Installation type/mounting | |
Design | Panel PC, built-in unit |
maximum permissible installation angle +/- | 45° |
Supply voltage | |
Type of supply voltage | 24 V DC |
Mains buffering | |
| 20 ms |
Processor | |
Processor type | Intel Celeron N2807 / N2930 |
Drives | |
SSD | Yes; ? 80 GB optional |
Memory | |
Type of memory | DDR3L |
Main memory | 2 / 4 / 8 GB |
Data areas and their retentivity | |
Retentive data area (incl. timers, counters, flags), max. | 512 kbyte; 128 KB can be stored in the buffer time; optional |
Interfaces | |
USB port | 1x USB 3.0 / 3x USB 2.0 (7"/9": 2x USB 2.0) |
Connection for keyboard/mouse | USB / USB |
serial interface | 1x COM (1x RS 232 / 422 / 485), selectable in the BIOS |
Video interfaces | |
| 1x DisplayPort |
Industrial Ethernet | |
| Onboard, 2x 10 / 100 / 1000 Mbit, RJ45 |
| Yes |
| Yes |
Integrated Functions | |
Monitoring functions | |
| Yes |
| Yes |
| No |
| No |
| Optional |
EMC | |
Interference immunity against discharge of static electricity | |
| ±6 kV contact discharge acc. to IEC 61000-4-2; ±8 kV air discharge acc. to IEC 61000-4-2 |
Interference immunity against high-frequency electromagnetic fields | |
| 10 V/m, 80 MHz to 2 GHz, 80 % AM acc. to IEC 61000-4-3; 3 V/m, 2 GHz to 2.7 GHz, 80 % AM acc. to IEC 61000-4-3; 10 V, 10 kHz to 80 MHz, 80 % AM acc. to IEC 61000-4-6 |
Interference immunity to cable-borne interference | |
| ±2 kV acc. to IEC 61000-4-4, burst; ±1 kV acc. to IEC 61000-4-5, surge symmetric; ±2 kV acc. to IEC 61000-4-5, surge asymmetric |
| ±2 kV acc. to IEC 61000-4-5, surge, length > 30 m |
| ±1 kV acc. to IEC 61000-4-4; burst; length < 3 m; ±2 kV acc. to IEC 61000-4-4; burst; length > 3 m |
Interference immunity against voltage surge | |
| ±2 kV acc. to IEC 61000-4-5, surge asymmetric |
| ±1 kV acc. to IEC 61000-4-5, surge symmetric |
Interference immunity to magnetic fields | |
| 100 A/m; to IEC 61000-4-8 |
Emission of conducted and non-conducted interference | |
| Noise emission: EN 61000-6-4:2007 +A1:2011 (industrial environments), CISPR 22 Class B, FCC Class A |
Degree and class of protection | |
IP (at the front) | IP65 |
IP (rear) | IP20 |
Standards, approvals, certificates | |
CE mark | Yes |
UL approval | Yes |
| Yes |
cULus | Yes |
RCM (formerly C-TICK) | Yes |
KC approval | Yes |
FCC | Yes |
EMC | CE, EN 61000-6-4:2007 +A1:2011, EN 61000-6-2:2005 |
| Yes |
Marine approval | |
| Yes; 7", 9", 12" |
| Yes; 7", 9", 12" |
| Yes; 7", 9", 12" |
Ambient conditions | |
Ambient temperature during operation | |
| 0 °C to 50 °C |
| 0 °C |
| 50 °C; 19": max. 45 °C |
Relative humidity | |
| Tested according to IEC 60068-2-78, IEC 60068-2-30: Operation: 5 % to 85 % at 30 °C (no condensation), storage / transport: 5 % to 95 % at 25 / 55 °C (no condensation) |
Vibrations | |
| Tested according to IEC 60068-2-6: 5 Hz to 8.4 Hz: 3.5 mm, 8.4 Hz to 500 Hz: 9.8 m/s? |
Shock testing | |
| Tested according to IEC 60068-2-27: 50 m/s?, 30 ms |
Operating systems | |
pre-installed operating system | Yes |
without operating system | Yes |
pre-installed operating system | |
| Yes; Ultimate 32 bits or 64 bits |
Software | |
SIMATIC Software | Optional package with SIMATIC WinCC or WinAC RTX |