General information | | | | | |
Product type designation | SIPLUS HMI KP400 Comfort | SIPLUS HMI KP700 Comfort | SIPLUS HMI KP900 Comfort | SIPLUS HMI KP1200 Comfort | SIPLUS HMI KP1500 Comfort |
Display | | | | | |
Design of display | TFT | TFT | TFT | TFT | TFT |
Screen diagonal | 4.3 in | 7 in | 9 in | 12.1 in | 15.4 in |
Number of colors | 16 777 216 | 16 777 216 | 16 777 216 | 16 777 216 | 16 777 216 |
Resolution (pixels) | | | | | |
| 480 Pixel | 800 Pixel | 800 Pixel | 1 280 Pixel | 1 280 Pixel |
| 272 Pixel | 480 Pixel | 480 Pixel | 800 Pixel | 800 Pixel |
Backlighting | | | | | |
| 80 000 h | 80 000 h | 80 000 h | 80 000 h | 80 000 h |
| Yes; 0-100 % | Yes; 0-100 % | Yes; 0-100 % | Yes; 0-100 % | Yes; 0-100 % |
Control elements | | | | | |
Keyboard fonts | | | | | |
| | | | | |
| 8 | 24 | 26 | 34 | 36 |
Touch operation | | | | | |
| No | No | No | No | No |
Installation type/mounting | | | | | |
Mounting in portrait format possible | No | No | No | No | No |
Supply voltage | | | | | |
Type of supply voltage | DC | DC | DC | DC | DC |
Rated value (DC) | 24 V | 24 V | 24 V | 24 V | 24 V |
Memory | | | | | |
Memory available for user data | 4 Mbyte | 12 Mbyte | 12 Mbyte | 12 Mbyte | 24 Mbyte |
Type of output | | | | | |
Acoustics | | | | | |
| No | Yes | Yes | Yes | Yes |
Time of day | | | | | |
Clock | | | | | |
| Yes | Yes | Yes | Yes | Yes |
| Yes; Back-up duration typically 6 weeks | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
Interfaces | | | | | |
Number of industrial Ethernet interfaces | 1 | 2 | 2 | 2 | 3 |
Number of RS 485 interfaces | 1; RS 422/485 combined | 1; RS 422/485 combined | 1; RS 422/485 combined | 1; RS 422/485 combined | 1; RS 422/485 combined |
Number of USB interfaces | 1; USB 2.0 | 2; USB 2.0 | 2; USB 2.0 | 2; USB 2.0 | 2; USB 2.0 |
| 1; 5-pole | 1; 5-pole | 1; 5-pole | 1; 5-pole | 1; 5-pole |
Number of SD card slots | 2 | 2 | 2 | 2 | 2 |
Industrial Ethernet | | | | | |
| 1 | 2 | 2 | 2 | 2 |
Protocols | | | | | |
PROFINET | Yes | Yes | Yes | Yes | Yes |
IRT | No | Yes; With WinCC, subsequent version | Yes; With WinCC, subsequent version | Yes; With WinCC, subsequent version | Yes; With WinCC, subsequent version |
MRP | No | Yes; With WinCC, subsequent version | Yes; With WinCC, subsequent version | Yes; With WinCC, subsequent version | Yes; With WinCC, subsequent version |
PROFIBUS | Yes | Yes | Yes | Yes | Yes |
MPI | Yes | Yes | Yes | Yes | Yes |
Degree and class of protection | | | | | |
IP (at the front) | IP65 | IP65 | IP65 | IP65 | IP65 |
Enclosure Type 4x at the front | Yes | Yes | Yes | Yes | Yes |
IP (rear) | IP20 | IP20 | IP20 | IP20 | IP20 |
Standards, approvals, certificates | | | | | |
CE mark | Yes | Yes | Yes | Yes | Yes |
cULus | Yes | Yes | No | Yes | No |
Marine approval | | | | | |
| No | No | No | No | No |
| No | No | No | No | No |
| No | No | No | No | No |
| No | No | No | No | No |
| No | No | No | No | No |
| No | No | No | No | No |
| No | No | No | No | No |
Use in hazardous areas | | | | | |
| Yes | No | No | No | No |
| Yes | No | No | No | No |
| Yes | No | No | No | No |
| No | No | No | No | No |
Ambient conditions | | | | | |
Suited for indoor use | Yes | Yes | Yes | Yes | Yes |
Suited for outdoor use | No | No | No | No | No |
Ambient temperature during operation | | | | | |
| | | | | |
| 0 °C; = Tmin | 0 °C; = Tmin | 0 °C; = Tmin | 0 °C; = Tmin | 0 °C; = Tmin |
| 50 °C; = Tmax | 50 °C; = Tmax | 50 °C; = Tmax | 50 °C; = Tmax | 50 °C; = Tmax |
Extended ambient conditions | | | | | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | | | | | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | | | | | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Configuration | | | | | |
Configuration software | | | | | |
| Yes; from V11 | Yes; from V11 | Yes; from V11 | Yes; from V11 | Yes; V11 SP2 or higher |
Languages | | | | | |
Online languages | | | | | |
| 32 | 32 | 32 | 32 | 32 |
Functionality under WinCC (TIA Portal) | | | | | |
Applications/options | | | | | |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
Number of Visual Basic Scripts | Yes | Yes | Yes | Yes | Yes |
Task planner | | | | | |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
Message system | | | | | |
| | | | | |
| 2 000 | 4 000 | 4 000 | 4 000 | 6 000 |
| | | | | |
| 50 | 200 | 200 | 200 | 200 |
| | | | | |
| 256 | 1 024 | 1 024 | 1 024 | 1 024 |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
Recipe management | | | | | |
| 100 | 300 | 300 | 300 | 500 |
| 512 kbyte | 2 Mbyte | 2 Mbyte | 2 Mbyte | 4 Mbyte |
| Yes | Yes | Yes | Yes | Yes |
Variables | | | | | |
| 1 024 | 2 048 | 2 048 | 2 048 | 4 096 |
| 50 | 400 | 400 | 400 | 400 |
Images | | | | | |
| 500 | 500 | 500 | 500 | 750 |
Archiving | | | | | |
| 10 | 50 | 50 | 50 | 50 |
Security | | | | | |
| 50 | 50 | 50 | 50 | 50 |
| 50 | 50 | 50 | 50 | 50 |
| Yes | Yes | Yes | Yes | Yes |
Logging through printer | | | | | |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
| Yes; pdf, html | Yes; pdf, html | Yes; pdf, html | Yes; pdf, html | Yes; pdf, html |
Transfer (upload/download) | | | | | |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
Process coupling | | | | | |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
| No; With WinCC, subsequent version | No; With WinCC, subsequent version | No; With WinCC, subsequent version | No; With WinCC, subsequent version | No; With WinCC, subsequent version |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
| No | No | No | No | No |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
| Yes | | | | |
| Yes | | | | |
Peripherals/Options | | | | | |
Peripherals | | | | | |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
Mechanics/material | | | | | |
Enclosure material (front) | | | | | |
| Yes | No | No | No | No |
| No | Yes | Yes | Yes | Yes |
Dimensions | | | | | |
Width of the housing front | 152 mm | 308 mm | 362 mm | 454 mm | 483 mm |
Height of housing front | 188 mm | 204 mm | 230 mm | 289 mm | 310 mm |
Mounting cutout, width | 135 mm | 281 mm | 338 mm | 434 mm | 450 mm |
Mounting cutout, height | 171 mm | 177 mm | 206 mm | 269 mm | 291 mm |
Overall depth | 49 mm | 63 mm | 63 mm | 65 mm | 75 mm |
Weights | | | | | |
Weight without packaging | 0.8 kg | 2.2 kg | 2.7 kg | 4.4 kg | 5.4 kg |