General information | |
Product type designation | SB 1223 DI2x24 VDC, DQ 2x24 VDC |
Input current | |
from backplane bus 5 V DC, typ. | 50 mA |
Output voltage | |
Power supply to the transmitters | |
| 4 mA; per channel |
Power loss | |
Power loss, typ. | 1 W |
Digital inputs | |
Number of digital inputs | 2; Current-sinking |
| 1 |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes |
Number of simultaneously controllable inputs | |
all mounting positions | |
| 2 |
Input voltage | |
| DC |
| 24 V |
| 0 to 5 V |
| +15 to +30V |
Input current | |
| 1 mA |
| 0.5 A |
Input delay (for rated value of input voltage) | |
for standard inputs | |
| Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four |
| 2 µs |
| 10 µs |
for interrupt inputs | |
| Yes |
for counter/technological functions | |
| Yes |
Cable length | |
| 500 m |
| 300 m |
Digital outputs | |
Number of digital outputs | 2; MOSFET, solid-state (current-sinking/current-sourcing) |
| 1 |
Short-circuit protection | No |
Switching capacity of the outputs | |
| 0.5 A |
| 5 W |
Load resistance range | |
| 0.6 ? |
Output voltage | |
| 24 V |
| 0.1 V; with 10 kOhm load |
| 20 V |
Output current | |
| 0.5 A |
| 10 µA |
Cable length | |
| 500 m |
| 150 m |
Interrupts/diagnostics/status information | |
Alarms | Yes |
Diagnostic functions | Yes |
Diagnostics indication LED | |
| Yes |
| Yes |
Isolation | |
Isolation tested with | According to EN 50155 (routine test) |
Degree and class of protection | |
Degree of protection acc. to EN 60529 | |
| Yes |
Standards, approvals, certificates | |
Railway application | |
| Yes; EMC for rail vehicles |
| Yes; EMC for signal and telecommunications systems |
| Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC |
| Yes; Rail vehicles - see ambient conditions |
| Yes; Stationary electrical equipment - see ambient conditions |
| Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) |
| Yes; Rail vehicles - temperature class T1, horizontal mounting position, salt spray Class ST2 |
| Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B |
| Yes; Rail vehicles - verification on request |
Ambient conditions | |
Free fall | |
| 0.3 m; five times, in product package |
Ambient temperature during operation | |
| -25 °C; = Tmin; Startup @ -25 °C |
| 55 °C; = Tmax; +70 °C for 10 minutes (T1 acc. to EN 50155) for horizontal mounting position |
Extended ambient conditions | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) |
Relative humidity | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 5B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation! |
| Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation! |
Mechanics/material | |
Enclosure material (front) | |
| Yes |
Dimensions | |
Width | 38 mm |
Height | 62 mm |
Depth | 21 mm |
Weights | |
Weight, approx. | 40 g |
Other | |
Note: | For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776 |