as user data per ISO on TCP connection for open communication by means of SEND/RECEIVE blocks, maximum

8 KB

  • as user data per TCP connection for open communication by means of SEND/RECEIVE blocks, maximum

8 KB

  • as user data per UDP connection for open IE communication by means of SEND/RECEIVE blocks, maximum

2 KB

Number of multicast stations

16

Performance dataS7 communication

Maximum number of possible connections for S7 communication

16

Number of possible connections for S7 communication - Note

-

Performance dataMultiprotocol operation

Number of active connections in multiprotocol mode

48

Performance dataIT functions

Number of possible connections

  • as client with FTP, maximum

10

  • as server

    • with FTP, maximum

2

    • with HTTP, maximum

4

  • as e-mail client, maximum

1

Data volume as user data for e-mail, maximum

8 KB

Storage capacity of user memory

  • as flash memory file system

28 Mibyte

  • as RAM

30 Mibyte

Number of possible write cycles of flash memory cells

100 000

Performance dataPROFINET communicationas PN IO Controller

Total number of PN IO Devices which can be operated on the PROFINET IO Controller

128

Number of PN IO IRT Devices which can be operated on the PROFINET IO Controller

32

Number of external PN IO lines with PROFINET, per rack

1

Data volume

  • As user data for input variables as PROFINET IO Controller, maximum

4 KB

  • As user data for output variables as PROFINET IO Controller, maximum

4 KB

  • As user data for input variables per PN IO Device as PROFINET IO Controller, maximum

240 byte

  • As user data for output variables per PN IO Device as PROFINET IO Controller, maximum

240 byte

  • As user data for input variables per PN IO Device as PROFINET IO Controller, maximum

-

  • As user data for output variables per PN IO Device as PROFINET IO Controller, maximum

-

Performance dataPROFINET communicationas PN IO Device

Product function: PROFINET IO Device

-

Data volume

  • As user data for input variables as PROFINET IO Device, maximum

1 024 byte

  • As user data for output variables as PROFINET IO Device, maximum

1 024 byte

  • As user data for input variables per submodule as PROFINET IO Device

240 byte

  • As user data for output variables per submodule as PROFINET IO Device

240 byte

  • As user data for the consistency area per submodule

240 byte

Number of submodules per PROFINET IO Device

32

Performance dataPROFINET CBA

Number of remote connection partners with PROFINET CBA

64

Total number of connections with PROFINET CBA

1 000

Data volume

  • As user data for digital inputs with PROFINET CBA, maximum

8 KB

  • As user data for digital outputs with PROFINET CBA, maximum

8 KB

  • As user data for arrays and data types

    • with acyclic transmission with PROFINET CBA, maximum

8 KB

    • with cyclic transmission with PROFINET CBA, maximum

250 byte

    • with local connection with PROFINET CBA, maximum

2 400 byte

Performance dataPROFINET CBAremote connectionwith acyclic transmission

Send cycle of remote connections with acyclic transmission with PROFINET CBA

100 ms

Number of remote connections with input variables with acyclic transmission with PROFINET CBA, maximum

128

Number of remote connections with output variables with acyclic transmission with PROFINET CBA, maximum

128

Data volume

  • as user data for remote connections with input variables with acyclic transmission with PROFINET CBA

8 KB

  • as user data for remote connections with output variables with acyclic transmission with PROFINET CBA

8 KB

Performance dataPROFINET CBAremote connectionwith cyclic transmission

Send cycle of remote connections with cyclic transmission with PROFINET CBA

8 ms

Number of remote connections with input variables with cyclic transmission with PROFINET CBA, maximum

200

Number of remote connections with output variables with cyclic transmission with PROFINET CBA, maximum

200

Data volume

  • as user data for remote connections with input variables with cyclic transmission with PROFINET CBA, maximum

2 000 byte

  • as user data for remote connections with output variables with cyclic transmission with PROFINET CBA, maximum

2 000 byte

Performance dataPROFINET CBAHMI variables via PROFINET,acyclic

Number of HMI stations for logging-on for HMI variables with acyclic transmission with PROFINET CBA

3

Send cycle of HMI variables with acyclic transmission with PROFINET CBA

500 ms

Number of HMI variables with acyclic transmission with PROFINET CBA, maximum

200

Data volume as user data for HMI variables with acyclic transmission with PROFINET CBA, maximum

8 KB

Performance dataPROFINET CBAdevice-internal connections

Maximum number of internal connections with PROFINET CBA

256

Data volume of internal connections with PROFINET CBA, maximum

2 400 byte

Maximum number of connections with constants with PROFINET CBA

200

Data volume as user data for connections with constants with PROFINET CBA, maximum

4 096 byte

Performance dataPROFINET CBAPROFIBUS proxy functionality

Performance data with PROFINET CBA PROFIBUS proxy functionality

No

Product functionsManagement, configuration, programming

Product function: MIB support

Yes

Protocol is supported

  • SNMP v1

Yes

  • DCP

Yes

  • LLDP

Yes

Configuration software

  • Required

STEP 7 V5.4 SP4 and higher

  • Required for PROFINET CBA

SIMATIC IMAP V3.0 SP1 and higher

Product functionsDiagnostics

Product function: Web-based diagnostics

Yes

Product functionsSwitch

Product feature: Switch

Yes

Product function

  • Switch-managed

No

  • with IRT PROFINET IO Switch

Yes

  • Configuration with STEP 7

Yes

Product functionsRedundancy

Product function

  • Ring redundancy

Yes

  • Redundancy manager

Yes

  • Redundancy procedure MRP

Yes

Product functionsSecurity

Product function

  • Password protection for Web applications

Yes

  • ACL - IP based

Yes

  • ACL - IP based for PLC/routing

Yes

  • Switching-off non-required services

Yes

  • Blocking of communication via physical ports

Yes

  • Log file for unauthorized access

No

Product functionsTime

Product function

  • SICLOCK support

Yes

  • Passing-on of time synchronization

Yes

NTP Protocol is supported

Yes
























































Каталог оборудования 2012
Каталог продуктов Siemens Industry Приводная техника Техника автоматизации Системы автоматизации Системы визуализации SIMATIC HMI Системы идентификации Промышленные коммуникации SIMATIC NET ECOFAST Введение Industrial Ethernet Введение Передача данных Обзор коммуникаций Топологии Критерии выбора типа сети Сетевые компоненты для Industrial Ethernet Industrial Ethernet коммутаторы Активные сетевые компоненты Безопасность передачи данных в промышленных сетях Системные интерфейсы SIMATIC S7 Модули связи для SIMATIC S7-200 Модуля связи для SIMATIC S7-1200 Модули связи для SIMATIC S7-300 Коммутатор CSM 377 CP 343-1 Lean SIPLUS CP 343-1 Lean CP 343-1 SIPLUS CP 343-1 CP 343-1 Advanced SIPLUS CP 343-1 Advanced CP 343-1 ERPC CP 343-1 BACnet TIM 3V-IE для глобальных сетей и Ethernet SIPLUS TIM 3V-IE TIM 3V-IE Advanced для WAN и Ethernet TIM 4R-IE для WAN и Ethernet Коммуникационные процессоры Модули связи для SIMATIC S7-mEC Устройства программирования PG/PC Системные интерфейсы для SIMATIC HMI Аксессуары Управление сетью Сетевые переходы Решения партнеров PROFINET PROFIBUS AS-интерфейс IO-Link Промышленная беспроводная связь SINAUT ST7 Сетевые переходы ECOFAST Промышленные аппараты управления SIRIUS Промышленные информационные технологии Управление на базе РС Системы управления процессом Датчики Блоки питания Продукты для специальных требований Автоматизация зданий Низковольтная коммутационная техника Технология безопасности Системные решения и продукты для отраслей Сервис ... и все, что Вам еще необходимо

  © ООО "СК ЭНЕРГО" 2007-2022
  (4872) 700-366
Яндекс.Метрика