6ES7 326-2BF10-0AB0 |
6ES7 326-2BF41-0AB0 |
|
|
Supply voltage |
||
|
Load voltage L+ |
||
|
24 V; 1L+, 2L+, 3L+ |
24 V; 1L+, 2L+, 3L+ |
|
Input current |
||
|
from load voltage1L+, max. |
100 mA; from supply voltage |
75 mA; from supply voltage |
|
from load voltage 2L+ (without load), max. |
100 mA |
100 mA |
|
from load voltage 3L+ (without load), max. |
100 mA |
100 mA |
|
from backplane bus 5 V DC, max. |
100 mA |
100 mA |
|
Power losses |
||
|
Power loss, typ. |
6 W |
12 W |
|
Digital outputs |
||
|
Number/binary outputs |
10 |
8 |
|
Functionality/short-circuit strength |
Yes; Electronic |
Yes; Electronic |
|
Limitation of inductive shutdown voltage to |
L+ (-33 V) |
|
|
Lamp load, max. |
5 W |
5 W |
|
Output voltage |
||
|
L+ (-1.0 V) |
|
|
Output current |
||
|
2 A |
2 A |
|
7 mA |
7 mA |
|
2.4 A |
2 A; 2 A for horizontal installation, 1 A for vertical installation |
|
7 mA |
7 mA |
|
2.4 A |
1 A; for horizontal installation |
|
0.5 mA |
0.5 mA |
|
Switching frequency |
||
|
25 Hz |
30 Hz |
|
25 Hz |
2 Hz |
|
10 Hz |
10 Hz |
|
Aggregate current of outputs (per group) |
||
|
||
|
10 A |
7.5 A |
|
6 A |
5 A |
|
||
|
5 A |
5 A |
|
Cable length |
||
|
1 000 m |
200 m; 200 m for SIL3, AK 6, Cat 4 |
|
600 m |
200 m |
|
Interrupts/diagnostics/status information |
||
|
Alarms |
||
|
Yes |
Yes; Parameterizable |
|
Diagnoses |
||
|
Yes |
Yes |
|
Galvanic isolation |
||
|
Galvanic isolation digital outputs |
||
|
Yes |
Yes |
|
5 |
4 |
|
Yes |
Yes |
|
Yes |
Yes |
|
Isolation |
||
|
Isolation checked with |
370 V for 1 min |
500 V DC / 350 V AC |
|
Standards, approvals, certificates |
||
|
Highest safety class achievable in safety mode |
||
|
AK 5 and 6 |
|
|
Cat. 4 |
Cat. 4 |
|
SIL 3 |
SIL 3 |
|
Connection method |
||
|
required front connector |
40-pin |
40-pin |
|
Dimensions |
||
|
Width |
40 mm |
80 mm |
|
Height |
125 mm |
125 mm |
|
Depth |
120 mm |
120 mm |
|
Weight |
||
|
Weight, approx. |
330 g |
465 g |