19" central unit

The following table lists the measuring conditions for standard applications. The listed values for the measuring range and detection limit (DL) are only approximate values. The exact values at the respective measuring point depend on the totality of all influencing variables and can be determined by Siemens for the specific case. Please note that the values for the detection limit and the maximum measuring range refer to an optical path of 1 m. Longer path lengths will improve the detection limit, but not linearly. due to limiting effects such as dust load. The maximum applicable measuring ranges can only be used if permitted by the process conditions such as dust load.

Standard application

Effective optical path length: 0.3 … 12 m

Dust load3): < 50 g/Nm3

Process gas temperature

Tmin  … Tmax

Process gas pressure pmin  … pmax

Min. measuring range

(with 1 m eff. opt. path length)

Max. measuring range

(also dependent on eff. opt. path length: see following column)

(Max. measuring range x path length)

(DL x path length)

Accuracy4)

under standard conditions1) 2)without cross-interference of other gases

At 1 013 hPa with cross-interference of gas 2

Gas 1

Gas 2

Gas code

Appl. code

Gas 1

Gas 1

Gas 1

Gas 1

Gas 1

Gas 1

O2

A

B

600 … 1 200 °C

950 …1 050 hPa

0 … 15 vol%

0 … 100 vol%

240 vol%*m

0.3 vol%*m
At 600 °C

5 %

C

0 … 600 °C

950 …1 050 hPa

0 … 5 vol%

0 … 100 vol%

75 vol%*m

0.1 vol%*m

2 %5)

P

0 … 200 °C

950 …5 000 hPa

0 … 5 vol%

0 … 100 vol%

75 vol%*m

0.1 vol%*m

2 %

O2

Temp

B

B

600 … 1 200 °C

950 …1 050 hPa

0 … 35 vol%

0 … 100 vol%

240 vol%*m

0.7 vol%*m
At 600 °C

5 %

NH3

C

A

0 … 150 °C

950 …1 050 hPa

0 … 25 ppmv

0 … 500 ppmv

2 500 ppmv*m

0.5 ppmv*m

0.9 ppmv*m

At 15 vol% H2O, 55 °C

2 %

T

0 … 150 °C

950 …1 050 hPa

0 … 25 ppmv

0 … 500 ppmv

2 500 ppmv*m

0.5 ppmv*m

0.9 ppmv*m

At 15 vol% H2O, 55 °C

2 %

E

250 … 350 °C

950 …1 050 hPa

0 … 45 ppmv

0 … 500 ppmv

2 500 ppmv*m

0.9 ppmv*m

At 250 °C

1.4 ppmv*m

at 15 Vol% H2O, 250 °C

2 %

F

300 … 400 °C

950 …1 050 hPa

0 … 50 ppmv

0 … 500 ppmv

2 500 ppmv*m

1 ppmv*m

At 300 °C

1.5 ppmv*m

at 15 Vol% H2O, 300 °C

2 %

NH3

H2O

D

A

0 … 150 °C

950 …1 050 hPa

0 … 25 ppmv

0 … 100 ppmv

1 200 ppmv*m

0.5 ppmv*m

0.9 ppmv*m

At 15 vol% H2O, 55 °C

2 %

T

0 … 150 °C

950 …1 050 hPa

0 … 25 ppmv

0 … 100 ppmv

1 200 ppmv*m

0.5 ppmv*m

0.9 ppmv*m

At 15 vol% H2O, 55 °C

2 %

E

250 … 350 °C

950 …1 050 hPa

0 … 45 ppmv

0 … 100 ppmv

1 200 ppmv*m

0.9 ppmv*m

At 250 °C

1.4 ppmv*m

At 15 vol% H2O, 250 °C

2 %

F

300 … 400 °C

950 …1 050 hPa

0 … 50 ppmv

0 … 100 ppmv

1 200 ppmv*m

1 ppmv*m

At 300 °C

1.5 ppmv*m

At 15 vol% H2O, 300 °C

2 %

HCl

E

A

0 … 150 °C

950 …1 050 hPa

0 … 30 ppmv

0 … 6 000  ppmv

1 200 ppmv*m

0.6 ppmv*m

2.2 ppmv*m

At 15 % H2O, 55 °C

5 %

T

120 … 210 °C

950 …1 050 hPa

0 … 10 ppmv

0 … 60 ppmv

720 ppmv*m

H

150 … 250 °C

950 … 1 050 hPa

0 … 50 ppmv

0 … 6 000 ppmv

1 200 ppmv*m

1.0 ppmv*m

At 150 °C

3.1 ppmv*m

at 15 Vol% H2O, 150 °C

5 %

HCl

H2O

F

A

0 … 150 °C

950 …1 050 hPa

0 … 30 ppmv

0 … 100 ppmv

1 200 ppmv*m

0.6 ppmv*m

2.2 ppmv*m

At 15 % H2O, 55 °C

5 %

T

120 … 210 °C

950 …1 050 hPa

0 … 10 ppmv

0 … 60 ppmv

720 ppmv*m

H

150 … 250 °C

950 … 1 050 hPa

0 … 50 ppmv

0 … 100 ppmv

1 200 ppmv*m

1.0 ppmv*m

At 150 °C

3.1 ppmv*m

At 15 vol% H2O, 150 °C

5 %

HF

G

A

0 … 150 °C

950 …1 050 hPa

0 … 5 ppmv

0 … 1 500 ppmv

200 ppmv*m

0.1 ppmv*m

0.6 ppmv*m

At 15 vol% H2O, 55 °C

5 %

H

150 … 250 °C

950 … 1 050 hPa

0 … 5 ppmv

0 … 1 500 ppmv

200 ppmv*m

0.11 ppmv*m

At 150 °C

0.6 ppmv*m

At 15 vol% H2O, 150 °C

5 %

HF

H2O

H

A

0 … 150 °C

950 …1 050 hPa

0 … 5 ppmv

0 … 200 ppmv

200 ppmv*m

0.1 ppmv*m

0.6 ppmv*m

At 15 vol% H2O, 55 °C

5 %

H

150 … 250 °C

950 … 1 050 hPa

0 … 5 ppmv

0 … 200 ppmv

200 ppmv*m

0.11 ppmv*m

At 150 °C

0.6 ppmv*m

At 15 vol% H2O, 150 °C

5 %

CO

J

C

0 … 600 °C

950 …1 050 hPa

0 … 1.5 vol%

0 … 100 vol%

40 vol%*m

300 ppmv*m

1 500 ppmv*m

at 50 vol% CO2, 20 °C

2 %

CO

CO2

K

D

0 … 400 °C

800 …1 400 hPa

0 … 3.0 vol%

0 … 100 vol%

35 vol%*m

0.5 vol%*m

0.7 vol%*m

at 50 vol% CO2, 20 °C

2 %6)

CO2

L

A

0 … 150 °C

950 …1 050 hPa

0 … 7.5 vol%

0 … 100 vol%

40 vol%*m

300 ppmv*m

2 %

H2O

M

A

0 … 150 °C

950 …1 050 hPa

0 … 5 vol%

0 … 30 vol%

240 vol%*m

0.1 vol%*m

5 %

T

0 … 150 °C

950 …1 050 hPa

0 … 5 vol%

0 … 30 vol%

240 vol%*m

0.1 vol%*m

5 %


1) At 20 °C, 1 013 hPa

2) If the smallest permissible process gas temperature of the application is Tmin > 20 °C, the detection limit refers to Tmin and standard pressure (1 013 hPa)

3) At 0.3 m effective optical path length, average diameter of the dust particles: 15 µm, specific weight of the dust particles: 650 kg/m3

4) At least: Detection limit

5) Up to 200 °C, 5% above this

6) Up to 60 vol% CO or up to 60 vol% CO2. Higher CO or CO2 concentrations on request.

Standard application

Effective optical path length: 0.3 … 12 m

Dust load3): < 50 g/Nm3

Min. measuring range

(with 1 m eff. opt. path length)

Max. measuring range

(usually also dependent on eff. opt. path length: see following column)

(Max. measuring range x path length)

(DL x path length)

Accuracy5)

Purging gas mode

Purging gas medium

under standard conditions1) 2)

At 1 013 hPa with cross-interference of gas 1

Gas 1

Gas 2

Gas code

Appl. code

Gas 2

Gas 2

Gas 2

Gas 2

Gas 2

Gas 2

Standard

Optional

O2

A

B

E, F

G, H

Steam + air, N2

C

D

B

N2

P

D

B

N2

O2

Temp

B

B

600 … 1 200 °C

5)

F

H

Steam, N2

NH3

C

A


C

G

Air

T


C

G

Air

E


E

G

Air

F


E

G

Air

NH3

H2O

D

A


0 … 5 vol%

0 … 30 vol%

240 vol%*m

0.1 vol%*m

0.1 vol%*m

5 %

C

G

Air

T


0 … 5 vol%

0 … 30 vol%

240 vol%*m

0.1 vol%*m

0.1 vol%*m

5 %

C

G

Air

E


0 … 5 vol%

0 … 30 vol%

240 vol%*m

0.1 vol%*m

At 250 °C

0.1 vol%*m

At 250 °C

5 %

E

G

Air

F


0 … 5 vol%

0 … 30 vol%

240 vol%*m

0.1 vol%*m

at 300 °C"

0.1 vol%*m

At 300 °C

5 %

E

G

Air

HCl

E

A


C

G

Air

T


C

G

Air

H


E

G

Air

HCl

H2O

F

A


0 … 5 vol%

0 … 30 vol%

360 vol%*m

0.1 vol%*m

0.1 vol%*m

5 %

C

G

Air

T


0 … 5 vol%

0 … 30 vol%

360 vol%*m

C

G

Air

H


0 … 5 vol%

0 … 30 vol%

360 vol%*m

0.1 vol%*m

At 150 °C

0.1 vol%*m

At 150 °C

5 %

E

G

Air

HF

G

A


C

G

Air

H


E

G

Air

HF

H2O

H

A


0 … 5 vol%

0 … 30 vol%

360 vol%*m

0.1 vol%*m

0.1 vol%*m

5 %

C

G

Air

H


0 … 5 vol%

0 … 30 vol%

360 vol%*m

300 ppmv*m

At 200 °C

300 ppmv*m

At 200 °C

5 %

E

G

Air

CO

J

C


E

G

Air, N2

CO

CO2

K

D

0 … 7.5 vol%

0 … 100 vol%

75 vol%*m

0.5 vol%*m

1 500 ppmv*m

At 50 vol% CO, 20 °C

2 … 5 %6)

C

G

Air

CO2

L

A

C

G

Air

H2O

M

A

C

G

Air

T

C

G

Air


1) At 20 °C, 1 013 hPa

2) If the smallest permissible process gas temperature of the application is Tmin > 20 °C, the detection limit refers to Tmin and standard pressure (1 013 hPa)

3) At 0.3 m optical path length, average diameter of the dust particles: 15 µm, specific weight of the dust particles: 650 kg/m3

4) At least: Detection limit

5)At 600 °C and at least 5 vol%*m O2 concentration: Resolution = 15 °C, at 1 000 °C and at least 5 vol%*m O2 concentration: Resolution = 25 °C

6) Depends on temperature (higher values at higher temperatures)























































Êàòàëîã îáîðóäîâàíèÿ 2012
Êàòàëîã ïðîäóêòîâ Siemens Industry Ïðèâîäíàÿ òåõíèêà Òåõíèêà àâòîìàòèçàöèè Ñèñòåìû àâòîìàòèçàöèè Ñèñòåìû âèçóàëèçàöèè SIMATIC HMI Ñèñòåìû èäåíòèôèêàöèè Ïðîìûøëåííûå êîììóíèêàöèè SIMATIC NET Ïðîìûøëåííûå àïïàðàòû óïðàâëåíèÿ SIRIUS Ïðîìûøëåííûå èíôîðìàöèîííûå òåõíîëîãèè Óïðàâëåíèå íà áàçå ÐÑ Ñèñòåìû óïðàâëåíèÿ ïðîöåññîì Äàò÷èêè Êîíòðîëüíî-èçìåðèòåëüíûå ïðèáîðû Àíàëèçàòîðû ïðîöåññà Íåïðåðûâíûå àíàëèçàòîðû ãàçîâ Íåïðåðûâíûå àíàëèçàòîðû ãàçîâ, ýêòðàêòèâíûå Íåïðåðûâíûé ãàçîâûé àíàëèç, in-situ Introduction to LDS 6 and SITRANS SL LDS 6 General information 19" central unit Cross-duct sensor CD 6 Documentation Suggestions for spare parts SITRANS SL Ïðîìûøëåííûå ãàçîâûå õðîìàòîãðàôû Analytical Application Sets General information Òåõíîëîãèè âçâåøèâàíèÿ Äàò÷èêè çðåíèÿ Áëîêè ïèòàíèÿ Ïðîäóêòû äëÿ ñïåöèàëüíûõ òðåáîâàíèé Àâòîìàòèçàöèÿ çäàíèé Íèçêîâîëüòíàÿ êîììóòàöèîííàÿ òåõíèêà Òåõíîëîãèÿ áåçîïàñíîñòè Ñèñòåìíûå ðåøåíèÿ è ïðîäóêòû äëÿ îòðàñëåé Ñåðâèñ ... è âñå, ÷òî Âàì åùå íåîáõîäèìî

  © ÎÎÎ "ÑÊ ÝÍÅÐÃÎ" 2007-2022
  (4872) 700-366
ßíäåêñ.Ìåòðèêà