Charging current charging voltage | | | | | | |
End-of-charge voltage at DC | | | | | | |
| 28.02 V | 28.02 V | 28.02 V | 28.8 V | 28.02 V | 28.02 V |
| 28.02 V | 28.02 V | 28.02 V | 28.8 V | 28.02 V | 28.02 V |
| 27.8 V | 27.8 V | 27.8 V | 28.8 V | 27.8 V | 27.8 V |
| 27.3 V | 27.3 V | 27.3 V | 28.8 V | 27.3 V | 27.3 V |
| 26.8 V | 26.8 V | 26.8 V | 28.8 V | 26.8 V | 26.8 V |
| 26.6 V | 26.6 V | 26.6 V | 28.8 V | 26.6 V | 26.6 V |
| 26.3 V | 26.3 V | 26.3 V | 28.8 V | 26.3 V | 26.3 V |
| | 26 V | | | | |
Permissible charging current, max. | 0.3 A | 5 A | 0.8 A | 2.1 A | 1.75 A | 3 A |
Rated voltage Vout DC | 24 V | 24 V | 24 V | 24 V | 24 V | 24 V |
Rated current value Iout rated | 10 A | 20 A | 20 A | 20 A | 40 A | 40 A |
Safety | | | | | | |
Short-circuit protection | Battery fuse 15 A/32 V (solid-state circuitry blade-type fuse + support) | Battery fuse 25 A/32 V (solid-state circuitry blade-type fuse + support) | Battery fuse 25 A/32 V (solid-state circuitry blade-type fuse + support) | Battery fuse 25 A/32 V (FKS blade-type fuse + holder); overcurrent switch-off at 60 A > 30 ms/min and 24 A > 5 s/min | Battery fuse 2x 25 A/32 V (solid-state circuitry blade-type fuse + support) | Battery fuse 2x 25 A/32 V (solid-state circuitry blade-type fuse + support) |
Design of the overload protection | Valve control | Valve control | Valve control | Valve control | Valve control | Valve control |
Status display | LED green: Battery OK; LED flashing green: Error or warning; OFF: No communication | LED green: Battery OK; LED flashing green: Error or warning; OFF: No communication | LED green: Battery OK; LED flashing green: Error or warning; OFF: No communication | LED green: Battery OK; LED flashing green: Error or warning; OFF: No communication | LED green: Battery OK; LED flashing green: Error or warning; OFF: No communication | LED green: Battery OK; LED flashing green: Error or warning; OFF: No communication |
Safety | | | | | | |
Protection class | Class III | Class III | Class III | Class III | Class III | Class III |
CE mark | Yes | Yes | Yes | Yes | Yes | Yes |
UL/cUL (CSA) approval | cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627 | cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627 | cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627 | cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627 | cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627 | cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627 |
Explosion protection | IECEx Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2013) Class I, Div. 2, Group ABCD, T4 | IECEx Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2013) Class I, Div. 2, Group ABCD, T4 | IECEx Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2013) Class I, Div. 2, Group ABCD, T4 | No | IECEx Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2013) Class I, Div. 2, Group ABCD, T4 | IECEx Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2013) Class I, Div. 2, Group ABCD, T4 |
Marine approval | GL, ABS | GL, ABS | GL, ABS | GL, ABS | GL, ABS | GL, ABS |
Degree of protection (EN 60529) | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 |
Operating data note | | | | | | |
Operating data note | For storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away. | For storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away. | For storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away. | For storage, mounting and operation of batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. | For storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away. | For storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away. |
Ambient temperature | | | | | | |
| -15 ... +50 °C | -40 ... +60 °C | -15 ... +50 °C | -20 ... +50 °C | -15 ... +50 °C | -15 ... +50 °C |
| -20 ... +50 °C | -40 ... +60 °C | -20 ... +50 °C | -40 ... +60 °C | -20 ... +50 °C | -20 ... +50 °C |
| -20 ... +50 °C | -40 ... +60 °C | -20 ... +50 °C | -40 ... +60 °C | -20 ... +50 °C | -20 ... +50 °C |
Relative temporary capacity loss at 20 °C in a month typical | 3 % | 3 % | 3 % | 3 % | 3 % | 3 % |
Service life | | | | | | |
Service life of energy storage | | | | | | |
| capacity falls to 50 % of original capacity | capacity falls to 50 % of original capacity | capacity falls to 50 % of original capacity | capacity falls to 50 % of original capacity | capacity falls to 50 % of original capacity | capacity falls to 50 % of original capacity |
| 4 y | 10 y | 4 y | 15 y | 4 y | 4 y |
| 2 y | 7 y | 2 y | 10 y | 2 y | 2 y |
| 1 y | 3 y | 1 y | 9 y | 1 y | 1 y |
| 0.5 y | 1.5 y | 0.5 y | 2 y | 0.5 y | 0.5 y |
| | 1 y | | | | |
Ambient temperature during storage Note | Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C. | Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C. | Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C. | Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C. | Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C. | Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C. |
Mechanics | | | | | | |
Connection technology | screw-type terminals | screw-type terminals | screw-type terminals | screw-type terminals | screw-type terminals | screw-type terminals |
Connection for power supply unit | 1 screw terminal each for 0.2 ... 6 mm? for + BATT and - BATT | 1 screw terminal each for 0.2 ... 6 mm? for + BATT and - BATT | 1 screw terminal each for 0.2 ... 6 mm? for + BATT and - BATT | 1 screw terminal each for 0.5 ... 16 mm? for + BATT and - BATT | 1 screw terminal each for 0.5 ... 16 mm? for + BATT and - BATT | 1 screw terminal each for 0.5 ... 16 mm? for + BATT and - BATT |
Type of electrical connection for control circuit and status message | 1 screw terminal each for 0.14 ... 4 mm? | 1 screw terminal each for 0.14 ... 4 mm? | 1 screw terminal each for 0.14 ... 4 mm? | 1 screw terminal each for 0.14 ... 4 mm? | 1 screw terminal each for 0.14 ... 4 mm? | 1 screw terminal each for 0.14 ... 4 mm? |
Product component belonging to | Accessories pack with solid-state circuitry fuse 15 A | Accessories pack with solid-state circuitry fuse 25 A | Accessories pack with solid-state circuitry fuse 25 A | Accessories pack with solid-state circuitry fuse 15 A | Accessories pack with solid-state circuitry fuse 25 A | Accessories pack with solid-state circuitry fuse 25 A |
Width of the enclosure | 89 mm | 265 mm | 190 mm | 189 mm | 186 mm | 253 mm |
Height of the enclosure | 130.3 mm | 115 mm | 169.3 mm | 186 mm | 186 mm | 186 mm |
Depth of the enclosure | 106.7 mm | 76 mm | 78.7 mm | 112.7 mm | 110.3 mm | 110.3 mm |
Installation width | 89 mm | 265 mm | 190 mm | 189 mm | 186 mm | 253 mm |
Installation height | 145.3 mm | 130 mm | 184.3 mm | 201 mm | 201 mm | 201 mm |
Weight, approx. | 1.9 kg | 3.7 kg | 3.8 kg | 3.4 kg | 6.1 kg | 9.8 kg |
Installation | snaps onto DIN rail EN 60715 35x7.5/15 or keyhole mounting for hooking in to M4 screws | snaps onto DIN rail EN 60715 35x7.5/15 or keyhole mounting for hooking in to M4 screws | snaps onto DIN rail EN 60715 35x15 or keyhole mounting for hooking in to M4 screws | snaps onto DIN rail EN 60715 35x7.5/15 or keyhole mounting for hooking in to M4 screws | can be screwed onto flat surface (keyhole mounting for hooking in to M4 screws) | can be screwed onto flat surface (keyhole mounting for hooking in to M4 screws) |
Number of cells | 12 | 12 | 12 | 16 | 12 | 12 |
Equipment marking acc. to DIN EN 81346-2 | G | G | G | G | G | G |
Other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |