Siemens
СРЕДСТВА ПРОМЫШЛЕННОЙ АВТОМАТИЗАЦИИ
официальный партнер Сименс
Каталог СА01 2012
архивный
(4872) 700-366
skenergo@mail.ru
OLM Optical Link Module

Order No.

6GK1 503-2CA00

6GK1 503-3CA00

6GK1 503-4CA00

Product type designation

PROFIBUS OLM P11

PROFIBUS OLM P12

PROFIBUS OLM P22

Transmission rate

Transmission rate

  • with PROFIBUS

9.6 Kbit/s … 12 Mbit/s

9.6 Kbit/s … 12 Mbit/s

9.6 Kbit/s … 12 Mbit/s

  • with PROFIBUS PA

45.45 Kbit/s

45.45 Kbit/s

45.45 Kbit/s

Interfaces

Maximum number of electrical/optical connections for network components or terminal equipment

2

3

4

Number of electrical connections

  • for network components or terminal equipment

1

1

2

  • for measuring instrument

1 1

1 1

1 1

  • for signaling contact

1

1

1

  • for power supply

1

1

1

  • for redundant power supply

1

1

1

Design of electrical connection

  • for network components or terminal equipment

9-pin sub-D socket

9-pin sub-D socket

9-pin sub-D socket

  • For measuring instrument

2-pin terminal block

2-pin terminal block

2-pin terminal block

  • for power supply and signaling contact

5-pin terminal block

5-pin terminal block

5-pin terminal block

Number of optical connections for fiber-optic cables

1

2

2

Design of optical connection for fiber-optic cables

BFOC port

BFOC port

BFOC port

Optical data

Attenuation factor of the FOC transmission link

  • for glass FOC with 10/125 µm or 9/125 µm at 0.5 dB/km, max.

-

-

-

  • for glass FOC with 50/125 µm at 3 dB/km, max.

-

-

-

  • for glass FOC with 62.5/125 µm

    • at 1 dB/km maximum

-

-

-

    • at 3.5 dB/km maximum

-

-

-

  • for PCF FOC with 200/230 µm at 10 dB/km

-

-

-

  • for POF FOC with 980/1000 µm at 230 dB/km

13 dB

13 dB

13 dB

Signal delay time in bit time

6.5 bit

6.5 bit

6.5 bit

Injectable optical power relative to 1 mW

  • for glass FOC with 10/125 µm or 9/125 µm at 0.5 dB/km

-

-

-

  • for glass FOC with 50/125 µm at 3 dB/km

-

-

-

  • for glass FOC with 62.5/125 µm

    • at 1 dB/km

-

-

-

    • at 3.5 dB/km

-

-

-

  • of the FOC transmission link

    • for PCF FOC with 200/230 µm at 10 dB/km

-17 dB

-

-

    • for POF FOC with 980/1000 µm at 230 dB/km

-5 dB

-

-

optical sensitivity relative to 1 mW

  • for glass FOC with 10/125 µm or 9/125 µm at 0.5 dB/km

-

-

-

  • for glass FOC with 50/125 µm at 3 dB/km

-

-

-

  • for glass FOC with 62.5/125 µm

    • at 1 dB/km

-

-

-

    • at 3.5 dB/km

-

-

-

  • of the FOC transmission link

    • for PCF FOC with 200/230 µm at 10 dB/km

-25 dB

-

-

    • for POF FOC with 980/1000 µm at 230 dB/km

-25 dB

-

-

Wavelength

  • for glass FOC with 10/125 µm or 9/125 µm compatible with interface at 0.5 dB/km

-

-

-

  • for glass FOC with 50/125 µm compatible with interface at 3 dB/km

-

-

-

  • for glass FOC with 62.5/125 µm compatible with interface

    • at 1 dB/km

-

-

-

    • at 3.5 dB/km

-

-

-

  • of the FOC transmission link

    • for PCF FOC with 200/230 µm at 10 dB/km

660 nm

660 nm

660 nm

    • for POF FOC with 980/1000 µm at 230 dB/km

660 nm

660 nm

660 nm

Cable length

  • for glass FOC with 10/125 µm or 9/125 µm at 0.5 dB/km, max.

-

-

-

  • for glass FOC with 50/125 µm at 3 dB/km, max.

-

-

-

  • for glass FOC with 62.5/125 µm

    • at 1 dB/km maximum

-

-

-

    • at 3.5 dB/km maximum

-

-

-

  • for PCF FOC with 200/230 µm at 10 dB/km maximum

400 m

400 m

400 m

  • for POF FOC with 980/1000 µm at 230 dB/km, max.

80 m

80 m

80 m

Inputs/outputs

Operating voltage of signaling contacts with DC rated value

24 V

24 V

24 V

Operating current of signaling contacts with DC maximum

0.1 A

0.1 A

0.1 A

Supply voltage, current consumption, power loss

Type of power supply

DC

DC

DC

DC power supply

  • Rated value

24 V

24 V

24 V

  • Minimum

18.8 V

18.8 V

18.8 V

  • Maximum

28.8 V

28.8 V

28.8 V

Product component: fusing at power supply input

Yes

Yes

Yes

Type of fusing of power supply input

-

-

-

Maximum current consumed at 24 V DC

0.2 A

0.2 A

0.2 A

Effective power loss at 24 V DC

-

-

-

Permitted ambient conditions

Ambient temperature

  • During operation

0 … 60 °C

0 … 60 °C

0 … 60 °C

  • During storage

-40 … +70 °C

-40 … +70 °C

-40 … +70 °C

  • During transport

-40 … +70 °C

-40 … +70 °C

-40 … +70 °C

Relative humidity at 25 °C without condensation during operation, maximum

95 %

95 %

95 %

IP degree of protection

IP40

IP40

IP40

Design, dimensions and weights

Type of construction

Compact

Compact

Compact

Width

39.5 mm

39.5 mm

39.5 mm

Height

112 mm

112 mm

112 mm

Depth

74.5 mm

74.5 mm

74.5 mm

Net weight

340 g

340 g

340 g

Type of mounting

  • 35 mm DIN rail mounting

Yes

Yes

Yes

  • Wall mounting

Yes

Yes

Yes

Product properties, functions, componentsGeneral

Product function: Ring redundancy

Yes

Yes

Yes

Standards, specifications, approvals

Standard

  • for EMC of FM

FM3611: Class 1, Division 2, Group A, B, C, D / T4, Class 1, Zone 2, Group IIC, T4

FM3611: Class 1, Division 2, Group A, B, C, D / T4, Class 1, Zone 2, Group IIC, T4

FM3611: Class 1, Division 2, Group A, B, C, D / T4, Class 1, Zone 2, Group IIC, T4

  • for hazardous zone

EN 60079-0: 2006, EN60079-15: 2005, EN60079-28: 2007, II 3 (2) G Ex nA [opis] IIC T4 KEMA 09 ATEX 0173X

EN 60079-0: 2006, EN60079-15: 2005, EN60079-28: 2007, II 3 (2) G Ex nA [opis] IIC T4 KEMA 09 ATEX 0173X

EN 60079-0: 2006, EN60079-15: 2005, EN60079-28: 2007, II 3 (2) G Ex nA [opis] IIC T4 KEMA 09 ATEX 0173X

  • for CSA and UL safety

UL 60950-1, CSA C22.2 No. 60950-1

UL 60950-1, CSA C22.2 Nr. 60950-1

UL 60950-1, CSA C22.2 No. 60950-1

  • for hazardous zone of CSA and UL

UL 1604 and UL 2279-15 (Hazardous Location), CSA C22.2 No. 213-M1987, Class 1 / Division 2 / Group A, B, C, D / T4, Class 1 / Zone 2 / Group IIC / T4

UL 1604 and UL 2279-15 (Hazardous Location), CSA C22.2 No. 213-M1987, Class 1 / Division 2 / Group A, B, C, D / T4, Class 1 / Zone 2 / Group IIC / T4

UL 1604 and UL 2279-15 (Hazardous Location), CSA C22.2 No. 213-M1987, Class 1 / Division 2 / Group A, B, C, D / T4, Class 1 / Zone 2 / Group IIC / T4

  • For emitted interference

EN 61000-6-4 (Class A)

EN 61000-6-4 (Class A)

EN 61000-6-4 (Class A)

  • For noise immunity

EN 61000-6-2

EN 61000-6-2

EN 61000-6-2

Certificate of suitability

EN 61000-6-2, EN 61000-6-4

EN 61000-6-2, EN 61000-6-4

EN 61000-6-2, EN 61000-6-4

  • CE mark

Yes

Yes

Yes

  • C-Tick

Yes

Yes

Yes

Marine classification society

  • American Bureau of Shipping Europe Ltd. (ABS)

Yes

Yes

Yes

  • Bureau Veritas (BV)

Yes

Yes

Yes

  • Det Norske Veritas (DNV)

Yes

Yes

Yes

  • Germanischer Lloyd (GL)

Yes

Yes

Yes

  • Lloyds Register of Shipping (LRS)

Yes

Yes

Yes

  • Nippon Kaiji Kyokai (NK)

Yes

Yes

Yes


Order No.

6GK1 503-2CB00

6GK1 503-3CB00

6GK1 503-4CB00

Product type designation

PROFIBUS OLM G11

PROFIBUS OLM G12

PROFIBUS OLM G22

Transmission rate

Transmission rate

  • with PROFIBUS

9.6 Kbit/s … 12 Mbit/s

9.6 Kbit/s … 12 Mbit/s

9.6 Kbit/s … 12 Mbit/s

  • with PROFIBUS PA

45.45 Kbit/s

45.45 Kbit/s

45.45 Kbit/s

Interfaces

Maximum number of electrical/optical connections for network components or terminal equipment

2

3

4

Number of electrical connections

  • for network components or terminal equipment

1

1

2

  • for measuring instrument

1 1

1 1

1 1

  • for signaling contact

1

1

1

  • for power supply

1

1

1

  • for redundant power supply

1

1

1

Design of electrical connection

  • for network components or terminal equipment

9-pin sub-D socket

9-pin sub-D socket

9-pin sub-D socket

  • for measuring instrument

2-pin terminal block

2-pin terminal block

2-pin terminal block

  • for power supply and signaling contact

5-pin terminal block

5-pin terminal block

5-pin terminal block

Number of optical connections for fiber-optic cables

1

2

2

Design of optical connection for fiber-optic cables

BFOC port

BFOC port

BFOC port

Optical data

Attenuation factor of the FOC transmission link

  • for glass FOC with 10/125 µm or 9/125 µm at 0.5 dB/km, max.

-

-

-

  • for glass FOC with 50/125 µm at 3 dB/km, max.

10 dB

10 dB

10 dB

  • for glass FOC with 62.5/125 µm

    • at 1 dB/km maximum

-

-

-

    • at 3.5 dB/km maximum

12 dB

12 dB

12 dB

  • for PCF FOC with 200/230 µm at 10 dB/km

-

-

-

  • for POF FOC with 980/1000 µm at 230 dB/km

-

-

-

Signal delay time in bit time

6.5 bit

6.5 bit

6.5 bit

Injectable optical power relative to 1 mW

  • for glass FOC with 10/125 µm or 9/125 µm at 0.5 dB/km

-

-

-

  • for glass FOC with 50/125 µm at 3 dB/km

-16 dB

-16 dB

-16 dB

  • for glass FOC with 62.5/125 µm

    • at 1 dB/km

-

-

-

    • at 3.5 dB/km

-13 dB

-13 dB

-13 dB

  • of the FOC transmission link

    • for PCF FOC with 200/230 µm at 10 dB/km

-

-

-

    • for POF FOC with 980/1000 µm at 230 dB/km

-

-

-

optical sensitivity relative to 1 mW

  • for glass FOC with 10/125 µm or 9/125 µm at 0.5 dB/km

-

-

-

  • for glass FOC with 50/125 µm at 3 dB/km

-28 dB

-28 dB

-28 dB

  • for glass FOC with 62.5/125 µm

    • at 1 dB/km

-

-

-

    • at 3.5 dB/km

-28 dB

-28 dB

-28 dB

  • of the FOC transmission link

    • for PCF FOC with 200/230 µm at 10 dB/km

-

-

-

    • for POF FOC with 980/1000 µm at 230 dB/km

-

-

-

Wavelength

  • for glass FOC with 10/125 µm or 9/125 µm compatible with interface at 0.5 dB/km

-

-

-

  • for glass FOC with 50/125 µm compatible with interface at 3 dB/km

860 nm

860 nm

860 nm

  • for glass FOC with 62.5/125 µm compatible with interface

    • at 1 dB/km

-

-

-

    • at 3.5 dB/km

860 nm

860 nm

860 nm

  • of the FOC transmission link

    • for PCF FOC with 200/230 µm at 10 dB/km

-

-

-

    • for POF FOC with 980/1000 µm at 230 dB/km

-

-

-

Cable length

  • for glass FOC with 10/125 µm or 9/125 µm at 0.5 dB/km, max.

-

-

-

  • for glass FOC with 50/125 µm at 3 dB/km, max.

3 km

3 km

3 km

  • for glass FOC with 62.5/125 µm

    • at 1 dB/km maximum

-

-

-

    • at 3.5 dB/km maximum

3 km

3 km

3 km

  • for PCF FOC with 200/230 µm at 10 dB/km maximum

-

-

-

  • for POF FOC with 980/1000 µm at 230 dB/km, max.

-

-

-

Inputs/outputs

Operating voltage of signaling contacts with DC rated value

24 V

24 V

24 V

Maximum operating current of signal contacts with DC

0.1 A

0.1 A

0.1 A

Supply voltage, current consumption, power loss

Type of power supply

DC

DC

DC

DC power supply

  • Rated value

24 V

24 V

24 V

  • Minimum

18.8 V

18.8 V

18.8 V

  • Maximum

28.8 V

28.8 V

28.8 V

Product component: fusing of power supply input

Yes

Yes

Yes

Type of fusing of power supply input

-

-

-

Maximum current consumed at 24 V DC

0.2 A

0.2 A

0.2 A

Effective power loss at 24 V DC

-

-

-

Permitted ambient conditions

Ambient temperature

  • During operation

0 … 60 °C

0 … 60 °C

0 … 60 °C

  • During storage

-40 … +70 °C

-40 … +70 °C

-40 … +70 °C

  • During transport

-40 … +70 °C

-40 … +70 °C

-40 … +70 °C

Relative humidity at 25 °C without condensation during operation, maximum

95 %

95 %

95 %

IP degree of protection

IP40

IP40

IP40

Design, dimensions and weights

Type of construction

Compact

Compact

Compact

Width

39.5 mm

39.5 mm

39.5 mm

Height

112 mm

112 mm

112 mm

Depth

74.5 mm

74.5 mm

74.5 mm

Net weight

340 g

340 g

340 g

Type of mounting

  • 35 mm DIN rail mounting

Yes

Yes

Yes

  • Wall mounting

Yes

Yes

Yes

Product properties, functions, componentsGeneral

Product function: Ring redundancy

Yes

Yes

Yes

Standards, specifications, approvals

Standard

  • for EMC of FM

FM3611: Class 1, Division 2, Group A, B, C, D / T4, Class 1, Zone 2, Group IIC, T4

FM3611: Class 1, Division 2, Group A, B, C, D / T4, Class 1, Zone 2, Group IIC, T4

FM3611: Class 1, Division 2, Group A, B, C, D / T4, Class 1, Zone 2, Group IIC, T4

  • for hazardous zone

EN 60079-0: 2006, EN60079-15: 2005, EN60079-28: 2007, II 3 (2) G Ex nA [opis] IIC T4 KEMA 09 ATEX 0173X

EN 60079-0: 2006, EN60079-15: 2005, EN60079-28: 2007, II 3 (2) G Ex nA [opis] IIC T4 KEMA 09 ATEX 0173X

EN 60079-0: 2006, EN60079-15: 2005, EN60079-28: 2007, II 3 (2) G Ex nA [opis] IIC T4 KEMA 09 ATEX 0173X

  • for CSA and UL safety

UL 60950-1, CSA C22.2 No. 60950-1

UL 60950-1, CSA C22.2 No. 60950-1

UL 60950-1, CSA C22.2 No. 60950-1

  • for hazardous zone of CSA and UL

UL 1604 and UL 2279-15 (Hazardous Location), CSA C22.2 No. 213-M1987, Class 1 / Division 2 / Group A, B, C, D / T4, Class 1 / Zone 2 / Group IIC / T4

UL 1604 and UL 2279-15 (Hazardous Location), CSA C22.2 No. 213-M1987, Class 1 / Division 2 / Group A, B, C, D / T4, Class 1 / Zone 2 / Group IIC / T4

UL 1604 and UL 2279-15 (Hazardous Location), CSA C22.2 No. 213-M1987, Class 1 / Division 2 / Group A, B, C, D / T4, Class 1 / Zone 2 / Group IIC / T4

  • for emitted interference

EN 61000-6-4 (Class A)

EN 61000-6-4 (Class A)

EN 61000-6-4 (Class A)

  • for noise immunity

EN 61000-6-2

EN 61000-6-2

EN 61000-6-2

Certificate of suitability

EN 61000-6-2, EN 61000-6-4

EN 61000-6-2, EN 61000-6-4

EN 61000-6-2, EN 61000-6-4

  • CE mark

Yes

Yes

Yes

  • C-Tick

Yes

Yes

Yes

Marine classification corporation

  • American Bureau of Shipping Europe Ltd. (ABS)

Yes

Yes

Yes

  • Bureau Veritas (BV)

Yes

Yes

Yes

  • Det Norske Veritas (DNV)

Yes

Yes

Yes

  • Germanischer Lloyd (GL)

Yes

Yes

Yes

  • Lloyds Register of Shipping (LRS)

Yes

Yes

Yes

  • Nippon Kaiji Kyokai (NK)

Yes

Yes

Yes


Order No.

6GK1 503-2CC00

6GK1 503-3CC00

6GK1 503-3CD00

Product type designation

PROFIBUS OLM G11-1300

PROFIBUS OLM G12-1300

PROFIBUS OLM G12 EEC

Transmission rate

Transmission rate

  • with PROFIBUS

9.6 Kbit/s … 12 Mbit/s

9.6 Kbit/s … 12 Mbit/s

9.6 Kbit/s … 12 Mbit/s

  • with PROFIBUS PA

45.45 Kbit/s

45.45 Kbit/s

45.45 Kbit/s

Interfaces

Maximum number of electrical/optical connections for network components or terminal equipment

2

3

3

Number of electrical connections

  • for network components or terminal equipment

1

1

1

  • For measuring instrument

1 1

1 1

1 1

  • For signaling contact

1

1

1

  • for power supply

1

1

1

  • for redundant power supply

1

1

1

Design of electrical connection

  • for network components or terminal equipment

9-pin sub-D socket

9-pin sub-D socket

9-pin sub-D socket

  • For measuring instrument

2-pin terminal block

2-pin terminal block

2-pin terminal block

  • for power supply and signaling contact

5-pin terminal block

5-pin terminal block

5-pin terminal block

Number of optical connections for fiber-optic cables

1

2

2

Design of optical connection for fiber-optic cables

BFOC port

BFOC port

BFOC port

Optical data

Attenuation factor of the FOC transmission link

  • for glass FOC with 10/125 µm or 9/125 µm at 0.5 dB/km, max.

8 dB

8 dB

-

  • for glass FOC with 50/125 µm at 3 dB/km, max.

-

-

10 dB

  • for glass FOC with 62.5/125 µm

    • at 1 dB/km maximum

10 dB

10 dB

-

    • at 3.5 dB/km maximum

-

-

12 dB

  • for PCF FOC with 200/230 µm at 10 dB/km

-

-

-

  • for POF FOC with 980/1000 µm at 230 dB/km

-

-

-

Signal delay time in bit time

6.5 bit

6.5 bit

6.5 bit

Injectable optical power relative to 1 mW

  • for glass FOC with 10/125 µm or 9/125 µm at 0.5 dB/km

-19 dB

-19 dB

-

  • for glass FOC with 50/125 µm at 3 dB/km

-

-

-16 dB

  • for glass FOC with 62.5/125 µm

    • at 1 dB/km

-17 dB

-17 dB

-

    • at 3.5 dB/km

-

-

-13 dB

  • of the FOC transmission link

    • for PCF FOC with 200/230 µm at 10 dB/km

-

-

-

    • for POF FOC with 980/1000 µm at 230 dB/km

-

-

-

optical sensitivity relative to 1 mW

  • for glass FOC with 10/125 µm or 9/125 µm at 0.5 dB/km

-29 dB

-29 dB

-

  • for glass FOC with 50/125 µm at 3 dB/km

-

-

-28 dB

  • for glass FOC with 62.5/125 µm

    • at 1 dB/km

-29 dB

-29 dB

-

    • at 3.5 dB/km

-

-

-28 dB

  • of the FOC transmission link

    • for PCF FOC with 200/230 µm at 10 dB/km

-

-

-

    • for POF FOC with 980/1000 µm at 230 dB/km

-

-

-

Wavelength

  • for glass FOC with 10/125 µm or 9/125 µm at 0.5 dB/km compatible with interface at 0.5 dB/km

1 310 nm

1 310 nm

-

  • for glass FOC with 50/125 µm compatible with interface at 3 dB/km

-

-

860 nm

  • for glass FOC with 62.5/125 µm compatible with interface

    • at 1 dB/km

1 310 nm

1 310 nm

-

    • at 3.5 dB/km

-

-

860 nm

  • of the FOC transmission link

    • for PCF FOC with 200/230 µm at 10 dB/km

-

-

-

    • for POF FOC with 980/1000 µm at 230 dB/km

-

-

-

Cable length

  • for glass FOC with 10/125 µm or 9/125 µm at 0.5 dB/km, max.

15 km

15 km

-

  • for glass FOC with 50/125 µm at 3 dB/km, max.

-

-

3 km

  • for glass FOC with 62.5/125 µm

    • at 1 dB/km maximum

10 km

10 km

-

    • at 3.5 dB/km maximum

-

-

3 km

  • for PCF FOC with 200/230 µm at 10 dB/km maximum

-

-

-

  • for POF FOC with 980/1000 µm at 230 dB/km, max.

-

-

-

Inputs/outputs

Operating voltage of signaling contacts with DC rated value

24 V

24 V

24 V

Maximum operating current of signal contacts with DC

0.1 A

0.1 A

0.1 A

Supply voltage, current consumption, power loss

Type of power supply

DC

DC

DC

Power supply with DC

  • Rated value

24 V

24 V

24 V

  • minimum

18.8 V

18.8 V

18.8 V

  • Maximum

28.8 V

28.8 V

28.8 V

Product component: fusing of power supply input

Yes

Yes

Yes

Type of fusing of power supply input

-

-

-

Maximum current consumed at 24 V DC

0.2 A

0.2 A

0.2 A

Effective power loss at 24 V DC

-

-

-

Permitted ambient conditions

Ambient temperature

  • During operation

0 … 60 °C

0 … 60 °C

-25 … +60 °C

  • During storage

-40 … +70 °C

-40 … +70 °C

-40 … +70 °C

  • During transport

-40 … +70 °C

-40 … +70 °C

-40 … +70 °C

Relative humidity at 25 °C without condensation during operation, maximum

95 %

95 %

95 %

IP degree of protection

IP40

IP40

IP40

Design, dimensions and weights

Type of construction

Compact

Compact

Compact

Width

39.5 mm

39.5 mm

39.5 mm

Height

112 mm

112 mm

112 mm

Depth

74.5 mm

74.5 mm

74.5 mm

Net weight

340 g

340 g

340 g

Type of mounting

  • 35 mm DIN rail mounting

Yes

Yes

Yes

  • Wall mounting

Yes

Yes

Yes

Product properties, functions, components General

Product function: Ring redundancy

Yes

Yes

Yes

Standards, specifications, approvals

Standard

  • for EMC of FM

FM3611: Class 1, Division 2, Group A, B, C, D / T4, Class 1, Zone 2, Group IIC, T4

FM3611: Class 1, Division 2, Group A, B, C, D / T4, Class 1, Zone 2, Group IIC, T4

FM3611: Class 1, Division 2, Group A, B, C, D / T4, Class 1, Zone 2, Group IIC, T4

  • for hazardous zone

EN 60079-0: 2006, EN60079-15: 2005, II 3 G Ex nA II T4 KEMA 07 ATEX 0003X

EN 60079-0: 2006, EN60079-15: 2005, II 3 G Ex nA II T4 KEMA 07 ATEX 0003X

EN 60079-0: 2006, EN60079-15: 2005, EN60079-28: 2007, II 3 (2) G Ex nA [opis] IIC T4 KEMA 09 ATEX 0173X

  • for CSA and UL safety

UL 60950-1, CSA C22.2 No. 60950-1

UL 60950-1, CSA C22.2 No. 60950-1

UL 60950-1, CSA C22.2 No. 60950-1

  • for hazardous zone of CSA and UL

UL 1604 and UL 2279-15 (Hazardous Location), CSA C22.2 No. 213-M1987, Class 1 / Division 2 / Group A, B, C, D / T4, Class 1 / Zone 2 / Group IIC / T4

UL 1604 and UL 2279-15 (Hazardous Location), CSA C22.2 No. 213-M1987, Class 1 / Division 2 / Group A, B, C, D / T4, Class 1 / Zone 2 / Group IIC / T4

UL 1604 and UL 2279-15 (Hazardous Location), CSA C22.2 No. 213-M1987, Class 1 / Division 2 / Group A, B, C, D / T4, Class 1 / Zone 2 / Group IIC / T4

  • For emitted interference

EN 61000-6-4 (Class A)

EN 61000-6-4 (Class A)

EN 61000-6-4 (Class A)

  • For noise immunity

EN 61000-6-2

EN 61000-6-2

EN 61000-6-2

Certificate of suitability

EN 61000-6-2, EN 61000-6-4

EN 61000-6-2, EN 61000-6-4

EN 61000-6-2, EN 61000-6-4

  • CE mark

Yes

Yes

Yes

  • C-Tick

Yes

Yes

Yes

Marine classification society

  • American Bureau of Shipping Europe Ltd. (ABS)

Yes

Yes

Yes

  • Bureau Veritas (BV)

Yes

Yes

Yes

  • Det Norske Veritas (DNV)

Yes

Yes

Yes

  • Germanischer Lloyd (GL)

Yes

Yes

Yes

  • Lloyds Register of Shipping (LRS)

Yes

Yes

Yes

  • Nippon Kaiji Kyokai (NK)

Yes

Yes

Yes
























































Каталог оборудования 2012
Каталог продуктов Siemens Industry Приводная техника Техника автоматизации Системы автоматизации Промышленные системы автоматизации SIMATIC Программируемые контроллеры Распределенный ввод/вывод Станции ET 200 для установки в шкафы управления Станции ET 200 для установки вне шкафов управления Технологические компоненты для PROFIBUS Технологические компоненты PROFINET Сетевые компоненты для PROFIBUS Обзор сетевых компонент Критерии выбора типа сети Примеры соединений Электрические сети (RS485) Электрические сети (PROFIBUS-PA) Оптические сети с OLM Стеклянный волоконно-оптический кабель Пластиковые и PCF волоконно-оптический кабели Набор инструментов для монтажа PCF FOC Модули OLM Оптические сети с ОВТ и встроенными интерфейсами Беспроводные соединения Сетевые переходы Система автоматизации SIMATIC TDC Программное обеспечение для SIMATIC S7/WinAC Программаторы Наборы Micro Automation Sets SIEMENS Solution Partner Motion Control - система SIMOTION Системы автоматизации ЧПУ SINUMERIK Система соединителей/ шкафы управления Программное обеспечение для систем автоматизации Системы визуализации SIMATIC HMI Системы идентификации Промышленные коммуникации SIMATIC NET Промышленные аппараты управления SIRIUS Промышленные информационные технологии Управление на базе РС Системы управления процессом Датчики Блоки питания Продукты для специальных требований Автоматизация зданий Низковольтная коммутационная техника Технология безопасности Системные решения и продукты для отраслей Сервис ... и все, что Вам еще необходимо