Order No. |
6EP1 337-3BA00 |
Technical specifications |
|
Product |
SITOP modular |
Power supply, type |
24 V/40 A |
Input |
|
Input |
1-phase and 2-phase AC |
Rated voltage value Vin rated min. |
|
Supply voltage |
|
|
|
|
|
Rated voltage value Vin rated max. |
|
Supply voltage |
|
|
|
|
|
|
120 V |
|
230 V |
|
|
|
Set by means of wire jumper on the device; starting from Vin > 95/190 V |
Voltage range |
|
Input voltage |
|
|
85 … 132 V |
|
176 … 264 V |
|
|
Overvoltage resistance |
2.3 Vin rated, 1.3 ms |
Mains buffering at Iout rated, min. |
20 ms |
Mains buffering |
at Vin = 230 V |
Rated line frequency |
|
|
50 Hz |
|
60 Hz |
Rated line range |
47 … 63 Hz |
Input current |
|
|
15 A |
|
8 A |
|
|
|
|
|
|
Switch-on current limiting (+25 °C), max. |
125 A |
I t, max. |
26 A ·s |
Built-in incoming fuse |
Yes |
Protection in the mains power input (IEC 898) |
Recommended miniature circuit breaker at 1-phase operation: 20 A, characteristic C; required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2421-4BA10 (120 V) or 3RV2411-1JA10 (230 V) |
Output |
|
Output |
controlled, isolated DC voltage |
Rated voltage Vout DC |
24 V |
Total tolerance, static ± |
3 % |
Static mains compensation, approx. |
0.1 % |
Static load balancing, approx. |
0.1 % |
Residual ripple peak-peak, max. |
100 mV |
Residual ripple peak-peak, typ. |
60 mV |
Spikes peak-peak, max. (bandwidth: 20 MHz) |
200 mV |
Spikes peak-peak, typ. (bandwidth: 20 MHz) |
120 mV |
Adjustment range |
24 … 28.8 V |
Product feature output voltage adjustable |
Yes |
Output voltage setting |
via potentiometer |
Note |
|
Status display |
Green LED for 24 V OK |
Signaling |
via signaling module (6EP1961-3BA10) |
On/off behavior |
Overshoot of Vout approx. 3 % |
Startup delay, max. |
0.1 s |
Note |
|
Voltage rise, typ. |
50 ms |
Voltage increase time of the output voltage maximum |
|
Rated current value Iout rated |
40 A |
Current range |
0 … 40 A |
Note |
> 60 °C Derating |
delivered active power typ. |
960 W |
short-term overload current at short-circuit during run-up typical |
|
Duration of overloading ability for excess current on short-circuiting during the start-up |
|
constant overload current at short-circuit during run-up typical |
46 A |
short-term overload current at short-circuit during operation typical |
120 A |
Duration of overloading ability for excess current on short-circuiting during the operational phase |
25 ms |
constant overload current at short-circuit during operation typical |
|
Parallel switching for enhanced performance |
Yes |
Note |
switchable characteristic |
Numbers of parallel switchable units for enhanced performance |
2 |
Efficiency |
|
Efficiency at Vout rated, Iout rated, approx. |
88 % |
Power loss at Vout rated, Iout rated, approx. |
131 W |
Closed-loop control |
|
Dynamic mains compensation (Vin rated ±15 %), max. |
1 % |
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. |
2 % |
Load step setting time 50 to 100%, typ. |
2 ms |
Load step setting time 100 to 50%, typ. |
2 ms |
Setting time maximum |
5 ms |
Protection and monitoring |
|
Output overvoltage protection |
< 35 V |
Current limitation, typ. |
46 A |
Characteristic feature of the output short-circuit protected |
Yes |
Short-circuit protection |
Alternatively, constant current characteristic approx. 46 A or latching shutdown |
Enduring short circuit current Effective level typical |
46 A |
Note |
|
Overload/short-circuit indicator |
LED yellow for "overload", LED red for "latching shutdown" |
Safety |
|
Primary/secondary isolation |
Yes |
Potential separation |
Safety extra low output voltage Vout according to EN 60950-1 and EN 50178 |
Protection class |
Class I |
stray current |
|
|
3.5 mA |
|
0.4 mA |
CE mark |
Yes |
UL/CSA approval |
Yes |
UL/cUL (CSA) approval |
cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 |
Explosion protection |
- |
FM approval |
No |
FM approval |
- |
CB approval |
No |
Marine approval |
- |
Degree of protection (EN 60529) |
IP20 |
EMC |
|
Emitted interference |
EN 55022 Class B |
Supply harmonics limitation |
- |
Noise immunity |
EN 61000-6-2 |
Operating data |
|
Ambient temperature |
|
|
0 … 70 °C |
|
with natural convection |
Ambient temparature |
|
|
-40 … +85 °C |
Ambient temparature |
|
|
-40 … +85 °C |
Humidity class according to EN 60721 |
Climate class 3K3, no condensation |
Mechanics |
|
Connection technology |
screw-type terminals |
Connections |
|
|
L, N, PE: 1 screw terminal each for 0.2 ... 4 mm single-core/finely stranded |
|
L+, M: 2 screw terminals each for 0.5 ... 10 mm |
|
- |
Width of the housing |
240 mm |
Height of the housing |
125 mm |
Depth of the housing |
125 mm |
Installation width |
240 mm |
Installation height |
225 mm |
Weight, approx. |
2.9 kg |
Product feature of the housing housing for side-by-side mounting |
Yes |
Type of mounting wall mounting |
No |
Type of fixing cap rail mounting |
Yes |
Type of mounting S7-300 rail mounting |
No |
Installation |
Snaps onto DIN rail EN 60715 35x15 |
Electrical accessories |
Buffer module, signaling module |
Mechanical accessories |