Input | | | | |
Input | 3-phase AC | 3-phase AC | 3-phase AC | 3-phase AC |
Rated voltage value Vin rated | 400 ... 500 V | 400 ... 500 V | 400 ... 500 V | 400 ... 500 V |
Voltage range AC | 320 ... 575 V | 320 ... 575 V | 320 ... 575 V | 320 ... 575 V |
| Derating 320 … 360 and 530 … 575 V | Derating 320 … 360 and 530 … 575 V | Derating 320 … 360 and 530 … 575 V | Derating 320 … 360 and 530 … 575 V |
Wide-range input | Yes | Yes | Yes | Yes |
Mains buffering at Iout rated, min. | 15 ms; at Vin = 400 V; Prioritized voltage supply to the outputs at power failure via DIP switch can be selected (only with expansion module CNX8600) | 15 ms; at Vin = 400 V; Prioritized voltage supply to the outputs at power failure via DIP switch can be selected (only with expansion module CNX8600) | 15 ms; at Vin = 400 V; Prioritized supply Output 1 at power failure can be selected via DIP switch | 15 ms; at Vin = 400 V; Prioritized supply Output 1 at power failure can be selected via DIP switch |
Rated line frequency 1 | 50 Hz | 50 Hz | 50 Hz | 50 Hz |
Rated line frequency 2 | 60 Hz | 60 Hz | 60 Hz | 60 Hz |
Rated line range | 47 ... 63 Hz | 47 ... 63 Hz | 47 ... 63 Hz | 47 ... 63 Hz |
Input current | | | | |
| 1.4 A | 2.75 A | 1.4 A | 2.75 A |
| 1.1 A | 2.2 A | 1.1 A | 2.2 A |
Switch-on current limiting (+25 °C), max. | 14 A | 14 A | 14 A | 14 A |
I?t, max. | 1.2 A?·s | 2.24 A?·s | 1.2 A?·s | 2.24 A?·s |
Built-in incoming fuse | none | none | none | none |
Protection in the mains power input (IEC 898) | Required: 3-pole connected miniature circuit breaker 6 ... 16 A characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) | Required: 3-pole connected miniature circuit breaker 10 ... 16 A characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) | Required: 3-pole connected miniature circuit breaker 6 ... 16 A characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) | Required: 3-pole connected miniature circuit breaker 10 ... 16 A characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) |
Output | | | | |
Output | Controlled, isolated DC voltage | Controlled, isolated DC voltage | Controlled, isolated DC voltage | Controlled, isolated DC voltage |
Number of outputs | 1 | 1 | 4 | 4 |
Rated voltage Vout DC | 24 V | 24 V | 24 V | 24 V |
Output voltage | | | | |
| 24 V | 24 V | 24 V | 24 V |
| | | 24 V | 24 V |
| | | 24 V | 24 V |
| | | 24 V | 24 V |
Total tolerance, static ± | 3 % | 3 % | 3 % | 3 % |
Static mains compensation, approx. | 0.2 % | 0.2 % | 0.2 % | 0.2 % |
Static load balancing, approx. | 0.1 % | 0.1 % | 0.1 % | 0.1 % |
Residual ripple peak-peak, max. | 100 mV | 100 mV | 100 mV | 100 mV |
Spikes peak-peak, max. (bandwidth: 20 MHz) | 200 mV | 200 mV | 200 mV | 200 mV |
Adjustment range | 4 ... 28 V | 4 ... 28 V | 4 ... 28 V | 4 ... 28 V |
Product function Output voltage adjustable | Yes | Yes | Yes | Yes |
Output voltage setting | via potentiometer; Derating > 24 V: 4%/V; max. 480 W overall system | via potentiometer; Derating > 24 V: 4%/V; max. 960 W overall system | via potentiometer; Derating > 24 V: 4%/V; max. 120 W per output, max. 480 W overall system | via potentiometer; Derating > 24 V: 4%/V; max. 240 W per output, max. 960 W overall system |
Status display | 3-color LED for operating state device; LED for operating mode manual/remote; 4 LEDs for communication PROFINET; 3-color LED for operating state output | 3-color LED for operating state device; LED for operating mode manual/remote; 4 LEDs for communication PROFINET; 3-color LED for operating state output | 3-color LED for operating state device; LED for operating mode manual/remote; 4 LEDs for communication PROFINET; 3-color LED per output for operating state output; LED green for parallel operation Output 1 and 2 / 3 and 4 | 3-color LED for operating state device; LED for operating mode manual/remote; 4 LEDs for communication PROFINET; 3-color LED per output for operating state output; LED green for parallel operation Output 1 and 2 / 3 and 4 |
Signaling | Relay contact (changeover contact, contact current capacity DC 60 V/0.3 A) for "Operating state OK" | Relay contact (changeover contact, contact current capacity DC 60 V/0.3 A) for "Operating state OK" | Relay contact (changeover contact, contact current capacity DC 60 V/0.3 A) for "Operating state OK" | Relay contact (changeover contact, contact current capacity DC 60 V/0.3 A) for "Operating state OK" |
On/off behavior | No overshoot of Vout (soft start) | No overshoot of Vout (soft start) | No overshoot of Vout (soft start) | No overshoot of Vout (soft start) |
Startup delay, max. | 1 s | 1 s | 1 s; Without on-delay of the outputs | 1 s; Without on-delay of the outputs |
connection of outputs operating | Simultaneous connecting-in of all outputs after device booting or delay time of 25 ms, 100 ms or "load-optimized" for sequential cutting-in of the outputs via DIP switches can be set (only with expansion module CNX8600) | Simultaneous connecting-in of all outputs after device booting or delay time of 25 ms, 100 ms or "load-optimized" for sequential cutting-in of the outputs via DIP switches can be set (only with expansion module CNX8600) | Simultaneous connecting-in of all outputs after device booting or delay time of 25 ms, 100 ms or "load-optimized" for sequential cutting-in of the outputs via DIP switches can be set | Simultaneous connecting-in of all outputs after device booting or delay time of 25 ms, 100 ms or "load-optimized" for sequential cutting-in of the outputs via DIP switches can be set |
Voltage increase time of the output voltage maximum | 500 ms | 500 ms | 500 ms | 500 ms |
Rated current value Iout rated | 20 A | 40 A | 20 A | 40 A |
Output current | | | | |
| 20 A | 40 A | 5 A | 10 A |
| 20 A | 40 A | 5 A | 10 A |
| | | 5 A | 10 A |
| | | 5 A | 10 A |
| | | 5 A | 10 A |
Current range | 0 ... 20 A | 0 ... 40 A | 0 ... 20 A | 0 ... 40 A |
| +50 ... +60 °C: Derating 2.5%/K; no derating in connection with expansion module CNX8600 and total load of the outputs at the basic device max. 240 W | +50 ... +60 °C: Derating 2.5%/K; no derating in connection with expansion module CNX8600 and total load of the outputs at the basic device max. 480 W | +50 ... +60 °C: Derating 2.5%/K; no derating in connection with expansion module CNX8600 and total load of the outputs at the basic device max. 240 W | +50 ... +60 °C: Derating 2.5%/K; no derating in connection with expansion module CNX8600 and total load of the outputs at the basic device max. 480 W |
Supplied active power typical | 480 W | 960 W | 480 W | 960 W |
Short-term overload current | | | | |
| 60 A | 120 A | | |
| only in operation without CNX8600 extension module | only in operation without CNX8600 extension module | | |
Duration of overloading capability for excess current | | | | |
| 25 ms | 25 ms | | |
Product feature parallel switching of outputs | | | Yes; Parallel circuit Output 1 with 2 or Output 3 with 4 can be selected via DIP switch | Yes; Parallel circuit Output 1 with 2 or Output 3 with 4 can be selected via DIP switch |
Parallel switching for enhanced performance | Yes; suitable output characteristics via DIP switch can be selected | Yes; suitable output characteristics via DIP switch can be selected | No | No |
Numbers of parallel switchable units for enhanced performance | 2 | 2 | | |
Efficiency | | | | |
Efficiency at Vout rated, Iout rated, approx. | 93 % | 93 % | 93 % | 93 % |
Power loss at Vout rated, Iout rated, approx. | 34 W | 72 W | 34 W | 72 W |
Power loss [W] during no-load operation maximum | 12 W | 20 W | 12 W | 20 W |
Closed-loop control | | | | |
Dynamic mains compensation (Vin rated ±15 %), max. | 0.1 % | 0.1 % | 0.1 % | 0.1 % |
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. | 0.4 % | 0.4 % | 0.4 % | 0.4 % |
Setting time maximum | 10 ms | 10 ms | 10 ms | 10 ms |
Protection and monitoring | | | | |
Output overvoltage protection | < 35 V | < 35 V | < 35 V | < 35 V |
Property of the output Short-circuit proof | Yes | Yes | Yes | Yes |
Short-circuit protection | Electronic overload shutdown; optional constant-current operation can be selected via DIP switch | Electronic overload shutdown; optional constant-current operation can be selected via DIP switch | electronic overload cut-off; optionally constant current operation can be selected for Output 4 via DIP switches | electronic overload cut-off; optionally constant current operation can be selected for Output 4 via DIP switches |
adjustable response value current of current-dependent overload trip | 2 ... 20 A | 4 ... 40 A | 0.5 ... 5 A | 0.5 ... 10 A |
type of threshold value setting | via potentiometer | via potentiometer | via potentiometer | via potentiometer |
characteristics of electronic overload switch-off | Ia >1.0…<1.5 x Ia threshold permissible for 5 s; Ia limit (= 1.5 x Ia threshold) permissible for 200 ms | Ia >1.0…<1.5 x Ia threshold permissible for 5 s; Ia limit (= 1.5 x Ia threshold) permissible for 200 ms | Ia >1.0…<1.5 x Ia threshold permissible for 5 s; Ia limit (= 1.5 x Ia threshold) permissible for 200 ms | Ia >1.0…<1.5 x Ia threshold permissible for 5 s; Ia limit (= 1.5 x Ia threshold) permissible for 200 ms |
characteristics of constant current operation | Ia limit (= 1.5 x Ia threshold) permissible for 5 s, afterwards Ia threshold continuous | Ia limit (= 1.5 x Ia threshold) permissible for 5 s, afterwards Ia threshold continuous | Ia limit (= 1.5 x Ia threshold) permissible for 5 s, afterwards Ia threshold continuous | Ia limit (= 1.5 x Ia threshold) permissible for 5 s, afterwards Ia threshold continuous |
Reset | Via sensor | Via sensor | Via sensor per output | Via sensor per output |
Remote reset | Non-electrically isolated 24 V input (signal level "high" at > 15 V) | Non-electrically isolated 24 V input (signal level "high" at > 15 V) | Non-electrically isolated 24 V input (signal level "high" at > 15 V) | Non-electrically isolated 24 V input (signal level "high" at > 15 V) |
Overcurrent overload capability in normal operation | Total system overloadable 150% Ia rated to 5 s/min | Total system overloadable 150% Ia rated to 5 s/min | Total system overloadable 150% Ia rated to 5 s/min | Total system overloadable 150% Ia rated to 5 s/min |
Overload/short-circuit indicator | 3-color LED for operating state device; 3-color LED for operating state output | 3-color LED for operating state device; 3-color LED for operating state output | 3-color LED for operating state device; 3-color LED per output for operating state output | 3-color LED for operating state device; 3-color LED per output for operating state output |
Interface | | | | |
Specification interface | Ethernet/PROFINET | Ethernet/PROFINET | Ethernet/PROFINET | Ethernet/PROFINET |
Safety | | | | |
Primary/secondary isolation | Yes | Yes | Yes | Yes |
Galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
Protection class | Class I | Class I | Class I | Class I |
Leakage current | | | | |
| 3.5 mA | 3.5 mA | 3.5 mA | 3.5 mA |
CE mark | Yes | Yes | Yes | Yes |
UL/cUL (CSA) approval | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) |
Explosion protection | IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T4 | IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T4 | IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T4 | IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T4 |
FM approval | - | - | - | - |
CB approval | Yes | Yes | Yes | Yes |
Marine approval | GL, ABS | GL, ABS | GL, ABS | GL, ABS |
Degree of protection (EN 60529) | IP20 | IP20 | IP20 | IP20 |
EMC | | | | |
Emitted interference | EN 55022 Class B | EN 55022 Class B | EN 55022 Class B | EN 55022 Class B |
Supply harmonics limitation | EN 61000-3-2 | EN 61000-3-2 | EN 61000-3-2 | EN 61000-3-2 |
Noise immunity | EN 61000-6-2 | EN 61000-6-2 | EN 61000-6-2 | EN 61000-6-2 |
Operating data | | | | |
Ambient temperature | | | | |
| -25 ... +60 °C | -25 ... +60 °C | -25 ... +60 °C | -25 ... +60 °C |
| with natural convection | with natural convection | with natural convection | with natural convection |
| -40 ... +85 °C | -40 ... +85 °C | -40 ... +85 °C | -40 ... +85 °C |
| -40 ... +85 °C | -40 ... +85 °C | -40 ... +85 °C | -40 ... +85 °C |
Mechanics | | | | |
Connection technology | Plug-in terminals with screwed connection | Plug-in terminals with screwed connection | Plug-in terminals with screwed connection | Plug-in terminals with screwed connection |
Connections | | | | |
| L1, L2, L3, PE: Plug-in terminal with 1 screwed connection each for 0.08 ... 4 mm? single-wire / fine stranded | L1, L2, L3, PE: Plug-in terminal with 1 screwed connection each for 0.08 ... 4 mm? single-wire / fine stranded | L1, L2, L3, PE: Plug-in terminal with 1 screwed connection each for 0.08 ... 4 mm? single-wire / fine stranded | L1, L2, L3, PE: Plug-in terminal with 1 screwed connection each for 0.08 ... 4 mm? single-wire / fine stranded |
| Output: plug-in terminals with 2 screw connectors for 0.08 ... 4 mm?; 0 V: screw terminal with 3 screw connectors for 0.08 ... 4 mm? | Output: plug-in terminals with 2 screw connectors for 0.2 ... 10 mm?; 0 V: screw terminal with 3 screw connectors for 0.2 ... 10 mm? | 1, 2, 3, 4: Two plug-in terminals (1, 2 and 3, 4) with 2 screwed connections each for 0.2 ... 2.5 mm?; 0 V: Plug-in terminal with 3 screwed connections for 0.08 ... 4 mm? | 1, 2, 3, 4: Two plug-in terminals (1, 2 and 3, 4) with 2 screwed connections each for 0.2 ... 2.5 mm?; 0 V: Plug-in terminal with 3 screwed connections for 0.5 ... 10 mm? |
| RST (Reset): Plug-in terminal (together with alarm signal) with 1 screwed connection for 0.2 ... 1.5 mm? | RST (Reset): Plug-in terminal (together with alarm signal) with 1 screwed connection for 0.2 ... 1.5 mm? | RST (Reset): Plug-in terminal (together with alarm signal) with 1 screwed connection for 0.2 ... 1.5 mm? | RST (Reset): Plug-in terminal (together with alarm signal) with 1 screwed connection for 0.2 ... 1.5 mm? |
Connections signaling contact | 11, 12, 14 (alarm signal): Plug-in terminal (together with Reset) with 1 screwed connection each for 0.2 ... 1.5 mm? | 11, 12, 14 (alarm signal): Plug-in terminal (together with Reset) with 1 screwed connection each for 0.2 ... 1.5 mm? | 11, 12, 14 (alarm signal): Plug-in terminal (together with Reset) with 1 screwed connection each for 0.2 ... 1.5 mm? | 11, 12, 14 (alarm signal): Plug-in terminal (together with Reset) with 1 screwed connection each for 0.2 ... 1.5 mm? |
Product function | | | | |
| Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes |
Design of the interface for communication | PROFINET/Ethernet: two RJ45 sockets (2-port switch) | PROFINET/Ethernet: two RJ45 sockets (2-port switch) | PROFINET/Ethernet: two RJ45 sockets (2-port switch) | PROFINET/Ethernet: two RJ45 sockets (2-port switch) |
Suitability for interaction modular system | Yes | Yes | Yes | Yes |
Width of the enclosure | 80 mm | 125 mm | 100 mm | 125 mm |
Height of the enclosure | 125 mm | 125 mm | 125 mm | 125 mm |
Depth of the enclosure | 150 mm | 150 mm | 150 mm | 150 mm |
Required spacing | | | | |
| 50 mm | 50 mm | 50 mm | 50 mm |
| 50 mm | 50 mm | 50 mm | 50 mm |
| 0 mm | 0 mm | 0 mm | 0 mm |
| 0 mm | 0 mm | 0 mm | 0 mm |
Weight, approx. | 1.8 kg | 2.6 kg | 2 kg | 2.6 kg |
Product feature of the enclosure housing for side-by-side mounting | Yes | Yes | Yes | Yes |
Installation | Snaps onto DIN rail EN 60715 35x15 | Snaps onto DIN rail EN 60715 35x15 | Snaps onto DIN rail EN 60715 35x15 | Snaps onto DIN rail EN 60715 35x15 |
Electrical accessories | Expansion modules CNX8600, buffer modules BUF8600 | Expansion modules CNX8600, buffer modules BUF8600 | Expansion modules CNX8600, buffer modules BUF8600 | Expansion modules CNX8600, buffer modules BUF8600 |
Mechanical accessories | Device identification label 20 mm ? 7 mm, TI-grey 3RT2900-1SB20 | Device identification label 20 mm ? 7 mm, TI-grey 3RT2900-1SB20 | Device identification label 20 mm ? 7 mm, TI-grey 3RT2900-1SB20 | Device identification label 20 mm ? 7 mm, TI-grey 3RT2900-1SB20 |
MTBF at 40 °C | | | | 226 272 h |
Other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |