Control unit ATEX IIG, compensation of losses through leaks |
|
Guidelines |
EC EMC directive 89/336/EEC, EC low voltage, RL 73/23/EEC, Ex directive 94/9/EC |
Design |
Explosion-protected enclosure (EEx e) with viewing window in the cover |
Enclosure material |
Glass fiber-reinforced polyester |
Degree of protection |
IP65 |
Terminals |
2.5 mm, finely stranded |
Pressure sensors |
MIN A = 0 … 300 hPa, |
Prepurging time |
0 … 99 min; 5 sec dropout delayed |
Weight |
11 kg |
Electrical data |
|
Supply voltage |
230 V AC (115 V AC) ± 10 %, 48 … 62 Hz |
Power consumption |
21 W /230 V |
NO contacts |
K2/3; max. 250 V, 5 A with cos = 1, K4/K5; supply voltage or floating, max. 250 V, 5 A with cos = 1 |
Communication |
RS 485 interface |
Temperature switching value (option) |
0 … +40 °C |
Explosion protection |
|
Marking |
EEx e d ib [ia p] IIC T4/T6 |
Test certification |
DMT 99 ATEX E 082 |
Ambient temperature |
-20 … +40 °C |