Siemens
СРЕДСТВА ПРОМЫШЛЕННОЙ АВТОМАТИЗАЦИИ
официальный партнер Сименс
Каталог СА01 2012
архивный
(4872) 700-366
skenergo@mail.ru

6ES7833-1CC02-0YA5


Внимание! Указаны цены архивного каталога СА01. Для уточнения актуальной цены перейдите по ссылке заказного номера товара или перейдите в каталог СА01 2016

Заказной номерВесPGОписание продуктаЦена
6ES7833-1CC02-0YA50.24241SIMATIC S7. F-PROG-SW U.FB-LIB. FLOAT. LICENSE F.1 INSTALLATION R-SW. SW AND DOCU. ON CD. CLASS A. 2 LANGUAGES (G.E). EXECUTABLE UNDER WINXP SP2/SP3. WIN SERVER 2003 SP2 REFERENCE-HW:SIMATIC S7-400H REFERENCE-HW:SIMATIC S7-400H1210.52

SIPLUS CPU 417H

CPU for SIMATIC S7-400H and S7-400F/FH

  • Usable in high-availability systems such as the S7-400H
  • Usable with F runtime license as F-capable CPU in S7-400F/FH safety-related systems
  • With integral PROFIBUS DP master interface
  • Features 2 slots for sync modules

Note:

SIPLUS extreme products are based on Siemens Industry standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added.

SIPLUS CPU 417H

Order number

6AG1 417-4HT14-4AB0

Order No. based on

6ES7 417-4HT14-0AB0

Ambient temperature range

0 ... +60 °C

Conformal coating

Coating of the printed circuit boards and the electronic components

Technical data

The technical data of the standard product applies except for the environmental conditions

Ambient conditions

Relative humidity

5 ... 100 %
Condensation permissible

Biologically active substances

Conformity with EN 60721 3 3, Class 3B2 mold and fungal spores (except fauna)

Chemically active substances

Conformity with EN 60721 3 3, Class 3C4 incl. salt mist and ISA–S71.04 severity level G1; G2; G3; GX1)2)

Mechanically active substances

Conformity with EN 60721 3 3, Class 3S4 including conductive sand, dust2)

Air pressure (depending on the highest positive temperature range specified)

1080 ... 795 hPa (-1000 ... +2000 m)
see ambient temperature range

795 ... 658 hPa (+2000 ... +3500 m)
derating 10 K

658 ... 540 hPa (+3500 ... +5000 m)
derating 20 K


1) ISA-S71.04 severity level GX: Long-term load: SO2 < 4.8 ppm; H2S < 9.9 ppm; Cl < 0.2 ppm; HCl < 0.66 ppm; HF < 0.12 ppm; NH < 49 ppm; O3 < 0.1 ppm; NOX < 5.2 ppm
Limit value (max. 30 min/d): SO2 < 17.8 ppm; H2S < 49.7 ppm; Cl < 1.0 ppm; HCl < 3.3 ppm; HF < 2.4 ppm; NH < 247 ppm; O3 < 1.0 ppm; NOX < 10.4 ppm

2) The supplied plug covers must remain in place over the unused interface when operated in atmospheres containing corrosive gases!

The technical documentation on SIPLUS can be found here:
http://www.siemens.de/siplus-extreme
























































  © ООО "СК ЭНЕРГО" 2007-2022
  (4872) 700-366
Яндекс.Метрика