6ES7 431-0HH00-0AB0 |
6ES7 431-1KF20-0AB0 |
6ES7 431-1KF00-0AB0 |
6ES7 431-1KF10-0AB0 |
|
Voltages and currents |
||||
Load voltage L+ |
||||
|
24 V |
24 V |
24 V |
|
|
Yes |
Yes |
Yes |
|
Current consumption |
||||
from load voltage L+ (without load), max. |
400 mA; for 16 connected, fully controlled 2-wire transmitters |
200 mA; for 8 connected, fully controlled 2-wire transmitters |
200 mA |
|
from backplane bus DC 5 V, max. |
100 mA |
1 000 mA |
350 mA |
600 mA |
Power loss, typ. |
2 W |
4.9 W |
1.8 W |
3.5 W |
Analog inputs |
||||
Number of analog inputs |
16 |
8 |
8 |
8 |
Number of analog inputs for voltage/current measurement |
16 |
8 |
8 |
8 |
Number of analog inputs for resistance measurement |
4 |
4 |
4 |
|
cable length, shielded, max. |
200 m |
200 m |
200 m |
200 m; 50 m with thermocouples and input ranges <= 80 mV |
permissible input frequency for voltage input (destruction limit), max. |
20 V; 20 V continuous, 75 V for max. 1 s (mark to space ratio 1:20) |
18 V; 18 V continuous, 75 V for 1 ms (mark to space ratio 1:20) |
50 V |
18 V; 18 V continuous, 75 V for 1 ms (mark to space ratio 1:20) |
permissible input current for current input (destruction limit), max. |
40 mA |
40 mA; Permanent |
50 mA; 40 mA continuous |
40 mA; Permanent |
Input ranges (rated values), voltages |
||||
|
Yes |
Yes |
Yes |
Yes |
|
Yes |
Yes |
Yes |
Yes |
|
Yes |
Yes |
Yes |
Yes |
|
Yes |
|||
|
Yes |
|||
|
Yes |
|||
|
Yes |
|||
|
Yes |
|||
Input ranges (rated values), currents |
||||
|
Yes |
|||
|
Yes |
Yes |
Yes |
|
|
Yes |
Yes |
Yes |
Yes |
Input ranges (rated values), thermoelements |
||||
|
Yes |
|||
|
Yes |
|||
|
Yes |
|||
|
Yes |
|||
|
Yes |
|||
|
Yes |
|||
|
Yes |
|||
|
Yes |
|||
|
Yes |
|||
|
Yes |
|||
Input ranges (rated values), resistors |
||||
|
Yes |
|||
|
Yes |
|||
|
Yes |
|||
|
Yes |
Yes |
Yes |
|
|
Yes; usable up to 5000 ohms |
|||
Input ranges (rated values), resistance thermometers |
||||
|
Yes |
|||
|
Yes |
|||
|
Yes |
|||
|
Yes |
|||
|
Yes |
|||
|
Yes |
|||
|
Yes |
|||
Characteristic curve linearization |
||||
|
Yes |
|||
|
Type B, E, J, K, L, N, R, S, T, U |
|||
|
Pt100, Pt200, Pt500, Pt1000, Ni100, Ni1000 |
|||
Temperature compensation |
||||
|
Yes |
|||
|
Yes |
|||
|
No |
|||
|
Yes |
|||
Analog value creation |
||||
Integration and conversion time/resolution per channel |
||||
|
13 Bit |
14 Bit; 14 / 14 / 14 |
13 Bit |
14 Bit; with activated smoothing: 16 Bit |
|
Yes |
Yes |
Yes |
Yes |
|
50 / 60 ms |
16.7 / 20 ms |
16.7 / 20 ms |
|
|
55 / 65 ms |
52 µs |
23 / 25 ms |
20.1 / 23.5 ms |
|
4.3 ms |
|||
|
5.5 ms |
|||
|
40.2 / 47 ms |
|||
|
60 / 50 Hz |
none / 400 / 60 / 50 Hz |
60 / 50 Hz |
60 / 50 Hz |
Encoder |
||||
Connection of signal encoders |
||||
|
Yes |
Yes; with external transmitter supply |
Yes |
|
|
Yes |
Yes |
Yes |
Yes |
|
Yes; Line resistances are also measured |
Yes; Line resistances are also measured |
Yes; Line resistances are also measured |
|
|
Yes; Line resistances are also measured |
Yes; Line resistances are also measured |
Yes |
|
|
Yes |
Yes |
Yes |
|
Errors/accuracies |
||||
Operational limit in overall temperature range |
||||
|
0,65 +/- %; 1.0% at 1 to 5 V; 0.65% at +/-1 V, +/-10 V |
0,7 +/- %; +/-0.7% at +/-1 V; +/-0.9% at +/-10 V, 1 to 5 V |
1 +/- %; +/-1.0% at +/-1 V; +/-0.6% at +/-10 V; +/-0.7% at 1 to 5 V |
0,38 +/- %; +/-0.38% at +/-80 mV; +/-0.35% at +/-250 mV, +/-500mV, +/-1 V, +/-2,5 V, +/-5 V, 1 to 5 V, +/-10 V |
|
0,65 +/- % |
0,8 +/- %; at +/-20 mA, 4 to 20 mA |
1 +/- %; at +/-20 mA, 4 to 20 mA |
0,35 +/- %; 0 to 20 mA, +/-20 mA, 4 to 20 mA |
|
1 +/- % |
1,25 +/- %; 0 to 500 ohms (4-conductor measurement, in range of 600 ohms) |
0,5 +/- % |
|
|
0,5 +/- % |
|||
Basic error limit (operational limit at 25 °C) |
||||
|
0,25 +/- %; 0.5% at 1 to 5 V; 0.25% at +/-1 V, +/-10 V |
0,6 +/- %; 0.6% at +/-1 V; 0.75% at +/-10 V, 1 to 5 V |
0,7 +/- %; 0.7% at +/-1 V; 0.4% at +/-10 V; 0.5% at 1 to 5 V |
0,15 +/- %; +/-0.15% (+/-250 mV, +/-500 mV, +/-1 V, +/-2.5 V, +/-5 V, 1 to 5 V, +/- 10 V); +/-0.17% (+/- 80 mV); |
|
0,25 +/- % |
0,7 +/- % |
0,7 +/- % |
0,15 +/- %; 0 to 20 mA, +/- 20 mA, 4 to 20 mA |
|
0,7 +/- %; 0 to 600 ohms |
0,8 +/- %; 0 to 500 ohms (4-conductor measurement, in range of 600 ohms) |
0,15 +/- %; +/-0.15% at 0 to 48 ohms (4-conductor measurement), 0 to 150 ohms (4-conductor measurement), 0 to 300 ohms (4-conductor measurement), 0 to 600 ohms (4-conductor measurement), 0 to 5000 ohms (4-conductor measurement, in range of 6000 ohms); +/-0.3% at 0 to 300 ohms (3-conductor measurement), 0 to 600 ohms (3-conductor measurement), 0 to 5000 ohms (3-conductor measurement, in range of 6000 ohms) |
|
|
0,3 +/- % |
|||
Isolation |
||||
Isolation checked with |
500 V DC between bus and local ground |
2120 V DC between bus and analog part; 500 V DC between bus and local ground; 707 V DC between analog part and L+/M; 2120 V DC between analog part and local ground; 2120 V DC between L+/M and local ground |
2120 V DC between bus and analog part; 500 V DC between bus and local ground; 2120 V DC between analog part and local ground |
2120 V DC between bus and L+/M; 2120 V D between bus and analog part; 500 V DC between bus and local ground; 707 V DC between analog part and L+/M; 2120 V DC between analog part and local ground; 2120 V DC between L+/M and local ground |
Isolation |
||||
Isolation, analog inputs |
||||
|
No |
Yes; internal/external |
Yes; internal/external |
Yes; internal/external |
|
No |
No |
No |
No |
Permissible potential difference |
||||
between the inputs (UCM) |
2 V DC / 2 Vpp AC |
8 V AC |
30 V AC |
120 V AC |
Dimensions |
||||
Dimensions |
||||
Width |
25 mm |
25 mm |
25 mm |
25 mm |
Height |
290 mm |
290 mm |
290 mm |
290 mm |
Depth |
210 mm |
210 mm |
210 mm |
210 mm |
Dimensions |
||||
Required slots |
1 |
1 |
1 |
1 |
Weights |
||||
Weight, approx. |
500 g |
500 g |
500 g |
500 g |