Siemens
СРЕДСТВА ПРОМЫШЛЕННОЙ АВТОМАТИЗАЦИИ
официальный партнер Сименс
Каталог СА01 2012
архивный
(4872) 700-366
skenergo@mail.ru
SIPLUS CPU 417H

6ES7 417-4HT14-0AB0

Product version

Hardware product version

1

Firmware version

V4.5

General information

associated programming package

STEP7 V 5.3 SP2 or higher with HW update

CiR - Configuration in RUN

CiR synchronization time, basic load

60 ms

CiR synchronization time, time per I/O slave

10 µs

Supply voltage

24 V DC

No; Power supply via system power supply

Input current

from backplane bus 5 V DC, max.

1.8 A

from interface 5 V DC, max.

90 mA; At each DP interface

Power losses

Power loss, typ.

6.5 W

Memory

Work memory

  • integrated

30 Mbyte

  • integrated (for program)

15 Mbyte

  • integrated (for data)

15 Mbyte

  • expandable

No

Load memory

  • expandable FEPROM

Yes

  • expandable FEPROM, max.

64 Mbyte

  • integrated RAM, max.

256 Kibyte

  • expandable RAM

Yes

  • expandable RAM, max.

64 Mbyte

Backup

  • present

Yes

  • with battery

Yes; all data

  • without battery

No

CPU-blocks

DB

  • Number, max.

8 191; Number range: 1 - 8191

  • Size, max.

64 Kibyte

FB

  • Number, max.

6 144; Number range: 0 - 6143

  • Size, max.

64 Kibyte

FC

  • Number, max.

6 144; Number range: 0 - 6143

  • Size, max.

64 Kibyte

OB

  • Size, max.

64 Kibyte

Nesting depth

  • per priority class

24

  • additional within an error OB

2

CPU processing times

for bit operations, min.

0.018 µs

for word operations, min.

0.018 µs

for fixed point arithmetic, min.

0.018 µs

for floating point arithmetic, min.

0.054 µs

Counters, timers and their retentivity

S7 counter

  • Number

2 048

  • Retentivity

    • adjustable

Yes

    • lower limit

0

    • upper limit

2 047

    • preset

Z 0 to Z 7

  • Counting range

    • lower limit

0

    • upper limit

999

IEC counter

  • present

Yes

  • Type

SFB

S7 times

  • Number

2 048

  • Retentivity

    • adjustable

Yes

    • lower limit

0

    • upper limit

2 047

    • preset

No times retentive

  • Time range

    • lower limit

10 ms

    • upper limit

9 990 s

IEC timer

  • present

Yes

  • Type

SFB

Data areas and their retentivity

retentive data area, total

Total working and load memory (with backup battery)

Flag

  • Number, max.

16 Kibyte

  • Retentivity available

Yes

  • Retentivity preset

MB 0 to MB 15

  • Number of clock memories

8; (in 1 memory byte)

Local data

  • adjustable, max.

64 Kibyte

  • preset

32 Kibyte

Address area

I/O address area

  • Inputs

16 Kibyte

  • Outputs

16 Kibyte

  • of which, distributed

    • MPI/DP interface, inputs

2 Kibyte

    • MPI/DP interface, outputs

2 Kibyte

    • DP interface, inputs

8 Kibyte

    • DP interface, outputs

8 Kibyte

Process image

  • Inputs, adjustable

16 Kibyte

  • Outputs, adjustable

16 Kibyte

  • Inputs, default

1 024 byte

  • Outputs, default

1 024 byte

  • consistent data, max.

244 byte

  • Access to consistent data in process image

Yes

Subprocess images

  • Number of subprocess images, max.

15

Digital channels

  • Inputs

131 072

  • Outputs

131 072

  • Inputs, of which central

131 072

  • Outputs, of which central

131 072

Analog channels

  • Inputs

8 192

  • Outputs

8 192

  • Inputs, of which central

8 192

  • Outputs, of which central

8 192

Hardware configuration

Expansion devices, max.

21

Multicomputing

No

Interface modules

  • Number of connectable IMs (total), max.

6

  • Number of connectable IM 460s, max.

6

  • Number of connectable IM 463s, max.

4; Single mode only

Number of DP masters

  • integrated

2

  • via CP

10

  • Mixed mode IM + CP permitted

No

Number of operable FMs and CPs (recommended)

  • FM

See manual Automation System S7-400H fault-tolerant systems. Limited by number of slots and number of connections

  • CP, point-to-point

See manual Automation System S7-400H fault-tolerant systems. Limited by number of slots and number of connections

  • PROFIBUS and Ethernet CPs

14; Of which max. 10 CP as DP master

Time of day

Clock

  • Hardware clock (real-time clock)

Yes

  • battery-backed and synchronizable

Yes

  • Resolution

1 ms

  • Deviation per day (buffered), max.

1.7 ms; Power off

  • Deviation per day (unbuffered) max.

8.6 ms; Power on

Operating hours counter

  • Number

8

  • Number/Number range

0 to 7

  • Range of values

0 to 32767 hours

  • Granularity

1 hour

  • retentive

Yes

Clock synchronization

  • supported

Yes

  • to MPI, master

Yes

  • to MPI, slave

Yes

  • to DP, master

Yes

  • to DP, slave

Yes

  • in AS, master

Yes

  • in AS, slave

Yes

1st interface

Type of interface

integrated

Physics

RS 485 / PROFIBUS + MPI

Isolated

Yes

Power supply to interface (15 to 30 V DC), max.

150 mA

Number of connection resources

MPI: 44, DP: 32

Functionality

  • MPI

Yes

  • DP master

Yes

  • DP slave

No

MPI

  • Number of connections

44

  • Services

    • PG/OP communication

Yes

    • Routing

Yes

    • Global data communication

No

    • S7 basic communication

No

    • S7 communication

Yes

    • S7 communication, as client

Yes

    • S7 communication, as server

Yes

  • Transmission rate, max.

12 Mbit/s

DP master

  • Number of connections, max.

32

  • Services

    • PG/OP communication

Yes

    • Global data communication

No

    • S7 basic communication

No

    • S7 communication

Yes

    • S7 communication, as client

Yes

    • S7 communication, as server

Yes

    • Equidistance mode support

No

    • SYNC/FREEZE

No

    • Activation/deactivation of DP slaves

No

    • Direct data exchange (slave-to-slave communication)

No

  • Transmission rate, max.

12 Mbit/s

  • Number of DP slaves, max.

32

  • Address area

    • Inputs, max.

2 Kibyte

    • Outputs, max.

2 Kibyte

  • User data per DP slave

    • User data per DP slave, max.

244 byte

    • Inputs, max.

244 byte

    • Outputs, max.

244 byte

    • Slots, max.

244

    • per slot, max.

128 byte

2nd interface

Type of interface

integrated

Physics

RS 485 / PROFIBUS + MPI

Isolated

Yes

Power supply to interface (15 to 30 V DC), max.

150 mA

Number of connection resources

32

Functionality

  • DP master

Yes

  • DP slave

No

DP master

  • Number of connections, max.

32

  • Services

    • PG/OP communication

Yes

    • Global data communication

No

    • S7 basic communication

No

    • S7 communication

Yes

    • Equidistance mode support

No

    • SYNC/FREEZE

No

    • Direct data exchange (slave-to-slave communication)

No

  • Transmission rate, max.

12 Mbit/s

  • Number of DP slaves, max.

125

  • Address area

    • Inputs, max.

8 Kibyte

    • Outputs, max.

8 Kibyte

  • User data per DP slave

    • User data per DP slave, max.

244 byte

    • Inputs, max.

244 byte

    • Outputs, max.

244 byte

    • Slots, max.

244

    • per slot, max.

128 byte

3rd interface

Type of interface

Pluggable synchronization submodule (FO)

Plug-in interface modules

Synchronization submodule IF 960 6ES7 960-1AA04-0XA0 or 6ES7 960-1AB04-0XA0

4th interface

Type of interface

Pluggable synchronization submodule (FO)

Plug-in interface modules

Synchronization submodule IF 960 6ES7 960-1AA04-0XA0 or 6ES7 960-1AB04-0XA0

Communication functions

PG/OP communication

Yes

  • Number of connectable OPs without message processing

63

  • Number of connectable OPs with message processing

16

Global data communication

  • supported

No

S7 basic communication

  • supported

No

S7 communication

  • supported

Yes

  • as server

Yes

  • as client

Yes

  • User data per job, max.

64 Kibyte

  • User data per job (of which consistent), max.

462 byte; 1 variable

S5-compatible communication

  • supported

Yes; (via CP max. 10 and FC AG_SEND and FC AG_RECV)

  • User data per job, max.

8 Kibyte

  • User data per job (of which consistent), max.

240 byte

  • Number of simultaneous AG-SEND/AG-RECV orders per CPU, max.

64/64

Standard communication (FMS)

  • supported

Yes; Via CP and loadable FB

Number of connections

  • overall

64

S7 message functions

Number of login stations for message functions, max.

16

Symbol-related messages

No

Block related messages

Yes

simultaneously active Alarm-S blocks, max.

200

Alarm 8-blocks

Yes

  • Number of instances for alarm 8 and S7 communication blocks, max.

10 000

  • preset, max.

1 200

Process control messages

Yes

Test commissioning functions

Status/control

  • Status/control variable

Yes

  • Variables

Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters

  • Number of variables, max.

70

Forcing

  • Forcing

Yes

  • Force, variables

Inputs/outputs, bit memories, distributed I/Os

  • Number of variables, max.

512

Status block

Yes

Single step

Yes

Number of breakpoints

4

Diagnostic buffer

  • present

Yes

  • Number of entries, max.

3 200

    • adjustable

Yes

    • preset

120

Configuration

Configuration software

  • STEP 7

Yes; With hardware update as of STEP7 V5.3 SP2

programming

  • Programming language

    • LAD

Yes

    • FBD

Yes

    • STL

Yes

    • SCL

Yes

    • CFC

Yes

    • GRAPH

Yes

    • HiGraph®

Yes

  • Command set

see instruction list

  • Nesting levels

8

Know-how protection

  • User program protection/password protection

Yes

Dimensions

Width

50 mm

Height

290 mm

Depth

219 mm

Required slots

2

Weight

Weight, approx.

995 g

























































  © ООО "СК ЭНЕРГО" 2007-2022