Y-link for S7-400H

Y-Link

  • Transmission rates for the redundant master system:
    9.6 Kbit/s to 12 Mbit/s.
  • Bumpless switchover of the redundant PROFIBUS DP master system's active channel.
  • Supports system changes on a SIMATIC S7-400H during operation.
  • Diagnostics using LEDs and the user program

Y-Coupler

  • Transmission rates for the lower-level master system (independent of redundant DP master system):
    187.5 Kbit/s to 12 Mbit/s.
  • Electrical isolation between lower-level DP master system and power supply via the coupler.
  • Degree of protection IP20
Principle of operation

The Y-Link maps the lower-level DP master system on the redundant PROFIBUS DP master system as a switched PROFIBUS DP slave .

The Y-Coupler and the lower-level DP master system form an independent bus system and operate decoupled from the redundant bus system.

The Y-Link as a DP slave on the redundant DP master system acts as a proxy for the stations on the lower-level DP master system with regard to data.

Configuration

The Y-Link can be configured with STEP 7 as of Version 5.2. It is not necessary to configure the Y-Coupler.

When STEP 7 calculates the bus parameters, the stations connected on the lower-level DP master system as well as the Y-Link itself are taken into account.

Parameter assignment for the DP slaves

The redundant DP master system assigns the parameters for the DP slaves in the lower-level DP master system via the Y-Link.