Motor dimensioningWhen motors for crane drives are dimensioned (high?inertia drives), two criteria must be taken into account:
When you check the torque, you check whether the motor can generate the required maximum torque (e.g. for acceleration). The maximum permissible torque is greater than the rated torque and is often specified as a multiple of the rated torque. An adequate safety margin from the stalling torque must be maintained. When the output is dimensioned, the rated motor output is adjusted in accordance with the effective power requirements of the drive. The rated motor output depends on the motor temperature which, in turn, is influenced by the operating mode and the thermal behavior of the motor. The rating data of a motor differs for the various operating modes in accordance with EN 60034?1. The data is usually specified for one or more of the following operating modes:
Intermittent duties S4 and S5 vary to such an extent that accurate data can only be provided when certain additional conditions have been clearly defined. The operating modes are defined in accordance with EN 60034?1.
Continuous duty (S1)Definition Operation with a constant load state, the duration of which is sufficient to attain thermal equilibrium. Explanation The operating time te of the motor must be greater than 3 ? TL to ensure that thermal equilibrium is attained. The rated motor output for continuous duty must be designed such that the final temperature ?e matches the permissible winding temperature. Start?up is deliberately discounted under the assumption that a single high?inertia start will not achieve the final temperature. The length of the subsequent idle time is insignificant. Caution is advised, however, when high?inertia starting is carried out on a warm machine or when a machine is started up several times in succession. Certain restrictions may apply or advice from a third party should be sought. Short?time duty (S2)Definition Operation with a constant load state that, however, does not last long enough to attain thermal equilibrium, followed by idle time that lasts until the machine temperature differs from the coolant temperature by no more than 2 K. Explanation The operating time te must be less than 3 ? TL to ensure that the theoretical final temperature is not reached. The rated motor output and the operating time are harmonized in such a way that the maximum winding temperature ?max does not exceed the permissible values. Here, too, start?up is deliberately discounted because it is assumed that the machine starts up cold and the start?up procedure is short with respect to the operating time te. The rated motor output for short?time duty can be higher than for continuous duty, although the permissible operating time must also be specified. The shorter the operating time, the higher the rated output of the machine. Operating times of 10, 30, 60, and 90 minutes are recommended. The subsequent idle time must be sufficiently long to ensure that the machine can cool back down to the ambient temperature (i.e. tP is greater than or equal to 3 ? TSt) because otherwise the maximum temperature will be exceeded the next time a similar duty cycle is carried out. Intermittent duty without the effect of the start?up process (S3)Definition Operation that involves a sequence of similar duty cycles, each with a constant?load period and idle time, whereby the starting current does not have a noticeable effect on the temperature rise (the duty cycle duration is generally short enough to ensure that thermal equilibrium is not attained). Explanation The operating time te must be less than 3 ? TL to ensure that the theoretical final temperature ?e is not reached. The subsequent idle time tp, however, is also less than 3 ? TSt, which means that the ambient temperature is no longer reached. A mean steady?state value ?mean develops around which the temperature varies, but is below the theoretical final temperature ?e. The rated motor output during intermittent duty is greater than during continuous duty. The time constants TL and TSt may be different. This influences the rated output during intermittent duty and is taken into account in the S3 motor tables. To determine the most suitable motor, therefore, a knowledge of the operating and idle times is required in addition to the required output during the operating time. They are specified by the duty cycle duration (total time) and the relative ON duration in % of the cycle duration. If no data has been provided for the duty cycle duration, 10 minutes apply in accordance with DIN EN 60034?1. The S3 motor tables are based on this. Values of 15, 25, 40, and 60 % are recommended for the cyclic duration factor. Effect of varying duty cycle durations The S3 rated output is designed in such a way that the temperature peaks ?max match the permissible values with a 10 minute duty cycle duration (see "a" in diagram below). Shorter duty cycle durations are not critical because lower temperature peaks occur at the same mean winding temperature ?mean (see "b" in diagram below). Since longer duty cycle durations result in higher temperature peaks (see "c" in diagram below) which, in turn, reduce the service life of the insulation, advice from a third party should be sought in this case. In S3 duty, the start?up processes are not discounted; the relevant standard assumes that they do not have any significant influence on the temperature rise. Any number of duty cycles can be carried out per hour provided that this standard is fulfilled. Intermittent duty with effect of the start?up process (S4) |
|||||||||||||||||||||||||||||||||||||
ED | ON time |
Mrms | rms torque |
M1, M2, M3 | Torques in travel diagram |
t1, t2, t3 | Operating times of torques M1, M2, M3 |
tP | Idle time |
te | Operating time of motor = t1 + t2 + t3 |
tS | Duty cycle duration = te + tP |
Torque diagram
Typical torque diagram for a gantry across one conveying cycle
Typical torque diagram for hoist across one conveying cycle


