The SENTRON PAC3200 is a control panel instrument for measuring and indicating more than 50 electric power distribution variables such as voltage, current, power, electrical work and frequency with their minimum, maximum and mean values. It convinces through its compact design and high performance capacity.
A large, backlit graphic display can be read even from great distances. User-friendly, intuitive operation is made possible by plain text displays in nine languages in combination with four function buttons. Language selection is possible either directly on the device or using configuration software.
SENTRON PAC3200 offers several communication options in addition to one digital input and one digital output. For integration in a higher-level power management system it is possible to use either the integrated Ethernet interface or the optionally available expansion modules.
SENTRON PAC3200 is also available with UL and CSA approval for use in the USA and Canada.
The SENTRON powerconfig software for user-friendly device configuration is included in the scope of supply.
The product variants of the SENTRON PAC 3200
PAC3200 |
Type | |
---|---|---|
With AC/DC power supply unit with wide voltage range and screw terminals
U
AUX: 95 ... 240 V AC ±10 %, 50/60 Hz U e: max. 3 AC 690/400 V, 50/60 Hz |
7KM2112-0BA00-3AA0 | |
With DC power supply unit with extra-low voltage and screw terminals U AUX: 22 ... 65 V ±10 % U e: max. 3 AC 500/289 V, 50/60 Hz |
7KM2111-1BA00-3AA0 | |
With AC/DC power supply unit with wide voltage range and cable lug terminals
U
AUX: 95 ... 240 AC V ±10 %, 50/60 Hz U e: max. 3 AC 690/400 V, 50/60 Hz |
7KM2112-0BA00-2AA0 |
The advantages of the SENTRON PAC3200 at a glance:
- Three-phase control panel measuring device for measuring electrical variables
- Measuring more than 50 variables such as phase voltage and phase-to-phase voltage, current, power, work, power factor, frequency, etc.
- High measuring accuracy for electrical work; Class 0.5S according to IEC62053-22
- Can be used for single-phase measurements as well as for multiphase measurements in 3 and 4-conductor networks
- Can be connected directly to three-phase industrial networks up to 690/400 V or up to max. 500/289 V for devices with DC power supply unit with extra-low voltage (CATIII)
- Measuring higher voltages using a voltage transformer; adjustable transformer ratio
- For x/1A and x/5A current transformers Adjustable transformer ratio and current direction
- 2 device types available with power supply unit with wide voltage range and with extra-low voltage in order to cover all standard AC and DC auxiliary voltage supply needs
- Slot for expansion modules such as the SENTRON PAC PROFIBUS DP or SENTRON PAC RS485 communication modules
- Small space requirement thanks to compact design (96 mm x 96 mm, mounting depth 51 mm or 73 mm with module)
- Large, graphic LCD display with intuitive user operation using function buttons
- Menu selections, test displays and documentation available in nine languages (German, English, Portuguese, Turkish, Spanish, Italian, French, Chinese and Russian)
Language selection on the device or using configuration software - IP65 using standard sealing
- Multifunctional digital input, for example for detecting counting pulses or for monitoring the status of switching devices
- Multifunctional digital output, for example for emitting active or reactive power pulses (S0) or for indicating limit value violations
- Monitoring of up to 6 limit values and connecting the limit values with logical AND / OR operations
- Measuring period averages for active and reactive power with minimum and maximum value
- Operating hours meter for indicating the load running time
- Integrated Ethernet interface (Modbus TCP or SEAbus TCP) for easy and low-cost integration in power management systems
- UL and CSA approval for the USA and Canada
- CD with SENTRON powerconfig software for user-friendly device configuration included in scope of supply
Measurement functions
The SENTRON PAC3200 measures the following variables:
Measured values |
||||||||
---|---|---|---|---|---|---|---|---|
Variable |
Display range |
L1/ |
L2/ |
L3/ |
Total |
Min |
Mean |
Max |
Current |
0 A ………120 kA |
? |
? |
? |
-- |
? |
?1) |
? |
Voltage L-N |
0 V …….. 700 kV |
? |
? |
? |
-- |
? |
?1) |
? |
Voltage L-L |
0 V …..… 1200 kV |
? |
? |
? |
-- |
? |
?1) |
? |
Frequency |
44.00 … 67.00 Hz |
? |
-- |
? |
-- |
? | ||
Active power per phase |
0 W ….. 100 GW |
? |
? |
? |
-- |
? |
-- |
? |
Reactive power per phase |
0 var … 100 Gvar |
? |
? |
? |
-- |
? |
-- |
? |
Apparent power per phase |
0 VA … 100 GVA |
? |
? |
? |
-- |
? |
-- |
? |
Active power total |
0 W … 100 GW |
-- |
-- |
-- |
? |
? |
?2) |
? |
Reactive power total |
0 var … 100 Gvar |
-- |
-- |
-- |
? |
? |
?2) |
? |
Apparent power total |
0 VA … 100 GVA |
-- |
-- |
-- |
? |
? |
-- |
? |
Power factor per phase |
0 …1 |
? |
? |
? |
-- |
? |
-- |
? |
Power factor total |
0 …1 |
-- |
-- |
-- |
? |
? |
-- |
? |
Active work total |
0 Wh … 1000 GWh |
-- |
-- |
-- |
?3) |
-- |
-- |
-- |
Reactive work total |
0 varh … 100 Gvarh |
-- |
-- |
-- |
?3) |
-- |
-- |
-- |
Apparent work total |
0 VAh … 100 GVAh |
-- |
-- |
-- |
?3) |
-- |
-- |
-- |
THD voltage per phase |
0 … 100 % |
? |
? |
? |
-- |
-- |
-- |
? |
THD current per phase |
0 … 100 % |
? |
? |
? |
-- |
-- |
-- |
? |
Voltage asymmetry |
0 … 100 % |
-- |
-- |
-- |
? |
-- |
-- |
-- |
Current asymmetry |
0 … 100 % |
-- |
-- |
-- |
? |
-- |
-- |
-- |
Operating hours |
0 h … 300 years |
-- |
-- |
-- |
? |
-- |
-- |
-- |
Universal counter |
0 … 999,999,999 pulses |
-- |
-- |
-- |
? |
-- |
-- |
-- |
1) The values quoted are mean values of all three phases.
2) Can be called up only through communication. The power averages (power count values), including minimum and maximum values, are transmitted for a selectable measurement period. The measurement period can be selected in the range 1 … 60 min; the default setting is 15 min.
3) The values for high rate and low rate are shown on the display.
? Measuring possible
-- Measuring not possible or not meaningful