Mode of Operation | |
Measuring principle | Ultrasonic level measurement |
Input | |
Measuring range | 0.25 ... 5 m (0.8 ... 16.4 ft) |
Frequency | 54 kHz |
Output | |
mA | 4 ... 20 mA |
| Proportional/ inversely proportional |
| 600 ? in the loop at 24 V DC |
Power supply | |
Supply voltage | 12 ... 30 V DC, 0.1 A surge |
Max. power consumption | 0.75 W (25 mA at 24 V DC) |
Certificates and approvals | CE, CSAUS/C |
Accuracy | |
Error in measurement | 0.25 % of measuring range (in air) |
Resolution | 3 mm (0.125 inch) |
Temperature compensation | Built in |
Echo processing | Sonic Intelligence |
Rated operation conditions | |
Beam angle | 12° |
Ambient temperature | |
| -30 ... +60 °C (-22 ... +140 °F) |
| -20 ... +60 °C (-4 ... +140 °F) |
Max. static operating pressure | Normal atmospheric pressure |
Design | |
Weight | 1.3 kg (2.9 lb) |
Material | |
| PBT |
| PVDF copolymer |
Degree of protection | IP68 / NEMA 6 / TYPE 6 |
Process connection | - 2" NPT [(Taper), ANSI/ASME B1.20.1]
- R 2" [(BSPT), EN 10226]
- G 2" [(BSPP), EN ISO 228-1]
- 4" sanitary
|
Flange adapter | 3" Universal, (fits DN 65, PN 10 and 3" ASME) |
Cable inlet | 1 inlet for M20, optional 1/2" NPT |