General technical data |
||||
---|---|---|---|---|
Relevant standards |
||||
EN 50178 |
Electronic equipment for use in power installations |
|||
EN 50274 |
Low-voltage switchgear and controlgear assemblies: Protection against electric shock – Protection against unintentional direct contact with hazardous live parts |
|||
EN 60146-1-1 |
Semiconductor converters: General requirements and line-commutated converters; specification of basic requirements |
|||
EN 61800-1 |
Adjustable speed electrical power drive systems, Part 1 – (DC drives) General requirements - Rating specifications for low-voltage DC power drive systems |
|||
EN 61800-3 |
Adjustable speed electrical power drive systems, Part 3 – EMC product standard including specific test methods |
|||
EN 61800-5-1 |
Adjustable speed electrical power drive systems – Part 5-1: Requirements regarding safety – electrical, thermal, and energy requirements |
|||
IEC 62103 (identical to EN 50178) |
Electronic equipment for use in power installations |
|||
UBC 97 |
Uniform Building Code |
|||
Electrical specifications |
||||
Overvoltage category |
Category II acc. to EN 61800-5-1 within the line supply circuits |
|||
Overvoltage strength |
Class 1 acc. to EN 50178 |
|||
Radio interference suppression |
No radio interference suppression according to EN 61800-3 |
|||
Mechanical data |
||||
Degree of protection |
IP00 acc. to EN 60529; IP20 with accessories "Mounting kit to upgrade to IP20" for units up to 850 A |
|||
Protection class |
Class 1 acc. to EN 61140 |
|||
Cooling method |
||||
|
Self-ventilated |
|||
|
Forced-air cooling with integrated fan |
|||
Closed-loop control stability |
||||
|
n = 0.006 % of the rated motor speed |
|||
|
n = 0.1 % of the rated motor speed |
|||
MTBF |
> 170 000 h |
|||
Environmental conditions |
||||
Permissible ambient temperature during storage and transport |
-40 ... +70 °C |
|||
Permissible humidity |
Relative humidity 95 % (75 % at 17 °C average annual value, 95 % at 24 °C max., condensation not permissible) |
|||
Climate class |
3K3 acc. to EN 60721-3-3 |
|||
Insulation |
Pollution degree 2 according to EN 61800-5-1 |
|||
Installation altitude |
1 000 m above sea level (100 % load capability) |
|||
Mechanical strength |
Storage |
Transport |
Operation |
|
Vibratory load |
1M2 acc. to EN 60721-3-1 |
2M2 acc. to EN 60721-3-2 |
Constant deflection: |
|
Shock load |
1M2 acc. to EN 60721-3-1 |
2M2 acc. to EN 60721-3-2 |
100 m/s2 at 11 ms (testing and measuring techniques acc. to EN 60068-2-27, Ea) |
|
Approvals |
||||
UL/cUL |
UL file No.: E203250 |
|||
UL 508 C |
Certification of the units up to and including 575 V |
|||
GOST |
||||
Lloyd s Register |
In order to maintain the important limit values for marine certification, radio interference suppression filters should be used (see "Accessories and supplementary components") and option M08 should be selected (coated PCBs). |
|||
Det Norske Veritas |
||||
American Bureau of Shipping |
||||
Germanische Lloyd |
1)Conditions:
The closed-loop control (PI control) stability is referred to the rated motor speed and applies when the SINAMICS DC MASTER is in the warm operating condition. This is based on the following preconditions:
- Temperature changes of ±10 °C
- Line supply voltage changes of +10 % / -5 % of the rated input voltage
- Temperature coefficient of the tachometer generator with temperature compensation 0.15 ‰ every 10 °C (for analog tachometer generators only)
- Constant setpoint
SINAMICS DC MASTER converters for 400 V 3 AC, 60 to 280 A, two-quadrant operation
Type |
||||||
---|---|---|---|---|---|---|
6RA8025-6DS22-0AA0 |
6RA8028-6DS22-0AA0 |
6RA8031-6DS22-0AA0 |
6RA8075-6DS22-0AA0 |
6RA8078-6DS22-0AA0 |
||
Rated armature supply voltage1) |
V |
400 V 3 AC |
||||
Rated armature input current |
A |
50 |
75 |
104 |
174 |
232 |
Rated supply voltage, electronics power supply |
V |
380 (-25 %) … 480 V (+10 %) 2 AC;In = 1 A or |
||||
Rated fan supply voltage |
V |
Self-ventilated |
24 V DC internal |
|||
Rated fan current |
A |
Internal supply |
||||
Air flow |
m3/h |
300 |
||||
Sound pressure level2) |
dB (A) |
52.4 |
||||
Rated field supply voltage1) |
V |
400 V 2 AC |
||||
Rated frequency |
Hz |
45 … 65 |
||||
Rated DC voltage 1) |
V |
485 |
||||
Rated DC current |
A |
60 |
90 |
125 |
210 |
280 |
Overload capability |
x In |
1.8 |
||||
Rated power |
kW |
29 |
44 |
61 |
102 |
136 |
Power loss at rated DC current |
kW |
0.25 |
0.36 |
0.41 |
0.69 |
0.81 |
Rated DC field voltage 1) |
V |
max. 325 |
||||
Rated DC field current |
A |
10 |
15 |
|||
Normal ambient temperature in operation5) |
°C |
0 … +45 |
0 … +40 |
|||
Storage and transport temperature |
°C |
-40 … +70 |
||||
Installation altitude above sea level5) |
1 000 m for rated DC current |
|||||
Dimensions |
||||||
|
mm |
268 |
||||
|
mm |
385 |
||||
|
mm |
252 |
||||
Weight, approx. |
kg |
10 |
14 |
15 |
Note:
Detailed dimension drawings in the PDF and DXF formats are available on the DVD-ROM supplied with Catalog D 23.1 and in the Internet under
http://www.siemens.com/sinamics-dcm
(information material).
Data for single-phase operation
Type |
||||||
---|---|---|---|---|---|---|
6RA8025-6DS22-0AA0 |
6RA8028-6DS22-0AA0 |
6RA8031-6DS22-0AA0 |
||||
Rated DC voltage |
V |
320 |
||||
Rated DC current |
A |
42.0 |
63.0 |
87.5 |
SINAMICS DC MASTER converters for 400 V 3 AC, 400 to 1 200 A, two-quadrant operation
Type |
|||||
---|---|---|---|---|---|
6RA8081-6DS22-0AA0 |
6RA8085-6DS22-0AA0 |
6RA8087-6DS22-0AA0 |
6RA8091-6DS22-0AA0 |
||
Rated armature supply voltage1) |
V |
400 V 3 AC |
|||
Rated armature input current |
A |
332 |
498 |
706 |
996 |
Rated supply voltage, electronics power supply |
V |
380 (-25 %) … 480 V (+10 %) 2 AC;In = 1 A or |
|||
Rated fan supply voltage |
V |
400 V 3 AC ± 10 % (50 Hz) |
|||
Rated fan current |
A |
0.23 3) |
0.3 3) |
||
Air flow |
m3/h |
600 |
1 000 |
||
Sound pressure level2) |
dB (A) |
64.5 |
|||
Rated field supply voltage 1) |
V |
400 V 2 AC |
480 V 2 AC |
||
Rated frequency |
Hz |
45 … 65 |
|||
Rated DC voltage 1) |
V |
485 |
|||
Rated DC current |
A |
400 |
600 |
850 |
1 200 |
Overload capability |
x In |
1.8 |
|||
Rated power |
kW |
194 |
291 |
412 |
582 |
Power loss at rated DC current |
kW |
1.37 |
1.84 |
2.47 |
4.11 |
Rated DC field voltage 1) |
V |
max. 325 |
max. 390 |
||
Rated DC field current |
A |
25 |
30 |
40 |
|
Normal ambient temperature in operation5) |
°C |
0 … +40 |
|||
Storage and transport temperature |
°C |
-40 … +70 |
|||
Installation altitude above sea level5) |
1 000 m for rated DC current |
||||
Dimensions |
|||||
|
mm |
268 |
|||
|
mm |
625 |
700 |
783 |
|
|
mm |
275 |
311 |
435 |
|
Weight, approx. |
kg |
26 |
28 |
38 |
78 |
Note:
Detailed dimension drawings in the PDF and DXF formats are available on the DVD-ROM supplied with Catalog D 23.1 and in the Internet under
http://www.siemens.com/sinamics-dcm
(information material).
SINAMICS DC MASTER converters for 400 V 3 AC, 1 600 to 3 000 A, two-quadrant operation
Type |
||||
---|---|---|---|---|
6RA8093-4DS22-0AA0 |
6RA8095-4DS22-0AA0 |
6RA8098-4DS22-0AA0 |
||
Rated armature supply voltage 1) |
V |
400 V 3 AC |
400 V 3 AC |
|
Rated armature input current |
A |
1 328 |
1 660 |
2 490 |
Rated supply voltage, electronics power supply |
V |
380 (-25 %) … 480 V (+10 %) 2 AC;In = 1 A or |
||
Rated fan supply voltage |
V |
400 V 3 AC ± 10 % (50 Hz) |
||
Rated fan current |
A |
1 4) |
||
Air flow |
m3/h |
2 400 |
||
Sound pressure level2) |
dB (A) |
75.6 |
||
Rated field supply voltage1) |
V |
480 V 2 AC |
||
Rated frequency |
Hz |
45 … 65 |
||
Rated DC voltage 1) |
V |
485 |
||
Rated DC current |
A |
1 600 |
2 000 |
3 000 |
Overload capability |
x In |
1.8 |
||
Rated power |
kW |
776 |
970 |
1 455 |
Power loss at rated DC current |
kW |
5.68 |
6.78 |
10.64 |
Rated DC field voltage 1) |
V |
max. 390 |
||
Rated DC field current |
A |
40 |
||
Normal ambient temperature in operation5) |
°C |
0 … +40 |
||
Storage and transport temperature |
°C |
-40 … +70 |
||
Installation altitude above sea level5) |
1 000 m for rated DC current |
|||
Dimensions |
||||
|
mm |
453 |
||
|
mm |
883 |
||
|
mm |
505 |
||
Weight, approx. |
kg |
135 |
165 |
Note:
Detailed dimension drawings in the PDF and DXF formats are available on the DVD-ROM supplied with Catalog D 23.1 and in the Internet under
http://www.siemens.com/sinamics-dcm
(information material).
SINAMICS DC MASTER converters for 480 V 3 AC, 60 to 280 A, two-quadrant operation
Type |
||||||
---|---|---|---|---|---|---|
6RA8025-6FS22-0AA0 |
6RA8028-6FS22-0AA0 |
6RA8031-6FS22-0AA0 |
6RA8075-6FS22-0AA0 |
6RA8078-6FS22-0AA0 |
||
Rated armature supply voltage 1) |
V |
480 V 3 AC |
||||
Rated armature input current |
A |
50 |
75 |
104 |
174 |
232 |
Rated supply voltage, electronics power supply |
V |
380 (-25 %) … 480 V (+10 %) 2 AC;In = 1 A or |
||||
Rated fan supply voltage |
V |
Self-ventilated |
24 V DC internal |
|||
Rated fan current |
A |
Internal supply |
||||
Air flow |
m3/h |
300 |
||||
Sound pressure level 2) |
dB (A) |
52.4 |
||||
Rated field supply voltage1) |
V |
480 V 2 AC |
||||
Rated frequency |
Hz |
45 … 65 |
||||
Rated DC voltage 1) |
V |
575 |
||||
Rated DC current |
A |
60 |
90 |
125 |
210 |
280 |
Overload capability |
x In |
1.8 |
||||
Rated power |
kW |
35 |
52 |
72 |
121 |
161 |
Power loss at rated DC current |
kW |
0.30 |
0.38 |
0.43 |
0.72 |
0.81 |
Rated DC field voltage 1) |
V |
max. 390 |
||||
Rated DC field current |
A |
10 |
15 |
|||
Normal ambient temperature in operation5) |
°C |
0 … +45 |
0 … +40 |
|||
Storage and transport temperature |
°C |
-40 … +70 |
||||
Installation altitude above sea level5) |
1 000 m for rated DC current |
|||||
Dimensions |
||||||
|
mm |
268 |
||||
|
mm |
385 |
||||
|
mm |
252 |
||||
Weight, approx. |
kg |
11 |
14 |
15 |
Note:
Detailed dimension drawings in the PDF and DXF formats are available on the DVD-ROM supplied with Catalog D 23.1 and in the Internet under
http://www.siemens.com/sinamics-dcm
(information material).
Data for single-phase operation
Type |
||||||
---|---|---|---|---|---|---|
|
6RA8025-6FS22-0AA0 |
6RA8028-6FS22-0AA0 |
6RA8031-6FS22-0AA0 |
|||
Rated DC voltage |
V |
385 |
||||
Rated DC current |
A |
42.0 |
63.0 |
87.5 |
SINAMICS DC MASTER converters for 480 V 3 AC, 450 to 1 200 A, two-quadrant operation
Type |
|||||
---|---|---|---|---|---|
6RA8082-6FS22-0AA0 |
6RA8085-6FS22-0AA0 |
6RA8087-6FS22-0AA0 |
6RA8091-6FS22-0AA0 |
||
Rated armature supply voltage 1) |
V |
480 V 3 AC |
|||
Rated armature input current |
A |
374 |
498 |
706 |
996 |
Rated supply voltage, electronics power supply |
V |
380 (-25 %) … 480 V (+10 %) 2 AC;In = 1 A or |
|||
Rated fan supply voltage |
V |
400 V 3 AC ± 10 % (50 Hz) |
|||
Rated fan current |
A |
0.23 3) |
0.3 3) |
||
Air flow |
m3/h |
600 |
1 000 |
||
Sound pressure level 2) |
dB (A) |
64.5 |
|||
Rated field supply voltage1) |
V |
480 V 2 AC |
|||
Rated frequency |
Hz |
45 … 65 |
|||
Rated DC voltage 1) |
V |
575 |
|||
Rated DC current |
A |
450 |
600 |
850 |
1 200 |
Overload capability |
x In |
1.8 |
|||
Rated power |
kW |
259 |
345 |
489 |
690 |
Power loss at rated DC current |
kW |
1.58 |
1.91 |
2.60 |
4.24 |
Rated DC field voltage 1) |
V |
max. 390 |
|||
Rated DC field current |
A |
25 |
30 |
||
Normal ambient temperature in operation5) |
°C |
0 … +40 |
|||
Storage and transport temperature |
°C |
-40 … +70 |
|||
Installation altitude above sea level5) |
1 000 m for rated DC current |
||||
Dimensions |
|||||
|
mm |
268 |
|||
|
mm |
625 |
700 |
783 |
|
|
mm |
275 |
311 |
435 |
|
Weight, approx. |
kg |
28 |
38 |
78 |
Note:
Detailed dimension drawings in the PDF and DXF formats are available on the DVD-ROM supplied with Catalog D 23.1 and in the Internet under
http://www.siemens.com/sinamics-dcm
(information material).
SINAMICS DC MASTER converters for 575 V 3 AC, 60 to 800 A, two-quadrant operation
Type |
|||||||
---|---|---|---|---|---|---|---|
6RA8025-6GS22-0AA0 |
6RA8031-6GS22-0AA0 |
6RA8075-6GS22-0AA0 |
6RA8081-6GS22-0AA0 |
6RA8085-6GS22-0AA0 |
6RA8087-6GS22-0AA0 |
||
Rated armature supply voltage 1) |
V |
575 V 3 AC |
|||||
Rated armature input current |
A |
50 |
104 |
174 |
332 |
498 |
664 |
Rated supply voltage, electronics power supply |
V |
380 (-25 %) … 480 V (+10 %) 2 AC;In = 1 A or |
|||||
Rated fan supply voltage |
V |
Self-ventilated |
24 V DC internal |
400 V 3 AC ± 10 % (50 Hz) |
|||
Rated fan current |
A |
Internal supply |
0.23 3) |
||||
Air flow |
m3/h |
300 |
600 |
||||
Sound pressure level 2) |
dB (A) |
52.4 |
64.5 |
||||
Rated field supply voltage1) |
V |
480 V 2 AC |
|||||
Rated frequency |
Hz |
45 … 65 |
|||||
Rated DC voltage 1) |
V |
690 |
|||||
Rated DC current |
A |
60 |
125 |
210 |
400 |
600 |
800 |
Overload capability |
x In |
1.8 |
|||||
Rated power |
kW |
41 |
86 |
145 |
276 |
414 |
552 |
Power loss at rated DC current |
kW |
0.27 |
0.46 |
0.74 |
1.60 |
2.00 |
2.69 |
Rated DC field voltage 1) |
V |
max. 390 |
|||||
Rated DC field current |
A |
10 |
15 |
25 |
30 |
||
Normal ambient temperature in operation5) |
°C |
0 … +45 |
0 … +40 |
||||
Storage and transport temperature |
°C |
-40 … +70 |
|||||
Installation altitude above sea level5) |
1 000 m for rated DC current |
||||||
Dimensions |
|||||||
|
mm |
268 |
|||||
|
mm |
385 |
625 |
700 |
|||
|
mm |
252 |
275 |
311 |
|||
Weight, approx. |
kg |
11 |
14 |
26 |
28 |
38 |
Note:
Detailed dimension drawings in the PDF and DXF formats are available on the DVD-ROM supplied with Catalog D 23.1 and in the Internet under
http://www.siemens.com/sinamics-dcm
(information material).
Data for single-phase operation
Type |
|||||||
---|---|---|---|---|---|---|---|
6RA8025-6GS22-0AA0 |
6RA8031-6GS22-0AA0 |
||||||
Rated DC voltage |
V |
460 |
|||||
Rated DC current |
A |
42.0 |
87.5 |
SINAMICS DC MASTER converters for 575 V 3 AC, 1 100 to 2 800 A, two-quadrant operation
Type |
||||||
---|---|---|---|---|---|---|
6RA8090-6GS22-0AA0 |
6RA8093-4GS22-0AA0 |
6RA8095-4GS22-0AA0 |
6RA8096-4GS22-0AA0 |
6RA8097-4GS22-0AA0 |
||
Rated armature supply voltage 1) |
V |
575 V 3 AC |
||||
Rated armature input current |
A |
913 |
1 328 |
1 660 |
1 826 |
2 324 |
Rated supply voltage, electronics power supply |
V |
380 (-25 %) … 480 V (+10 %) 2 AC;In = 1 A or |
||||
Rated fan supply voltage |
V |
400 V 3 AC ± 10 % (50 Hz) |
||||
Rated fan current |
A |
0.3 3) |
1 4) |
|||
Air flow |
m3/h |
1 000 |
2 400 |
|||
Sound pressure level2) |
dB (A) |
64.5 |
75.6 |
|||
Rated field supply voltage1) |
V |
480 V 2 AC |
||||
Rated frequency |
Hz |
45 … 65 |
||||
Rated DC voltage 1) |
V |
690 |
||||
Rated DC current |
A |
1 100 |
1 600 |
2 000 |
2 200 |
2 800 |
Overload capability |
x In |
1.8 |
||||
Rated power |
kW |
759 |
1 104 |
1 380 |
1 518 |
1 932 |
Power loss at rated DC current |
kW |
4.02 |
6.04 |
7.07 |
7.39 |
10.53 |
Rated DC field voltage 1) |
V |
max. 390 |
||||
Rated DC field current |
A |
40 |
||||
Normal ambient temperature in operation5) |
°C |
0 … +40 |
||||
Storage and transport temperature |
°C |
-40 … +70 |
||||
Installation altitude above sea level5) |
1 000 m for rated DC current |
|||||
Dimensions |
||||||
|
mm |
268 |
453 |
|||
|
mm |
785 |
883 |
|||
|
mm |
435 |
505 |
|||
Weight, approx. |
kg |
78 |
135 |
165 |
Note:
Detailed dimension drawings in the PDF and DXF formats are available on the DVD-ROM supplied with Catalog D 23.1 and in the Internet under
http://www.siemens.com/sinamics-dcm
(information material).
SINAMICS DC MASTER converters for 690 V 3 AC, 720 to 2 600 A, two-quadrant operation
Type |
||||||
---|---|---|---|---|---|---|
6RA8086-6KS22-0AA0 |
6RA8090-6KS22-0AA0 |
6RA8093-4KS22-0AA0 |
6RA8095-4KS22-0AA0 |
6RA8097-4KS22-0AA0 |
||
Rated armature supply voltage 1) |
V |
690 V 3 AC |
||||
Rated armature input current |
A |
598 |
830 |
1 245 |
1 660 |
2 158 |
Rated supply voltage, electronics power supply |
V |
380 (-25 %) … 480 V (+10 %) 2 AC;In = 1 A or |
||||
Rated fan supply voltage |
V |
400 V 3 AC ± 10 % (50 Hz) |
||||
Rated fan current |
A |
0.23 3) |
0.3 3) |
1 4) |
||
Air flow |
m3/h |
600 |
1 000 |
2 400 |
||
Sound pressure level2) |
dB (A) |
64.5 |
75.6 |
|||
Rated field supply voltage1) |
V |
480 V 2 AC |
||||
Rated frequency |
Hz |
45 … 65 |
||||
Rated DC voltage 1) |
V |
830 |
||||
Rated DC current |
A |
720 |
1 000 |
1 500 |
2 000 |
2 600 |
Overload capability |
x In |
1.8 |
||||
Rated power |
kW |
598 |
830 |
1 245 |
1 660 |
2 158 |
Power loss at rated DC current |
kW |
2.77 |
3.96 |
6.67 |
8.16 |
10.30 |
Rated DC field voltage 1) |
V |
max. 390 |
||||
Rated DC field current |
A |
30 |
40 |
|||
Normal ambient temperature in operation5) |
°C |
0 … +40 |
||||
Storage and transport temperature |
°C |
-40 … +70 |
||||
Installation altitude above sea level5) |
1 000 m for rated DC current |
|||||
Dimensions |
||||||
|
mm |
268 |
453 |
|||
|
mm |
700 |
785 |
883 |
||
|
mm |
311 |
435 |
505 |
||
Weight, approx. |
kg |
38 |
78 |
135 |
165 |
Note:
Detailed dimension drawings in the PDF and DXF formats are available on the DVD-ROM supplied with Catalog D 23.1 and in the Internet under
http://www.siemens.com/sinamics-dcm
(information material).
SINAMICS DC MASTER converters for 830 V 3 AC, 950 to 1 900 A and 950 V 3 AC, 2 200 A, two-quadrant operation
Type |
|||||
---|---|---|---|---|---|
6RA8088-6LS22-0AA0 |
6RA8093-4LS22-0AA0 |
6RA8095-4LS22-0AA0 |
6RA8096-4MS22-0AA0 |
||
Rated armature supply voltage 1) |
V |
830 V 3 AC |
950 V 3 AC |
||
Rated armature input current |
A |
789 |
1 245 |
1 577 |
1 826 |
Rated supply voltage, electronics power supply |
V |
380 (-25 %) … 480 V (+10 %) 2 AC;In = 1 A or |
|||
Rated fan supply voltage |
V |
400 V 3 AC ± 10 % (50 Hz) |
|||
Rated fan current |
A |
0.3 3) |
1 4) |
||
Air flow |
m3/h |
1 000 |
2 400 |
||
Sound pressure level2) |
dB (A) |
64.5 |
75.6 |
||
Rated field supply voltage1) |
V |
480 V 2 AC |
|||
Rated frequency |
Hz |
45 … 65 |
|||
Rated DC voltage 1) |
V |
1 000 |
1 140 |
||
Rated DC current |
A |
950 |
1 500 |
1 900 |
2 200 |
Overload capability |
x In |
1.8 |
|||
Rated power |
kW |
950 |
1 500 |
1 900 |
2 508 |
Power loss at rated DC current |
kW |
4.22 |
7.12 |
8.67 |
11.34 |
Rated DC field voltage 1) |
V |
max. 390 |
|||
Rated DC field current |
A |
40 |
|||
Normal ambient temperature in operation5) |
°C |
0 … +40 |
|||
Storage and transport temperature |
°C |
-40 … +70 |
|||
Installation altitude above sea level5) |
1 000 m for rated DC current |
||||
Dimensions |
|||||
|
mm |
268 |
453 |
||
|
mm |
785 |
883 |
||
|
mm |
435 |
505 |
||
Weight, approx. |
kg |
78 |
135 |
165 |
Note:
Detailed dimension drawings in the PDF and DXF formats are available on the DVD-ROM supplied with Catalog D 23.1 and in the Internet under
http://www.siemens.com/sinamics-dcm
(information material).
SINAMICS DC MASTER converters for 400 V 3 AC, 15 to 125 A, four-quadrant operation
Type |
||||||
---|---|---|---|---|---|---|
6RA8013-6DV62-0AA0 |
6RA8018-6DV62-0AA0 |
6RA8025-6DV62-0AA0 |
6RA8028-6DV62-0AA0 |
6RA8031-6DV62-0AA0 |
||
Rated armature supply voltage 1) |
V |
400 V 3 AC |
||||
Rated armature input current |
A |
12 |
25 |
50 |
75 |
104 |
Rated supply voltage, electronics power supply |
V |
380 (-25 %) … 480 V (+10 %) 2 AC;In = 1 A or |
||||
Rated fan supply voltage |
V |
Self-ventilated |
||||
Rated fan current |
A |
|||||
Air flow |
m3/h |
|||||
Sound pressure level2) |
dB (A) |
|||||
Rated field supply voltage1) |
V |
400 V 2 AC |
||||
Rated frequency |
Hz |
45 … 65 |
||||
Rated DC voltage 1) |
V |
420 |
||||
Rated DC current |
A |
15 |
30 |
60 |
90 |
125 |
Overload capability |
x In |
1.8 |
||||
Rated power |
kW |
6.3 |
12.6 |
25 |
38 |
53 |
Power loss at rated DC current |
kW |
0.13 |
0.18 |
0.25 |
0.32 |
0.41 |
Rated DC field voltage 1) |
V |
max. 325 |
||||
Rated DC field current |
A |
3 |
5 |
10 |
||
Normal ambient temperature in operation5) |
°C |
0 … +45 |
||||
Storage and transport temperature |
°C |
-40 … +70 |
||||
Installation altitude above sea level5) |
1 000 m for rated DC current |
|||||
Dimensions |
||||||
|
mm |
268 |
||||
|
mm |
385 |
||||
|
mm |
221 |
252 |
|||
Weight, approx. |
kg |
11 |
14 |
Note:
Detailed dimension drawings in the PDF and DXF formats are available on the DVD-ROM supplied with Catalog D 23.1 and in the Internet under
http://www.siemens.com/sinamics-dcm
(information material).
Data for single-phase operation
Type |
||||||
---|---|---|---|---|---|---|
6RA8013-6DV62-0AA0 |
6RA8018-6DV62-0AA0 |
6RA8025-6DV62-0AA0 |
6RA8028-6DV62-0AA0 |
6RA8031-6DV62-0AA0 |
||
Rated DC voltage |
V |
280 |
||||
Rated DC current |
A |
10.5 |
21.0 |
42.0 |
63.0 |
87.5 |
SINAMICS DC MASTER converters for 400 V 3 AC, 210 to 850 A, four-quadrant operation
Type |
||||||
---|---|---|---|---|---|---|
6RA8075-6DV62-0AA0 |
6RA8078-6DV62-0AA0 |
6RA8081-6DV62-0AA0 |
6RA8085-6DV62-0AA0 |
6RA8087-6DV62-0AA0 |
||
Rated armature supply voltage 1) |
V |
400 V 3 AC |
||||
Rated armature input current |
A |
174 |
232 |
332 |
498 |
706 |
Rated supply voltage, electronics power supply |
V |
380 (-25 %) … 480 V (+10 %) 2 AC;In = 1 A or |
||||
Rated fan supply voltage |
V |
24 V DC internal |
400 V 3 AC ± 10 % (50 Hz) |
|||
Rated fan current |
A |
Internal supply |
0.23 3) |
|||
Air flow |
m3/h |
300 |
600 |
|||
Sound pressure level2) |
dB (A) |
52.4 |
64.5 |
|||
Rated field supply voltage1) |
V |
400 V 2 AC |
||||
Rated frequency |
Hz |
45 … 65 |
||||
Rated DC voltage 1) |
V |
420 |
||||
Rated DC current |
A |
210 |
280 |
400 |
600 |
850 |
Overload capability |
x In |
1.8 |
||||
Rated power |
kW |
88 |
118 |
168 |
252 |
357 |
Power loss at rated DC current |
kW |
0.69 |
0.81 |
1.37 |
1.84 |
2.47 |
Rated DC field voltage 1) |
V |
max. 325 |
||||
Rated DC field current |
A |
15 |
25 |
30 |
||
Normal ambient temperature in operation5) |
°C |
0 … +40 |
||||
Storage and transport temperature |
°C |
-40 … +70 |
||||
Installation altitude above sea level5) |
1 000 m for rated DC current |
|||||
Dimensions |
||||||
|
mm |
268 |
||||
|
mm |
385 |
625 |
700 |
||
|
mm |
252 |
275 |
311 |
||
Weight, approx. |
kg |
15 |
26 |
31 |
42 |
Note:
Detailed dimension drawings in the PDF and DXF formats are available on the DVD-ROM supplied with Catalog D 23.1 and in the Internet under
http://www.siemens.com/sinamics-dcm
(information material).
SINAMICS DC MASTER converters for 400 V 3 AC, 1 200 to 3 000 A, four-quadrant operation
Type |
|||||
---|---|---|---|---|---|
6RA8091-6DV62-0AA0 |
6RA8093-4DV62-0AA0 |
6RA8095-4DV62-0AA0 |
6RA8098-4DV62-0AA0 |
||
Rated armature supply voltage 1) |
V |
400 V 3 AC |
400 V 3 AC |
||
Rated armature input current |
A |
996 |
1 328 |
1 660 |
2 490 |
Rated supply voltage, electronics power supply |
V |
380 (-25 %) … 480 V (+10 %) 2 AC;In = 1 A or |
|||
Rated fan supply voltage |
V |
400 V 3 AC ± 10 % (50 Hz) |
|||
Rated fan current |
A |
0.3 3) |
1 4) |
||
Air flow |
m3/h |
1 000 |
2 400 |
||
Sound pressure level2) |
dB (A) |
64.5 |
75.6 |
||
Rated field supply voltage1) |
V |
480 V 2 AC |
|||
Rated frequency |
Hz |
45 … 65 |
|||
Rated DC voltage 1) |
V |
420 |
|||
Rated DC current |
A |
1 200 |
1 600 |
2 000 |
3 000 |
Overload capability |
x In |
1.8 |
|||
Rated power |
kW |
504 |
672 |
840 |
1 260 |
Power loss at rated DC current |
kW |
4.11 |
5.68 |
6.78 |
10.64 |
Rated DC field voltage 1) |
V |
max. 390 |
|||
Rated DC field current |
A |
40 |
|||
Normal ambient temperature in operation5) |
°C |
0 … +40 |
|||
Storage and transport temperature |
°C |
-40 … +70 |
|||
Installation altitude above sea level5) |
1 000 m for rated DC current |
||||
Dimensions |
|||||
|
mm |
268 |
453 |
||
|
mm |
785 |
883 |
||
|
mm |
435 |
505 |
||
Weight, approx. |
kg |
78 |
155 |
185 |
Note:
Detailed dimension drawings in the PDF and DXF formats are available on the DVD-ROM supplied with Catalog D 23.1 and in the Internet under
http://www.siemens.com/sinamics-dcm
(information material).
SINAMICS DC MASTER converters for 480 V 3 AC, 15 to 210 A, four-quadrant operation
Type |
||||||||
---|---|---|---|---|---|---|---|---|
6RA8013-6FV62-0AA0 |
6RA8018-6FV62-0AA0 |
6RA8025-6FV62-0AA0 |
6RA8028-6FV62-0AA0 |
6RA8031-6FV62-0AA0 |
6RA8075-6FV62-0AA0 |
|||
Rated armature supply voltage 1) |
V |
480 V 3 AC |
480 V 3 AC |
|||||
Rated armature input current |
A |
12 |
25 |
50 |
75 |
104 |
174 |
|
Rated supply voltage, electronics power supply |
V |
380 (-25 %) … 480 V (+10 %) 2 AC;In = 1 A or |
||||||
Rated fan supply voltage |
V |
Self-ventilated |
24 V DC internal |
|||||
Rated fan current |
A |
Internal supply |
||||||
Air flow |
m3/h |
300 |
||||||
Sound pressure level2) |
dB (A) |
52.4 |
||||||
Rated field supply voltage1) |
V |
480 V 2 AC |
||||||
Rated frequency |
Hz |
45 … 65 |
||||||
Rated DC voltage 1) |
V |
500 |
||||||
Rated DC current |
A |
15 |
30 |
60 |
90 |
125 |
210 |
|
Overload capability |
x In |
1.8 |
||||||
Rated power |
kW |
6 |
15 |
30 |
45 |
63 |
105 |
|
Power loss at rated DC current |
kW |
0.13 |
0.19 |
0.30 |
0.34 |
0.43 |
0.72 |
|
Rated DC field voltage 1) |
V |
max. 390 |
||||||
Rated DC field current |
A |
3 |
5 |
10 |
10 |
10 |
15 |
|
Normal ambient temperature in operation5) |
°C |
0 … +45 |
0 … +40 |
|||||
Storage and transport temperature |
°C |
-40 … +70 |
||||||
Installation altitude above sea level5) |
1 000 m for rated DC current |
|||||||
Dimensions |
||||||||
|
mm |
268 |
||||||
|
mm |
385 |
||||||
|
mm |
221 |
252 |
|||||
Weight, approx. |
kg |
11 |
14 |
15 |
Note:
Detailed dimension drawings in the PDF and DXF formats are available on the DVD-ROM supplied with Catalog D 23.1 and in the Internet under
http://www.siemens.com/sinamics-dcm
(information material).
Data for single-phase operation
Type |
|||||||
---|---|---|---|---|---|---|---|
6RA8013-6FV62-0AA0 |
6RA8018-6FV62-0AA0 |
6RA8025-6FV62-0AA0 |
6RA8028-6FV62-0AA0 |
6RA8031-6FV62-0AA0 |
|||
Rated DC voltage |
V |
335 |
|||||
Rated DC current |
A |
10.5 |
21.0 |
42.0 |
63.0 |
87.5 |
SINAMICS DC MASTER converters for 480 V 3 AC, 280 to 1 200 A, four-quadrant operation
Type |
||||||
---|---|---|---|---|---|---|
6RA8078-6FV62-0AA0 |
6RA8082-6FV62-0AA0 |
6RA8085-6FV62-0AA0 |
6RA8087-6FV62-0AA0 |
6RA8091-6FV62-0AA0 |
||
Rated armature supply voltage 1) |
V |
480 V 3 AC |
||||
Rated armature input current |
A |
232 |
374 |
498 |
706 |
996 |
Rated supply voltage, electronics power supply |
V |
380 (-25 %) … 480 V (+10 %) 2 AC;In = 1 A or |
||||
Rated fan supply voltage |
V |
24 V DC internal |
400 V 3 AC ± 10 % (50 Hz) |
|||
Rated fan current |
A |
Internal supply |
0.23 3) |
0.3 3) |
||
Air flow |
m3/h |
300 |
600 |
1 000 |
||
Sound pressure level2) |
dB (A) |
52.4 |
64.5 |
|||
Rated field supply voltage1) |
V |
480 V 2 AC |
||||
Rated frequency |
Hz |
45 … 65 |
||||
Rated DC voltage 1) |
V |
500 |
||||
Rated DC current |
A |
280 |
450 |
600 |
850 |
1 200 |
Overload capability |
x In |
1.8 |
||||
Rated power |
kW |
140 |
225 |
300 |
425 |
600 |
Power loss at rated DC current |
kW |
0.81 |
1.58 |
1.91 |
2.60 |
4.24 |
Rated DC field voltage 1) |
V |
max. 390 |
||||
Rated DC field current |
A |
15 |
25 |
25 |
30 |
40 |
Normal ambient temperature in operation5) |
°C |
0 … +40 |
||||
Storage and transport temperature |
°C |
-40 … +70 |
||||
Installation altitude above sea level5) |
1 000 m for rated DC current |
|||||
Dimensions |
||||||
|
mm |
268 |
||||
|
mm |
385 |
625 |
700 |
785 |
|
|
mm |
252 |
275 |
311 |
435 |
|
Weight, approx. |
kg |
15 |
31 |
42 |
78 |
Note:
Detailed dimension drawings in the PDF and DXF formats are available on the DVD-ROM supplied with Catalog D 23.1 and in the Internet under
http://www.siemens.com/sinamics-dcm
(information material).
SINAMICS DC MASTER converters for 575 V 3 AC, 60 to 850 A, four-quadrant operation
Type |
|||||||
---|---|---|---|---|---|---|---|
6RA8025-6GV62-0AA0 |
6RA8031-6GV62-0AA0 |
6RA8075-6GV62-0AA0 |
6RA8081-6GV62-0AA0 |
6RA8085-6GV62-0AA0 |
6RA8087-6GV62-0AA0 |
||
Rated armature supply voltage 1) |
V |
575 V 3 AC |
|||||
Rated armature input current |
A |
50 |
104 |
174 |
332 |
498 |
706 |
Rated supply voltage, electronics power supply |
V |
380 (-25 %) … 480 V (+10 %) 2 AC;In = 1 A or |
|||||
Rated fan supply voltage |
V |
Self-ventilated |
24 V DC internal |
400 V 3 AC ± 10 % (50 Hz) |
|||
Rated fan current |
A |
Internal supply |
0.23 3) |
||||
Air flow |
m3/h |
300 |
600 |
||||
Sound pressure level2) |
dB (A) |
52.4 |
64.5 |
||||
Rated field supply voltage1) |
V |
480 V 2 AC |
|||||
Rated frequency |
Hz |
45 … 65 |
|||||
Rated DC voltage 1) |
V |
600 |
|||||
Rated DC current |
A |
60 |
125 |
210 |
400 |
600 |
850 |
Overload capability |
x In |
1.8 |
|||||
Rated power |
kW |
36 |
75 |
126 |
240 |
360 |
510 |
Power loss at rated DC current |
kW |
0.27 |
0.46 |
0.74 |
1.60 |
2.00 |
2.83 |
Rated DC field voltage 1) |
V |
max. 390 |
|||||
Rated DC field current |
A |
10 |
10 |
15 |
25 |
25 |
30 |
Normal ambient temperature in operation5) |
°C |
0 … +45 |
0 … +40 |
||||
Storage and transport temperature |
°C |
-40 … +70 |
|||||
Installation altitude above sea level5) |
1 000 m for rated DC current |
||||||
Dimensions |
|||||||
|
mm |
268 |
|||||
|
mm |
385 |
65 |
700 |
|||
|
mm |
252 |
275 |
311 |
|||
Weight, approx. |
kg |
11 |
14 |
15 |
26 |
31 |
42 |
Note:
Detailed dimension drawings in the PDF and DXF formats are available on the DVD-ROM supplied with Catalog D 23.1 and in the Internet under
http://www.siemens.com/sinamics-dcm
(information material).
Data for single-phase operation
Type |
|||||||
---|---|---|---|---|---|---|---|
6RA8025-6GV62-0AA0 |
6RA8031-6GV62-0AA0 |
||||||
Rated DC voltage |
V |
400 |
|||||
Rated DC current |
A |
42.0 |
87.5 |
SINAMICS DC MASTER converters for 575 V 3 AC, 1 100 to 2 800 A, four-quadrant operation
Type |
||||||
---|---|---|---|---|---|---|
6RA8090-6GV62-0AA0 |
6RA8093-4GV62-0AA0 |
6RA8095-4GV62-0AA0 |
6RA8096-4GV62-0AA0 |
6RA8097-4GV62-0AA0 |
||
Rated armature supply voltage 1) |
V |
575 V 3 AC |
||||
Rated armature input current |
A |
913 |
1 328 |
1 660 |
1 826 |
2 324 |
Rated supply voltage, electronics power supply |
V |
380 (-25 %) … 480 V (+10 %) 2 AC;In = 1 A or |
||||
Rated fan supply voltage |
V |
400 V 3 AC ± 10 % (50 Hz) |
||||
Rated fan current |
A |
0.3 3) |
1 4) |
|||
Air flow |
m3/h |
1 000 |
2 400 |
|||
Sound pressure level2) |
dB (A) |
64.5 |
75.6 |
|||
Rated field supply voltage1) |
V |
480 V 2 AC |
||||
Rated frequency |
Hz |
45 … 65 |
||||
Rated DC voltage 1) |
V |
600 |
||||
Rated DC current |
A |
1 100 |
1 600 |
2 000 |
2 200 |
2 800 |
Overload capability |
x In |
1.8 |
||||
Rated power |
kW |
660 |
960 |
1 200 |
1 320 |
1 680 |
Power loss at rated DC current |
kW |
4.02 |
6.04 |
7.07 |
7.39 |
10.53 |
Rated DC field voltage 1) |
V |
max. 390 |
||||
Rated DC field current |
A |
40 |
||||
Normal ambient temperature in operation5) |
°C |
0 … +40 |
||||
Storage and transport temperature |
°C |
-40 … +70 |
||||
Installation altitude above sea level5) |
1 000 m for rated DC current |
|||||
Dimensions |
||||||
|
mm |
268 |
453 |
|||
|
mm |
785 |
883 |
|||
|
mm |
435 |
505 |
|||
Weight, approx. |
kg |
78 |
155 |
185 |
Note:
Detailed dimension drawings in the PDF and DXF formats are available on the DVD-ROM supplied with Catalog D 23.1 and in the Internet under
http://www.siemens.com/sinamics-dcm
(information material).
SINAMICS DC MASTER converters for 690 V 3 AC, 760 to 2 600 A, four-quadrant operation
Type |
||||||
---|---|---|---|---|---|---|
6RA8086-6KV62-0AA0 |
6RA8090-6KV62-0AA0 |
6RA8093-4KV62-0AA0 |
6RA8095-4KV62-0AA0 |
6RA8097-4KV62-0AA0 |
||
Rated armature supply voltage 1) |
V |
690 V 3 AC |
||||
Rated armature input current |
A |
631 |
830 |
1 245 |
1 660 |
2 158 |
Rated supply voltage, electronics power supply |
V |
380 (-25 %) … 480 V (+10 %) 2 AC;In = 1 A or |
||||
Rated fan supply voltage |
V |
400 V 3 AC ± 10 % (50 Hz) |
||||
Rated fan current |
A |
0.23 3) |
0.3 3) |
1 4) |
||
Air flow |
m3/h |
600 |
1 000 |
2 400 |
||
Sound pressure level2) |
dB (A) |
64.5 |
75.6 |
|||
Rated field supply voltage1) |
V |
480 V 2 AC |
||||
Rated frequency |
Hz |
45 … 65 |
||||
Rated DC voltage 1) |
V |
725 |
||||
Rated DC current |
A |
760 |
1 000 |
1 500 |
2 000 |
2 600 |
Overload capability |
x In |
1.8 |
||||
Rated power |
kW |
551 |
725 |
1 088 |
1 450 |
1 885 |
Power loss at rated DC current |
kW |
2.90 |
3.96 |
6.67 |
8.16 |
10.30 |
Rated DC field voltage 1) |
V |
max. 390 |
||||
Rated DC field current |
A |
30 |
40 |
|||
Normal ambient temperature in operation5) |
°C |
0 … +40 |
||||
Storage and transport temperature |
°C |
-40 … +70 |
||||
Installation altitude above sea level5) |
1 000 m for rated DC current |
|||||
Dimensions |
||||||
|
mm |
268 |
453 |
|||
|
mm |
700 |
785 |
883 |
||
|
mm |
311 |
435 |
505 |
||
Weight, approx. |
kg |
42 |
78 |
155 |
185 |
Note:
Detailed dimension drawings in the PDF and DXF formats are available on the DVD-ROM supplied with Catalog D 23.1 and in the Internet under
http://www.siemens.com/sinamics-dcm
(information material).
SINAMICS DC MASTER converters for 830 V 3 AC, 950 to 1 900 A and 950 V 3 AC, 2 200 A, four-quadrant operation
Type |
|||||
---|---|---|---|---|---|
6RA8088-6LV62-0AA0 |
6RA8093-4LV62-0AA0 |
6RA8095-4LV62-0AA0 |
6RA8096-4MV62-0AA0 |
||
Rated armature supply voltage 1) |
V |
830 V 3 AC |
950 V 3 AC |
||
Rated armature input current |
A |
789 |
1 245 |
1 577 |
1 826 |
Rated supply voltage, electronics power supply |
V |
380 (-25 %) … 480 V (+10 %) 2 AC;In = 1 A or |
|||
Rated fan supply voltage |
V |
400 V 3 AC ± 10 % (50 Hz) |
|||
Rated fan current |
A |
0.3 3) |
1 4) |
||
Air flow |
m3/h |
1 000 |
2 400 |
||
Sound pressure level2) |
dB (A) |
64.5 |
75.6 |
||
Rated field supply voltage1) |
V |
480 V 2 AC |
|||
Rated frequency |
Hz |
45 … 65 |
|||
Rated DC voltage 1) |
V |
875 |
1 000 |
||
Rated DC current |
A |
950 |
1 500 |
1 900 |
2 200 |
Overload capability |
x In |
1.8 |
|||
Rated power |
kW |
831 |
1 313 |
1 663 |
2 200 |
Power loss at rated DC current |
kW |
4.22 |
7.12 |
8.67 |
11.34 |
Rated DC field voltage 1) |
V |
max. 390 |
|||
Rated DC field current |
A |
40 |
|||
Normal ambient temperature in operation5) |
°C |
0 … +40 |
|||
Storage and transport temperature |
°C |
-40 … +70 |
|||
Installation altitude above sea level5) |
1 000 m for rated DC current |
||||
Dimensions |
|||||
|
mm |
268 |
453 |
||
|
mm |
785 |
883 |
||
|
mm |
435 |
505 |
||
Weight, approx. |
kg |
78 |
155 |
185 |
Note:
Detailed dimension drawings in the PDF and DXF formats are available on the DVD-ROM supplied with Catalog D 23.1 and in the Internet under
http://www.siemens.com/sinamics-dcm
(information material).
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set via parameter; in the case of units with a 400 V rated voltage, an input voltage of up to 85 V is permitted). The output voltage decreases accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage).
2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply)
3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit-breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A.
4) For fan motor type RH28M-2DK.3F.1R in units 6RA8090, 6RA8091, 6RA8093, and 6RA8095 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit-breaker of type 3RV1011-0KA1 or 3RV1011-1AA1, set to 1.25 A.
5) Derating factors for higher temperatures and installation altitudes, see „Current derating“.