Order No. |
6EP1 437-3BA10 |
Technical specifications |
|
Product |
SITOP PSU300M |
Power supply, type |
24 V/40 A |
Input |
|
Input |
3-phase AC |
Rated voltage value Vin rated min. |
400 V |
Supply voltage |
|
|
|
|
|
Rated voltage value Vin rated max. |
500 V |
Supply voltage |
|
|
|
|
|
|
|
|
|
|
|
|
|
Voltage range |
320 … 575 V |
Input voltage |
|
|
|
|
|
|
|
Overvoltage resistance |
|
Mains buffering at Iout rated, min. |
15 ms |
Mains buffering |
at Vin = 400 V |
Rated line frequency |
|
|
50 Hz |
|
60 Hz |
Rated line range |
47 … 63 Hz |
Input current |
|
|
|
|
|
|
2.6 A |
|
2.1 A |
|
|
Switch-on current limiting (+25 °C), max. |
56 A |
I t, max. |
2.24 A ·s |
Built-in incoming fuse |
none |
Protection in the mains power input (IEC 898) |
Required: 3-pole connected miniature circuit breaker 10 ... 16 A characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) |
Output |
|
Output |
controlled, isolated DC voltage |
Rated voltage Vout DC |
24 V |
Total tolerance, static ± |
3 % |
Static mains compensation, approx. |
0.1 % |
Static load balancing, approx. |
0.2 % |
Residual ripple peak-peak, max. |
100 mV |
Residual ripple peak-peak, typ. |
|
Spikes peak-peak, max. (bandwidth: 20 MHz) |
200 mV |
Spikes peak-peak, typ. (bandwidth: 20 MHz) |
|
Adjustment range |
24 … 28.8 V |
Product feature output voltage adjustable |
Yes |
Output voltage setting |
via potentiometer |
Note |
max. 960 W |
Status display |
Green LED for 24 V OK |
Signaling |
Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK" |
On/off behavior |
No overshoot of Vout (soft start) |
Startup delay, max. |
2.5 s |
Note |
|
Voltage rise, typ. |
|
Voltage increase time of the output voltage maximum |
500 ms |
Rated current value Iout rated |
40 A |
Current range |
0 … 40 A |
Note |
25 A up to +70 °C |
delivered active power typ. |
960 W |
short-term overload current at short-circuit during run-up typical |
|
Duration of overloading ability for excess current on short-circuiting during the start-up |
|
constant overload current at short-circuit during run-up typical |
44 A |
short-term overload current at short-circuit during operation typical |
120 A |
Duration of overloading ability for excess current on short-circuiting during the operational phase |
25 ms |
constant overload current at short-circuit during operation typical |
|
Parallel switching for enhanced performance |
Yes |
Note |
switchable characteristic |
Numbers of parallel switchable units for enhanced performance |
2 |
Efficiency |
|
Efficiency at Vout rated, Iout rated, approx. |
92 % |
Power loss at Vout rated, Iout rated, approx. |
83 W |
Closed-loop control |
|
Dynamic mains compensation (Vin rated ±15 %), max. |
1 % |
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. |
3 % |
Load step setting time 50 to 100%, typ. |
|
Load step setting time 100 to 50%, typ. |
|
Setting time maximum |
10 ms |
Protection and monitoring |
|
Output overvoltage protection |
< 35 V |
Current limitation, typ. |
44 A |
Characteristic feature of the output short-circuit protected |
Yes |
Short-circuit protection |
Alternatively, constant current characteristic approx. 44 A or latching shutdown |
Enduring short circuit current Effective level typical |
44 A |
Note |
overload capability 150 % Iout rated up to 5 s/min |
Overload/short-circuit indicator |
LED yellow for "overload", LED red for "latching shutdown" |
Safety |
|
Primary/secondary isolation |
Yes |
Potential separation |
Safety extra low output voltage Vout according to EN 60950-1 and EN 50178 |
Protection class |
Class I |
stray current |
|
|
3.5 mA |
|
|
CE mark |
Yes |
UL/CSA approval |
Yes |
UL/cUL (CSA) approval |
cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 |
Explosion protection |
in preparation |
FM approval |
No |
FM approval |
- |
CB approval |
No |
Marine approval |
GL and ABS in process |
Degree of protection (EN 60529) |
IP20 |
EMC |
|
Emitted interference |
EN 55022 Class B |
Supply harmonics limitation |
EN 61000-3-2 |
Noise immunity |
EN 61000-6-2 |
Operating data |
|
Ambient temperature |
|
|
-25 … +70 °C |
|
with natural convection |
Ambient temparature |
|
|
-40 … +85 °C |
Ambient temparature |
|
|
-40 … +85 °C |
Humidity class according to EN 60721 |
Climate class 3K3, no condensation |
Mechanics |
|
Connection technology |
screw-type terminals |
Connections |
|
|
L1, L2, L3, PE: 1 screw terminal each for 0.2 ... 4 mm single-core/finely stranded |
|
+, -: 2 screw terminals each for 0.33 ... 10 mm |
|
13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm |
Width of the housing |
150 mm |
Height of the housing |
125 mm |
Depth of the housing |
150 mm |
Installation width |
150 mm |
Installation height |
225 mm |
Weight, approx. |
3.4 kg |
Product feature of the housing housing for side-by-side mounting |
Yes |
Type of mounting wall mounting |
No |
Type of fixing cap rail mounting |
Yes |
Type of mounting S7-300 rail mounting |
No |
Installation |
Snaps onto DIN rail EN 60715 35x15 |
Electrical accessories |
Buffer module |
Mechanical accessories |
Device identification label 20 mm 7 mm, pastel-turpuoise 3RT1900-1SB20 |