Rated voltages | 380 ... 480 V 3 AC ±10 % (-15 % <1 min) 500 ... 690 V 3 AC ±10 % (-15 % <1 min) |
Line supply types | Grounded TN/TT systems and non-grounded IT systems |
Line frequency | 47 ... 63 Hz |
Overvoltage category | III to EN 61800-5-1 |
Electronics power supply | 24 V DC, -15 % +20 % implemented as PELV circuit in accordance with EN 61800-5-1 Ground = negative pole grounded via the electronics |
Rated short-circuit current per IEC, in conjunction with the specified fuses or circuit breakers | |
| 65 kA |
| 84 kA |
| 170 kA |
| 200 kA |
Rated short-circuit current SCCR (Short Circuit Current Rating) according to UL508C (up to 600 V), in conjunction with the specified fuses or circuit breakers | |
| 65 kA |
| 84 kA |
| 170 kA |
| 200 kA |
Control method | Vector/servo control with and without encoder or V/f control |
Fixed speeds | 15 fixed speeds plus 1 minimum speed, parameterizable (in the default setting, 3 fixed setpoints plus 1 minimum speed are selectable using terminal block/PROFIBUS/PROFINET) |
Skippable speed ranges | 4, parameterizable |
Setpoint resolution | 0.001 rpm digital (14 bits + sign) 12 bits analog |
Braking operation | With Active Line Modules and Smart Line Modules, four-quadrant operation as standard (energy recovery). With Basic Line Modules, two-quadrant operation as standard, braking by means of an optional braking chopper, or alternatively by a Motor Module. |
Mechanical specifications |
Degree of protection | IP00 or IP20 depending on type |
Protection class | I acc. to EN 61800?5?1 |
Touch protection | EN 50274/DGUV regulation 3 when used as intended |
Cooling method | Forced air cooling AF according to EN 60146 |
Ambient conditions | Storage 1) | Transport 1) | Operation |
Ambient temperature | -25 ... +55 °C (-13 ... +131 °F) Class 1K4 acc. to EN 60721-3-1 | -25 ... +70 °C (-13 ... +158 °F) Class 2K4 acc. to EN 60721-3-2 | Line-side components, Power Modules, Line Modules and Motor Modules: 0 … 40 °C (32 ... 104 °F)without derating Up to 55 °C (131 °F), see derating data Control Units, supplementary system components, and Sensor Modules: 0 ... 55 °C (32 ... 131 °F) (for operation in control cabinet) DC link components and motor-side components: 0 ... 55 °C (32 ... 131 °F) |
Relative humidity Condensation, splashwater, and ice formation not permitted (EN 60204, Part 1) | 5 ... 95 % Class 1K4 acc. to EN 60721?3?1 | 5 ... 95 % at 40 °C Class 2K3 acc. to EN 60721?3?2 | 5 ... 95 % Class 3K3 acc. to EN 60721?3?3 |
Environmental class/harmful chemical substances | Class 1C2 acc. to EN 60721?3?1 | Class 2C2 acc. to EN 60721?3?2 | Class 3C2 acc. to EN 60721?3?3 |
Organic/biological influences | Class 1B1 acc. to EN 60721?3?1 | Class 2B1 acc. to EN 60721?3?2 | Class 3B1 acc. to EN 60721?3?3 |
Degree of pollution | 2 acc. to EN 61800?5?1 |
Installation altitude | Up to 2000 m (6562 ft) above sea level without derating >2000 m (6562 ft) above sea level, see derating data |
Mechanical stability | Storage 1) | Transport 1) | Operation |
Vibratory load | – | Class 2M2 acc. to EN 60721?3?2 | Test values acc. to EN 60068?2?6 test Fc: - 10 ... 58 Hz with constant deflection 0.075 mm
- 58 ... 150 Hz with constant acceleration 9.81 m/s2 (1 ? g)
|
Shock load | – | Class 2M2 acc. to EN 60721?3?2 | Test values according to EN 60068?2?27 test Ea: 98 m/s2 (10 ? g)/20 ms |
Compliance with standards |
Conformances/ approvals, according to | CE (EMC Directive No. 2014/30/EU, Low Voltage Directive No. 2014/35/EU and Machinery Directive 2006/42/EC for functional safety) RCM cULus (only for devices connected to line supply voltages 380 ... 480 V 3 AC and 500 ... 600 V 3 AC) |
Electromagnetic compatibility | Built-in units SINAMICS S120 chassis format can be operated in the second environment, Category C3/C2 according to EMC product standard EN 61800?3. For further information, see section Tools and configuring. |