Siemens
СРЕДСТВА ПРОМЫШЛЕННОЙ АВТОМАТИЗАЦИИ
официальный партнер Сименс
Каталог СА01 2012
архивный
(4872) 700-366
skenergo@mail.ru
SITRANS P300 for gauge and absolute pressure

SITRANS P300 for gauge and absolute pressure

HART

PROFIBUS PA and FOUNDATION Fieldbus

Gauge pressure input

Measured variable

Gauge pressure

Spans (infinitely adjustable) or nominal measuring range and
max. permissible test pressure

Span (min. ... max.)

Max. perm. test pressure

Nominal measuring range

Max. perm. test pressure

0.01 ... 1 bar g
(0.15 ... 14.5 psi g)

6 bar g
(87 psi g)

1 bar g
(14.5 psi g)

6 bar g
(87 psi g)

0.04 ... 4 bar g
(0.58 ... 58 psi g)

10 bar g
(145 psi g)

4 bar g
(58 psi g)

10 bar g
(145 psi g)

0.16 ... 16 bar g
(2.3 ... 232 psi g)

32 bar g
(464 psi g)

16 bar g
(232 psi g)

32 bar g
(464 psi g)

0.6 ... 63 bar g
(9.1 ... 914 psi g)

100 bar g
(1450 psi g)

63 bar g
(914 psi g)

100 bar g
(1450 psi g)

1.6 ... 160 bar g
(23.2 ... 2321 psi g)

250 bar g
(3626 psi g)

160 bar g
(2321 psi g)

250 bar g
(3626 psi g)

4.0 ... 400 bar g
(58 ... 5802 psi g)

600 bar g
(8700 psi g)

400 bar g
(5802 psi g)

600 bar g
(8700 psi g)

Depending on the process connection, the span may differ from these values

Depending on the process connection, the nominal measuring range may differ from these values

Lower measuring limit

  • Measuring cell with silicone oil

30 mbar a (0.44 psi a)

Upper measuring limit

  • Measuring cell with silicone oil

100% of max. span

100 % of the max. nominal measuring range

Absolute pressure input

Measured variable

Absolute pressure

Spans (infinitely adjustable) or nominal measuring range and
max. permissible test pressure

Span (min. ... max.)

Max. perm. test pressure

Nominal measuring range

Max. perm. test pressure

8 ... 250 mbar a
(0.12 ... 3.63 psi a)

6 bar a
(87 psi a)

250 mbar a
(3.63 psi a)

6 bar a
(87 psi a)

43 ... 1300 mbar a
(0.62 ... 18.9 psi a)

10 bar a
(145 psi a)

1.30 bar a
(19 psi a)

10 bar a
(145 psi a)

0.16 ... 5 bar a
(2.3 ... 73 psi a)

30 bar a
(435 psi a)

5 bar a
(73 psi a)

30 bar a
(435 psi a)

1 ... 30 bar a
(14.5 ... 435 psi a)

100 bar a
(1450 psi a)

30 bar a
(435 psi a)

100 bar a
(1450 psi a)

Lower measuring limit

  • Measuring cell with silicone oil

0 mbar a (0 psi a)

Upper measuring limit

  • Measuring cell with silicone oil

100% of max. span

100 % of the max. nominal measuring range

Input of gauge pressure, with flush-mounted diaphragm

Measured variable

Gauge pressure, flush-mounted

Spans (infinitely adjustable) or nominal measuring range and max. permissible test pressure

Span (min. ... max.)

Max. perm. test pressure

Nominal measuring range

Max. perm. test pressure

0,01 ... 1 bar g (0.15 ... 14.5 psi g)

6 bar g
(87 psi g)

1 bar g
(14.5 psi g)

6 bar g
(87 psi g)

0,04 ... 4 bar g (0.58 ... 58 psi g)

10 bar g
(145 psi g)

4 bar g
(58 psi g)

10 bar g
(145 psi g)

0,16 ... 16 bar g (2.32 ... 232 psi g)

32 bar g
(464 psi g)

16 bar g
(232 psi g)

32 bar g
(464 psi g)

0,6 ... 63 bar g (9.14 ... 914 psi g)

100 bar g
(1450 psi g)

63 bar g
(914 psi g)

100 bar g
(1450 psi g)

Lower measuring limit

100 mbar a (1.45 psi a)

Upper measuring limit

  • Measuring cell with silicone oil

100% of max. span

100 % of the max. nominal measuring range

Input of absolute pressure, with flush-mounted diaphragm

Measured variable

Absolute pressure, flush-mounted

Spans (infinitely adjustable) or nominal measuring range and
max. permissible test pressure

Span (min. ... max.)

Max. perm. test pressure

Nominal measuring range

Max. perm. test pressure

43 ... 1300 mbar a
(0.62 ... 18.85 psi a)

10 bar a
(145 psi a)

1300 mbar a
(18.85 psi a)

10 bar a
(145 psi a)

0.16 ... 5 bar a
(2.32 ... 72.5 psi a)

30 bar a
(435 psi a)

5 bar a
(72.5 psi a)

30 bar a
(435 psi a)

1 ... 30 bar a
(14.5 ... 435 psi a)

100 bar a
(1450 psi a)

30 bar a
(435 psi a)

100 bar a
(1450 psi a)

Depending on the process connection, the span may differ from these values

Depending on the process connection, the nominal measuring range may differ from these values

Lower measuring limit

0 bar a (0 psi a)

Upper measuring limit

  • Measuring cell with silicone oil

100% of max. span

100 % of the max. nominal measuring range

Output

Output signal

4 ... 20 mA

Digital PROFIBUS PA signal

Physical bus

-

IEC 61158-2

Protection against polarity reversal

Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage.

Electrical damping (step width 0.1 s)

Set to 2 s (0 ... 100 s)

Measuring accuracy

According to IEC 60770-1

Reference conditions
(All error data refer always refer to the set span)

Rising characteristic curve, start-of-scale value 0 bar, stainless steel seal diaphragm, measuring cell with silicone oil, room temperature 25 °C (77 °F), span ratio (r = max. span / set span)

Error in measurement at limit setting incl. hysteresis and reproducibility

Gauge pressure

Absolute pressure

Absolute pressure, flush-mounted

Gauge pressure

Absolute pressure

Absolute pressure, flush-mounted

Linear characteristic

0,075 %

0,1 %

0,2 %

  • r 10

(0.0029 · r + 0.071) %

0,1 %

0,2 %

  • 10 < r 30

(0.0045 · r + 0.071) %

0,2 %

0,4 %

  • 30 < r 100

(0.005 · r + 0.05) %

-

-

Step response time T63

approx. 0.2 NO

Long-term stability at ± 30 °C (± 54 °F)

(0.25 · r) %/5 years

(0.1 · r) %/year

0.25 %/5 years

0.1 %/year

Influence of ambient temperature

  • at -10 ... +60 °C (14 ... 140 °F)

(0.08· r + 0.1) %

(0.2 · r + 0.3) %

0,3 %

0,5 %

Conversion of temperature error per 28 °C. Valid for temperature range -3 ... +53 °C < (0.064. r + 0.08) % / 28 °C (50 °F).

  • at -40 ... -10 °C and +60 ... +85 °C
    (-40 ... 14 °F and 140 ... 185 °F)

(0.1 · r + 0.15) %/10 K

(0.2 · r + 0.3) %/10 K

0.25 %/10 K

0.5 %/10 K

Influence of the medium temperature (only with flush-mounted diaphragm)

  • Temperature difference between medium temperature and ambient temperature

3 mbar/10 K (0.04 psi/10 K)


Rated conditions

Installation conditions

Ambient temperature

Observe the temperature class in areas subject to explosion hazard.

  • Measuring cell with silicone oil

-40 ... +85 °C (-40 ... +185 °F)

  • Measuring cell with Neobee oil (FDA-compliant, with flush-mounted diaphragm)

-10 ... +85 °C (14 ... +185 °F)

  • Measuring cell with inert liquid (not with flush-mounted diaphragm)

-20 ... +85 °C (-4 ... +185 °F)

  • Display readable

-30 ... +85 °C (-22 ... +185 °F)

  • Storage temperature

-50 ... +85 °C (-58 ... +185 °F)
(for Neobee: -20 ... +85 °C (-4 ... +185 °F))

Climatic class

Condensation

Relative humidity 0 ... 100 %
Condensation permissible, suitable for use in the tropics

Degree of protection acc. to EN 60529

IP65, IP68, NEMA X, enclosure cleaning, resistant to lyes, steam to 150 °C (302 °F)

Electromagnetic Compatibility

  • Emitted interference and interference immunity

Acc. to EN 61326 and NAMUR NE 21

Medium conditions

Temperature of medium

  • Measuring cell with silicone oil

-40 ... +100 °C (-40 ... +212 °F)

  • Measuring cell with silicone oil (with flush-mounted diaphragm)

-40 ... +150 °C (-40 ... +302 °F)

  • Measuring cell with Neobee oil (FDA-compliant, with flush-mounted diaphragm)

-10 ... +150 °C (-14 ... +302 °F)

  • Measuring cell with silicone oil, with temperature decoupler (only with flush-mounted diaphragm)

-40 ... +200 °C (-40 ... +392 °F)

  • Measuring cell with inert liquid

-20 ... +100 °C (-4 ... +212 °F)

  • Measuring cell with high-temperature oil

-10 ... +250 °C (14 ... 482 °F)

Design (standard version)

Weight (without options)

Approx. 800 g (1.8 lb)

Enclosure material

Stainless steel, mat. no. 1.4301/304

Material of parts in contact with the medium

  • Connection shank

Stainless steel, mat. no. 1.4404/316L or Hastelloy C276, mat. no. 2.4819

  • Oval flange

Stainless steel, mat. no. 1.4404/316L

  • Seal diaphragm

Stainless steel, mat. no. 1.4404/316L or Hastelloy C276, mat. no. 2.4819

  • Measuring cell filling
  • Silicone oil
  • Inert filling liquid

Process connection

  • G B to EN 837-1
  • Female thread -14 NPT
  • Oval flange PN 160 (MAWP 2320 psi) with fastening thread:
    • 7a „16-20 UNF to IEC 61518
  • M10 as per DIN 19213

Design (version with flush-mounted diaphragm)

Weight (without options)

approx. 1 ... 13 kg (2.2 ... 29 lb)

Enclosure material

Stainless steel, mat. no. 1.4301/304

Material of parts in contact with the medium

  • Process connection

Stainless steel, mat. no. 1.4404/316L

  • Seal diaphragm

Stainless steel, mat. no. 1.4404/316L

  • Measuring cell filling
  • Silicone oil
  • Inert filling liquid
  • FDA compliant fill fluid (Neobee oil)

Process connection

  • Flanges as per EN and ASME
  • F&B and pharmaceutical flanges

Surface quality touched-by-media

Ra-values 0.8 µm (32 µ-inch)/welds Ra) 1.6 µm (64 µ-inch)

(Process connectionsaccording to 3A; Ra-values 0.8 µm (32 µ-inch)/welds Ra) 0.8 µm (32 µ-inch)

Power supply UH

Terminal voltage on transmitter

10.5 ... 42 V DC
for intrinsically safe operation: 10.5 ... 30 V DC

Supplied through bus

Separate power supply

-

Not necessary

Bus voltage

  • Without EEx

-

9 ... 32 V

  • With intrinsically-safe operation

-

9 ... 24 V

Current consumption

  • Max. basic current

-

12.5 mA

  • Start-up current basic current

-

Yes

  • Max. fault current in the event of a fault

-

15.5 mA

Fault disconnection electronics (FDE)

-

Available

Certificates and approvals

Classification according to PED 97/23/EC

For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of Article 3, paragraph 3 (sound engineering practice)

Water, waste water

In preparation

Explosion protection

Intrinsic safety "i"

PTB 05 ATEX 2048

  • Marking

Ex II 1/2 G EEx ia/ib IIB/IIC T4, T5, T6

  • Permissible ambient temperature

  • Temperature class T4

-40 ... +85 °C (-40 ... +185 °F)

  • Temperature class T5

-40 ... +70 °C (-40 ... +158 °F)

  • Temperature class T6

-40 ... +60 °C (-40 ... +140 °F)

  • Connection

To certified intrinsically-safe circuits with peak values:

Ui = 30 V, Ii = 100 mA,
Pi = 750 mW, Ri = 300

To certified intrinsically-safe circuits with peak values:

FISCO supply unit:

Ui = 17.5 V, Ii = 380 mA,
Pi = 5.32 W

Linear barrier:

Ui = 24 V, Ii = 250 mA, Pi = 1.2 W

  • Effective inner capacitance

Ci = 6 nF

Ci = 1.1 nF

  • Effective internal inductance

Li = 0.4 mH

Li 7 H

Explosion protection to FM for USAand Canada (cFMUS)

  • Identification (DIP) or (IS); (NI)

Certificate of Compliance 3025099

CL I, DIV 1, GP ABCD T4 ... T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4 ... T6; CL I, DIV 2, GP ABCD T4 ... T6; CL II, DIV 2, GP FG; CL III

  • Identification (DIP) or (IS)

Certificate of Compliance 3025099C

CL I, DIV 1, GP ABCD T4 ... T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC 4 ... T6; CL I, DIV 2, GP ABCD T4 ... T6; CL II, DIV 2, GP FG; CL III

Dust explosion protection for zone 20/21/22

PTB 05 ATEX 2048

  • Marking

Ex II 1D Ex ia D 20 T 120 °C

Ex II 2D Ex ib D 21 T 120 °C

Ex II 3D Ex ib D 21 T 120 °C

  • Permissible ambient temperature

  • Temperature class T4

-40 ... +85 °C (-40 ... +185 °F) (in the case of mineral glass windows only
-20 ... +85 °C (-4 ... +185 °F))

  • Temperature class T5

-40 ... +70 °C (-40 ... +158 °F) (in the case of mineral glass windows only
-20 ... +70 °C (-4 ... +158 °F))

  • Temperature class T6

-40 ... +60 °C (-40 ... +140 °F) (in the case of mineral glass windows only
-20 ... +60 °C (-4 ... +140 °F))

  • Connection

To certified intrinsically-safe circuits with peak values:

Ui = 30 V, Ii = 100 mA, Pi = 750 mW

To certified intrinsically-safe circuits with peak values:

Ui = 24 V, Ii = 380 mA, Pi = 5.32 W

  • Effective inner capacitance

Ci = 6 nF

Ci = 5 nF

  • Effective internal inductance

Li 0.4 H

Li = 10 H

Type of protection Ex nA/nL/ic (Zone 2)

PTB 05 ATEX 2048

  • Marking

II 2/3 G Ex ic IIB/IIC T4/T5/T6

II 2/3 G Ex nA T4/T5/T6

II 2/3 G Ex nL IIB/IIC T4/T5/T6

  • Permissible ambient temperature

  • Temperature class T4

-40 ... +85 °C (-40 ... +185 °F) (in the case of mineral glass windows only -20 ... +85 °C (-4 ... +185 °F))

  • Temperature class T5

-40 ... +70 °C (-40 ... +158 °F) (in the case of mineral glass windows only -20 ... +70 °C (-4 ... +158 °F))

  • Temperature class T6

-40 ... +60 °C (-40 ... +140 °F) (in the case of mineral glass windows only -20 ... +60 °C (-4 ... +140 °F))

  • Ex nA connection

To certified intrinsically-safe circuits with peak values:

Um = 45 V

To certified intrinsically-safe circuits with peak values:

Um = 32 V

  • Ex ic/nL connection

To certified intrinsically-safe circuits with

peak values:

Ui = 45 V

To certified intrinsically-safe circuits with

peak values:

Ui = 32 V

  • Effective inner capacitance

Ci = 6 nF

Ci = 5 nF

  • Effective internal inductance

Li = 0.4 mH

Li = 20 H


HART communication

HART communication

230 ... 1100 

Protocol

HART Version 5.x

Software for computer

SIMATIC PDM


PROFIBUS PA communication

Simultaneous communication with master class 2 (max.)

4

The address can be set using

Configuration tool or local operation

(standard setting Address 126)

Cyclic data usage

  • Output byte

5 (one measured value) or 10 (two measured values)

  • Input byte

0, 1 or 2 (totalizer mode and reset function for dosing)

  • Internal preprocessing

Device profile

PROFIBUS PA Profile for Process Control Devices Version 3.0, Class B

Function blocks

2

  • Analog input

  • Adaptation to customer-specific process variables

Yes, linearly rising or falling characteristic

  • Electrical damping adjustable

0 … 100 s

  • Simulation function

Input /Output

  • Failure function

parameterizable (last good value, substitute value, incorrect value)

  • Limit monitoring

Yes, one upper and lower warning limit and one alarm limit respectively

  • Register (totalizer)

Can be reset, preset, optional direction of counting, simulation function of register output

  • Failure mode

parameterizable (summation with last good value, continuous summation, summation with incorrect value)

  • Limit monitoring

One upper and lower warning limit and one alarm limit respectively

  • Physical block

1

Transducer blocks

2

  • Pressure transducer block

  • Can be calibrated by applying two pressures

Yes

  • Monitoring of sensor limits

Yes

  • Specification of a container characteristic with

Max. 30 nodes

  • Simulation function for measured pressure value and sensor temperature

Constant value or over parameterizable ramp function


FOUNDATION Fieldbus communication

Function blocks

3 function blocks analog input, 1 function block PID

  • Analog input

  • Adaptation to customer-specific process variables

Yes, linearly rising or falling characteristic

  • Electrical damping adjustable

0 & 100 s

  • Simulation function

Output/input (can be locked within the device with a bridge)

  • Failure mode

parameterizable (last good value, substitute value, incorrect value)

  • Limit monitoring

Yes, one upper and lower warning limit and one alarm limit respectively

  • Square-rooted characteristic for flow measurement

Yes

  • PID

Standard FOUNDATION Fieldbus function block

  • Physical block

1 resource block

Transducer blocks

1 transducer block Pressure with calibration, 1 transducer block LCD

  • Pressure transducer block

  • Can be calibrated by applying two pressures

Yes

  • Monitoring of sensor limits

Yes

  • Simulation function: Measured pressure value, sensor temperature and electronics temperature

Constant value or over parameterizable ramp function
























































Каталог оборудования 2012
Каталог продуктов Siemens Industry Приводная техника Техника автоматизации Системы автоматизации Системы визуализации SIMATIC HMI Системы идентификации Промышленные коммуникации SIMATIC NET Промышленные аппараты управления SIRIUS Промышленные информационные технологии Управление на базе РС Системы управления процессом Датчики Контрольно-измерительные приборы Pressure gauge Transmitter for gauge, absolute and differ. pressure, flow and level Measurement transducer for basic requirements Transmitter with WirelessHART communication Transmitters for food, pharmaceuticals and biotechnology SITRANS P300 for gauge and absolute pressure Accessories Transmitter for gauge pressure for the paper industry Transmitter for general requirements Transmitter for high-end requirements Remote seals for transmitters and pressure gauges Fittings Датчики давления Приборы измерения температуры SITRANS T Расходомеры Уровнемеры Расходомеры и счетчики Позиционеры Устройство для защиты и пуска двигателей SIMOCODE-DP Блок питания/искробезопасной развязки датчиков SITRANS I Источники питания и разделители Сигнализаторы сбоев в промышленном процессе Аппаратные ПИД-регуляторы SIPART Встраиваемые самописцы и индикаторы Коммуникации и программное обеспечение Анализаторы процесса Технологии взвешивания Датчики зрения Блоки питания Продукты для специальных требований Автоматизация зданий Низковольтная коммутационная техника Технология безопасности Системные решения и продукты для отраслей Сервис ... и все, что Вам еще необходимо

  © ООО "СК ЭНЕРГО" 2007-2022
  (4872) 700-366
Яндекс.Метрика