SITRANS P MPS pressure measurement transmitter (submersible sensor) |
|
Mode of operation |
|
Measuring principle |
piezo-resistive |
Input |
|
Measured variable |
Hydrostatic level |
Measuring range |
Maximum operating pressure |
|
|
|
|
|
|
|
|
|
|
|
|
Output |
|
Output signal |
4 ... 20 mA |
Measuring accuracy |
According to IEC 60770-1 |
Error in measurement at limit setting incl. hysteresis and reproducibility |
0.3% of full-scale value (typical) |
Influence of ambient temperature |
|
Zero and span |
|
|
0.45 %/10 K of full-scale value |
|
0.3 %/10 K of full-scale value |
Long-term stability |
|
Zero and span |
|
|
0.25 % of full-scale value/year |
|
0.2 % of full-scale value/year |
Rated conditions |
|
Ambient conditions |
|
|
-10 ... +80 °C (+14 ... +176 °F) |
|
-40 ... +100 °C (-40 ... +212 °F) |
Degree of protection to IEC 60529 |
IP68 |
Design |
|
Weight |
|
|
0.4 kg ( 0.88 lb) |
|
0.08 kg/m ( 0.054 lb/ft) |
Electrical connection |
Cable with 2 conductors with screen and vent pipe, strength cord (max. 300 N (67.44 lbf)) |
Material |
|
|
Stainless steel, mat. no. 316L/316 Ti |
|
Stainless steel, mat. no. 316L/316 Ti |
|
Viton |
|
Either |
Auxiliary power supply |
|
Terminal voltage on pressure transmitterUB |
10 ... 33 V DC |
Certificates and approvals |
|
The transmitter is not subject to the pressure equipment directive (PED 97/23/EC) |
|
Explosion protection |
|
|
TUV 03 ATEX 2004X |
|
Ex II 1 G EEx ia IIC T4 |
Junction box |
|
Application |
for connecting the transmitter cable |
Design |
|
Weight |
0.2 kg (0.44 lb) |
Electrical connection |
2 x 3-way (28 to 18 AWG) |
Cable entry |
2 x M20x1.5 |
Enclosure material |
polycarbonate |
Vent pipe for atmospheric pressure |
|
Screw for cable strength cord |
|
Rated conditions |
|
Degree of protection to IEC 60529 |
IP54 |
Cable hanger |
|
Application |
for mounting the transmitter |
Design |
|
Weight |
0.16 kg (0.35 lb) |
Material |
Galvanized steel, polyamide |