Central processing units

Order number

6ES7412-1XJ05-0AB0

6ES7412-2XJ05-0AB0

6ES7412-2EK07-0AB0

CPU412-1, MPI/DP, 288 KB

CPU412-2, MPI/DP, 512 KB

CPU412-2 PN, 1 MB, 2 SCHNITTSTELLEN

General information

 

 

 

Product type designation

CPU 412-1

CPU 412-2

CPU 412-2 PN

Engineering with

 

 

 

  • ? Programming package

STEP 7 V5.3 SP2 or higher with HW update

STEP 7 V5.3 SP2 or higher with HW update

STEP 7 V5.5 or higher with HSP 262

Supply voltage

 

 

 

Rated value (DC)

  • ? 24 V DC

No; Power supply via system power supply

No; Power supply via system power supply

No; Power supply via system power supply

Power loss

 

 

 

Power loss, typ.

2.5 W

4.5 W

5.5 W

Memory

 

 

 

Work memory

 

 

 

  • ? integrated

288 kbyte

512 kbyte

1 Mbyte

  • ? integrated (for program)

144 kbyte

256 kbyte

512 kbyte

  • ? integrated (for data)

144 kbyte

256 kbyte

512 kbyte

Load memory

 

 

 

  • ? expandable FEPROM, max.

64 Mbyte

64 Mbyte

64 Mbyte

  • ? integrated RAM, max.

512 kbyte

512 kbyte

512 kbyte

  • ? expandable RAM, max.

64 Mbyte

64 Mbyte

64 Mbyte

CPU processing times

 

 

 

for bit operations, typ.

75 ns

75 ns

31.25 ns

for word operations, typ.

75 ns

75 ns

31.25 ns

for fixed point arithmetic, typ.

75 ns

75 ns

31.25 ns

for floating point arithmetic, typ.

225 ns

225 ns

62.5 ns

Counters, timers and their retentivity

 

 

 

S7 counter

 

 

 

  • ? Number

2 048

2 048

2 048

IEC counter

 

 

 

  • ? present

Yes

Yes

Yes

S7 times

 

 

 

  • ? Number

2 048

2 048

2 048

IEC timer

 

 

 

  • ? present

Yes

Yes

Yes

Data areas and their retentivity

 

 

 

Flag

 

 

 

  • ? Number, max.

4 kbyte; Size of bit memory address area

4 kbyte; Size of bit memory address area

4 kbyte; Size of bit memory address area

Address area

 

 

 

I/O address area

 

 

 

  • ? Inputs

4 kbyte

4 kbyte

4 kbyte

  • ? Outputs

4 kbyte

4 kbyte

4 kbyte

Process image

 

 

 

  • ? Inputs, adjustable

4 kbyte

4 kbyte

4 kbyte

  • ? Outputs, adjustable

4 kbyte

4 kbyte

4 kbyte

Time of day

 

 

 

Clock

 

 

 

  • ? Hardware clock (real-time)

Yes

Yes

Yes

Operating hours counter

 

 

 

  • ? Number

16

16

16

Interfaces

 

 

 

Interfaces/bus type

1 x MPI/PROFIBUS DP

1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP

1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports)

Number of RS 485 interfaces

1; Combined MPI / PROFIBUS DP

2; Combined MPI / PROFIBUS DP and PROFIBUS DP

1; Combined MPI / PROFIBUS DP

1. Interface

 

 

 

Interface type

Integrated

Integrated

Integrated

Physics

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

Functionality

 

 

 

  • ? MPI

Yes

Yes

Yes

  • ? PROFIBUS DP master

Yes

Yes

Yes

  • ? PROFIBUS DP slave

Yes

Yes

Yes

DP master

 

 

 

  • ? Number of DP slaves, max.

32

32

32

2. Interface

 

 

 

Interface type

Integrated

PROFINET

Physics

RS 485 / PROFIBUS

Ethernet RJ45

Interface types

 

 

 

  • ? Number of ports

2

Functionality

 

 

 

  • ? PROFINET IO Controller

Yes

  • ? PROFINET IO Device

Yes

  • ? PROFINET CBA

Yes

  • ? PROFIBUS DP master

Yes

No

  • ? PROFIBUS DP slave

Yes

No

DP master

 

 

 

  • ? Number of DP slaves, max.

64

Isochronous mode

 

 

 

Isochronous operation (application synchronized up to terminal)

Yes; For PROFIBUS only

Yes; For PROFIBUS only

Yes; Via PROFIBUS DP or PROFINET interface

Communication functions

 

 

 

PG/OP communication

Yes

Yes

Yes

Data record routing

Yes

Yes

Yes

Global data communication

 

 

 

  • ? supported

Yes

Yes

Yes

S7 basic communication

 

 

 

  • ? supported

Yes

Yes

Yes

S7 communication

 

 

 

  • ? supported

Yes

Yes

Yes

S5 compatible communication

 

 

 

  • ? supported

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Standard communication (FMS)

 

 

 

  • ? supported

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Open IE communication

 

 

 

  • ? TCP/IP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

46

  • ? ISO-on-TCP (RFC1006)

Via CP 443-1 Adv. and loadable FB

Via CP 443-1 and loadable FB

Yes; Via integrated PROFINET interface or CP 443-1 Adv. and loadable FBs

  • Number of connections, max.

46

  • ? UDP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

46

Web server

 

 

 

  • ? supported

No

No

Yes

Number of connections

 

 

 

  • ? overall

32

32

48

Standards, approvals, certificates

 

 

 

Use in hazardous areas

 

 

 

  • ? ATEX

ATEX II 3G Ex nA IIC T4 Gc

ATEX II 3G Ex nA IIC T4 Gc

ATEX II 3G Ex nA IIC T4 Gc

Ambient conditions

 

 

 

Ambient temperature during operation

 

 

 

  • ? min.

0 °C

0 °C

0 °C

  • ? max.

60 °C

60 °C

60 °C

Configuration

 

 

 

Know-how protection

 

 

 

  • ? User program protection/password protection

Yes

Yes

Yes

  • ? Block encryption

Yes; With S7 block Privacy

Dimensions

 

 

 

Width

25 mm

25 mm

25 mm

Height

290 mm

290 mm

290 mm

Depth

219 mm

219 mm

219 mm

Weights

 

 

 

Weight, approx.

700 g

700 g

750 g


Order number

6ES7414-2XK05-0AB0

6ES7414-3XM05-0AB0

6ES7414-3EM07-0AB0

CPU414-2, MPI/DP, 1 MB

CPU414-3, 2.8 MB, 3 INTERFACES

CPU414-3 PN/DP, 4 MB, 3 INTERFACES

General information

 

 

 

Product type designation

CPU 414-2

CPU 414-3

CPU414-3 PN/DP

Engineering with

 

 

 

  • ? Programming package

STEP 7 V5.3 SP2 or higher with HW update

STEP 7 V5.3 SP2 or higher with HW update

STEP 7 V5.5 or higher with HSP 262

Supply voltage

 

 

 

Rated value (DC)

  • ? 24 V DC

No; Power supply via system power supply

No; Power supply via system power supply

No; Power supply via system power supply

Power loss

 

 

 

Power loss, typ.

4.5 W

5.5 W

6.5 W

Memory

 

 

 

Work memory

 

 

 

  • ? integrated

1 Mbyte

2.8 Mbyte

4 Mbyte

  • ? integrated (for program)

0.5 Mbyte

1.4 Mbyte

2 Mbyte

  • ? integrated (for data)

0.5 Mbyte

1.4 Mbyte

2 Mbyte

Load memory

 

 

 

  • ? expandable FEPROM, max.

64 Mbyte

64 Mbyte

64 Mbyte

  • ? integrated RAM, max.

512 kbyte

512 kbyte

512 kbyte

  • ? expandable RAM, max.

64 Mbyte

64 Mbyte

64 Mbyte

CPU processing times

 

 

 

for bit operations, typ.

45 ns

45 ns

18.75 ns

for word operations, typ.

45 ns

45 ns

18.75 ns

for fixed point arithmetic, typ.

45 ns

45 ns

18.75 ns

for floating point arithmetic, typ.

135 ns

135 ns

37.5 ns

Counters, timers and their retentivity

 

 

 

S7 counter

 

 

 

  • ? Number

2 048

2 048

2 048

IEC counter

 

 

 

  • ? present

Yes

Yes

Yes

S7 times

 

 

 

  • ? Number

2 048

2 048

2 048

IEC timer

 

 

 

  • ? present

Yes

Yes

Yes

Data areas and their retentivity

 

 

 

Flag

 

 

 

  • ? Number, max.

8 kbyte; Size of bit memory address area

8 kbyte; Size of bit memory address area

8 kbyte; Size of bit memory address area

Address area

 

 

 

I/O address area

 

 

 

  • ? Inputs

8 kbyte

8 kbyte

8 kbyte

  • ? Outputs

8 kbyte

8 kbyte

8 kbyte

Process image

 

 

 

  • ? Inputs, adjustable

8 kbyte

8 kbyte

8 kbyte

  • ? Outputs, adjustable

8 kbyte

8 kbyte

8 kbyte

Time of day

 

 

 

Clock

 

 

 

  • ? Hardware clock (real-time)

Yes

Yes

Yes

Operating hours counter

 

 

 

  • ? Number

16

16

16

Interfaces

 

 

 

Interfaces/bus type

1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP

1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP, 1 x PROFIBUS DP (optionally pluggable)

1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports), 1 x PROFIBUS DP (optionally pluggable)

Number of RS 485 interfaces

2; Combined MPI / PROFIBUS DP and PROFIBUS DP

2; Combined MPI / PROFIBUS DP and PROFIBUS DP

1; Combined MPI / PROFIBUS DP

Number of other interfaces

1; PROFIBUS DP with IF 964-DP (plug-in option; MLFB: 6ES7964-2AA04-0AB0)

1. Interface

 

 

 

Interface type

Integrated

Integrated

Integrated

Physics

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

Functionality

 

 

 

  • ? MPI

Yes

Yes

Yes

  • ? PROFIBUS DP master

Yes

Yes

Yes

  • ? PROFIBUS DP slave

Yes

Yes

Yes

DP master

 

 

 

  • ? Number of DP slaves, max.

32

32

32

2. Interface

 

 

 

Interface type

Integrated

Integrated

PROFINET

Physics

RS 485 / PROFIBUS

RS 485 / PROFIBUS

Ethernet RJ45

Interface types

 

 

 

  • ? Number of ports

2

Functionality

 

 

 

  • ? PROFINET IO Controller

Yes

  • ? PROFINET IO Device

Yes

  • ? PROFINET CBA

Yes

  • ? PROFIBUS DP master

Yes

Yes

No

  • ? PROFIBUS DP slave

Yes

Yes

No

DP master

 

 

 

  • ? Number of DP slaves, max.

96

96

3. Interface

 

 

 

Interface type

Pluggable interface module (IF), technical data as for 2nd interface

Pluggable interface module (IF)

Plug-in interface modules

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

Physics

RS 485 / PROFIBUS

RS 485 / PROFIBUS

Functionality

 

 

 

  • ? MPI

No

No

  • ? PROFIBUS DP master

Yes

Yes

  • ? PROFIBUS DP slave

Yes

Yes

DP master

 

 

 

  • ? Number of DP slaves, max.

96

96

Isochronous mode

 

 

 

Isochronous operation (application synchronized up to terminal)

Yes; For PROFIBUS only

Yes; For PROFIBUS only

Yes; Via PROFIBUS DP or PROFINET interface

Communication functions

 

 

 

PG/OP communication

Yes

Yes

Yes

Data record routing

Yes

Yes

Yes

Global data communication

 

 

 

  • ? supported

Yes

Yes

Yes

S7 basic communication

 

 

 

  • ? supported

Yes

Yes

Yes

S7 communication

 

 

 

  • ? supported

Yes

Yes

Yes

S5 compatible communication

 

 

 

  • ? supported

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Standard communication (FMS)

 

 

 

  • ? supported

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Open IE communication

 

 

 

  • ? TCP/IP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

62

  • ? ISO-on-TCP (RFC1006)

Via CP 443-1 and loadable FB

Via CP 443-1 and loadable FB

Yes; Via integrated PROFINET interface or CP 443-1 Adv. and loadable FBs

  • Number of connections, max.

62

  • ? UDP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

62

Web server

 

 

 

  • ? supported

No

No

Yes

Number of connections

 

 

 

  • ? overall

32

32

64

Standards, approvals, certificates

 

 

 

Use in hazardous areas

 

 

 

  • ? ATEX

ATEX II 3G Ex nA IIC T4 Gc

ATEX II 3G Ex nA IIC T4 Gc

ATEX II 3G Ex nA IIC T4 Gc

Ambient conditions

 

 

 

Ambient temperature during operation

 

 

 

  • ? min.

0 °C

0 °C

0 °C

  • ? max.

60 °C

60 °C

60 °C

Configuration

 

 

 

Know-how protection

 

 

 

  • ? User program protection/password protection

Yes

Yes

Yes

  • ? Block encryption

Yes; With S7 block Privacy

Dimensions

 

 

 

Width

25 mm

50 mm

50 mm

Height

290 mm

290 mm

290 mm

Depth

219 mm

219 mm

219 mm

Weights

 

 

 

Weight, approx.

700 g

900 g

900 g


Order number

6ES7416-2XN05-0AB0

6ES7416-3XR05-0AB0

6ES7416-3ES07-0AB0

CPU 416-2, MPI, PROFIBUS, 5.6 MB

CPU 416-3, 11.2 MB, 3 INTERFACES

CPU416-3 PN/DP, 16 MB, 3 INTERFACES

General information

 

 

 

Product type designation

CPU 416-2

CPU 416-3

CPU416-3 PN/DP

Engineering with

 

 

 

  • ? Programming package

STEP 7 V5.3 SP2 or higher with HW update

STEP 7 V5.3 SP2 or higher with HW update

STEP 7 V5.5 or higher with HSP 262

Supply voltage

 

 

 

Rated value (DC)

  • ? 24 V DC

No; Power supply via system power supply

No; Power supply via system power supply

No; Power supply via system power supply

Power loss

 

 

 

Power loss, typ.

4.5 W

5.5 W

6.5 W

Memory

 

 

 

Work memory

 

 

 

  • ? integrated

5.6 Mbyte

11.2 Mbyte

16 Mbyte

  • ? integrated (for program)

2.8 Mbyte

5.6 Mbyte

8 Mbyte

  • ? integrated (for data)

2.8 Mbyte

5.6 Mbyte

8 Mbyte

Load memory

 

 

 

  • ? expandable FEPROM, max.

64 Mbyte

64 Mbyte

64 Mbyte

  • ? integrated RAM, max.

1 Mbyte

1 Mbyte

1 Mbyte

  • ? expandable RAM, max.

64 Mbyte

64 Mbyte

64 Mbyte

CPU processing times

 

 

 

for bit operations, typ.

30 ns

30 ns

12.5 ns

for word operations, typ.

30 ns

30 ns

12.5 ns

for fixed point arithmetic, typ.

30 ns

30 ns

12.5 ns

for floating point arithmetic, typ.

90 ns

90 ns

25 ns

Counters, timers and their retentivity

 

 

 

S7 counter

 

 

 

  • ? Number

2 048

2 048

2 048

IEC counter

 

 

 

  • ? present

Yes

Yes

Yes

S7 times

 

 

 

  • ? Number

2 048

2 048

2 048

IEC timer

 

 

 

  • ? present

Yes

Yes

Yes

Data areas and their retentivity

 

 

 

Flag

 

 

 

  • ? Number, max.

16 kbyte; Size of bit memory address area

16 kbyte; Size of bit memory address area

16 kbyte; Size of bit memory address area

Address area

 

 

 

I/O address area

 

 

 

  • ? Inputs

16 kbyte

16 kbyte

16 kbyte

  • ? Outputs

16 kbyte

16 kbyte

16 kbyte

Process image

 

 

 

  • ? Inputs, adjustable

16 kbyte

16 kbyte

16 kbyte

  • ? Outputs, adjustable

16 kbyte

16 kbyte

16 kbyte

Time of day

 

 

 

Clock

 

 

 

  • ? Hardware clock (real-time)

Yes

Yes

Yes

Operating hours counter

 

 

 

  • ? Number

16

16

16

Interfaces

 

 

 

Interfaces/bus type

1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP

1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP, 1 x PROFIBUS DP (optionally pluggable)

1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports), 1 x PROFIBUS DP (optionally pluggable)

Number of RS 485 interfaces

2; Combined MPI / PROFIBUS DP and PROFIBUS DP

2

1; Combined MPI / PROFIBUS DP

Number of other interfaces

0

1; PROFIBUS DP with IF 964-DP (plug-in option; MLFB: 6ES7964-2AA04-0AB0)

1. Interface

 

 

 

Interface type

Integrated

Integrated

Integrated

Physics

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

Functionality

 

 

 

  • ? MPI

Yes

Yes

Yes

  • ? PROFIBUS DP master

Yes

Yes

Yes

  • ? PROFIBUS DP slave

Yes

Yes

Yes

DP master

 

 

 

  • ? Number of DP slaves, max.

32

32

32

2. Interface

 

 

 

Interface type

Integrated

Integrated

PROFINET

Physics

RS 485 / PROFIBUS

RS 485 / PROFIBUS

Ethernet RJ45

Interface types

 

 

 

  • ? Number of ports

2

Functionality

 

 

 

  • ? PROFINET IO Controller

Yes

  • ? PROFINET IO Device

Yes

  • ? PROFINET CBA

Yes

  • ? PROFIBUS DP master

Yes

Yes

No

  • ? PROFIBUS DP slave

Yes

Yes

No

DP master

 

 

 

  • ? Number of DP slaves, max.

125

125

3. Interface

 

 

 

Interface type

Pluggable interface module (IF), technical data as for 2nd interface

Pluggable interface module (IF)

Plug-in interface modules

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

Physics

RS 485 / PROFIBUS

RS 485 / PROFIBUS

Functionality

 

 

 

  • ? MPI

No

No

  • ? PROFIBUS DP master

Yes

Yes

  • ? PROFIBUS DP slave

Yes

Yes

DP master

 

 

 

  • ? Number of DP slaves, max.

125

125

Isochronous mode

 

 

 

Isochronous operation (application synchronized up to terminal)

Yes; For PROFIBUS only

Yes; For PROFIBUS only

Yes; Via PROFIBUS DP or PROFINET interface

Communication functions

 

 

 

PG/OP communication

Yes

Yes

Yes

Data record routing

Yes

Yes

Yes

Global data communication

 

 

 

  • ? supported

Yes

Yes

Yes

S7 basic communication

 

 

 

  • ? supported

Yes

Yes

Yes

S7 communication

 

 

 

  • ? supported

Yes

Yes

Yes

S5 compatible communication

 

 

 

  • ? supported

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Standard communication (FMS)

 

 

 

  • ? supported

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Open IE communication

 

 

 

  • ? TCP/IP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

94

  • ? ISO-on-TCP (RFC1006)

Via CP 443-1 and loadable FB

Via CP 443-1 and loadable FB

Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs

  • Number of connections, max.

94

  • ? UDP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

94

Web server

 

 

 

  • ? supported

No

No

Yes

Number of connections

 

 

 

  • ? overall

64

64

96

Standards, approvals, certificates

 

 

 

Use in hazardous areas

 

 

 

  • ? ATEX

ATEX II 3G Ex nA IIC T4 Gc

ATEX II 3G Ex nA IIC T4 Gc

ATEX II 3G Ex nA IIC T4 Gc

Ambient conditions

 

 

 

Ambient temperature during operation

 

 

 

  • ? min.

0 °C

0 °C

0 °C

  • ? max.

60 °C

60 °C

60 °C

Configuration

 

 

 

Know-how protection

 

 

 

  • ? User program protection/password protection

Yes

Yes

Yes

  • ? Block encryption

Yes; With S7 block Privacy

Dimensions

 

 

 

Width

25 mm

50 mm

50 mm

Height

290 mm

290 mm

290 mm

Depth

219 mm

219 mm

219 mm

Weights

 

 

 

Weight, approx.

720 g

900 g

900 g


Order number

6ES7417-4XT07-0AB0

CPU 417-4, 32 MB, 4 INTERFACES

General information

 

Product type designation

CPU 417-4

Engineering with

 

  • ? Programming package

STEP 7 V5.4 or higher with HSP 261

Supply voltage

 

Rated value (DC)

  • ? 24 V DC

No; Power supply via system power supply

Power loss

 

Power loss, typ.

6.5 W

Memory

 

Work memory

 

  • ? integrated

32 Mbyte

  • ? integrated (for program)

16 Mbyte

  • ? integrated (for data)

16 Mbyte

Load memory

 

  • ? expandable FEPROM, max.

64 Mbyte

  • ? integrated RAM, max.

1 Mbyte

  • ? expandable RAM, max.

64 Mbyte

CPU processing times

 

for bit operations, typ.

7.5 ns

for word operations, typ.

7.5 ns

for fixed point arithmetic, typ.

7.5 ns

for floating point arithmetic, typ.

15 ns

Counters, timers and their retentivity

 

S7 counter

 

  • ? Number

2 048

IEC counter

 

  • ? present

Yes

S7 times

 

  • ? Number

2 048

IEC timer

 

  • ? present

Yes

Data areas and their retentivity

 

Flag

 

  • ? Number, max.

16 kbyte; Size of bit memory address area

Address area

 

I/O address area

 

  • ? Inputs

16 kbyte

  • ? Outputs

16 kbyte

Process image

 

  • ? Inputs, adjustable

16 kbyte

  • ? Outputs, adjustable

16 kbyte

Time of day

 

Clock

 

  • ? Hardware clock (real-time)

Yes

Operating hours counter

 

  • ? Number

16

Interfaces

 

Interfaces/bus type

1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP, 2 x PROFIBUS DP (optionally pluggable)

Number of RS 485 interfaces

2; Combined MPI / PROFIBUS DP and PROFIBUS DP

Number of other interfaces

2; PROFIBUS DP with IF 964-DP (plug-in option; MLFB: 6ES7964-2AA04-0AB0)

1. Interface

 

Interface type

Integrated

Physics

RS 485 / PROFIBUS + MPI

Functionality

 

  • ? MPI

Yes

  • ? PROFIBUS DP master

Yes

  • ? PROFIBUS DP slave

Yes

DP master

 

  • ? Number of DP slaves, max.

32

2. Interface

 

Interface type

Integrated

Physics

RS 485 / PROFIBUS

Functionality

 

  • ? PROFIBUS DP master

Yes

  • ? PROFIBUS DP slave

Yes

DP master

 

  • ? Number of DP slaves, max.

125

3. Interface

 

Interface type

Pluggable interface module (IF), technical data as for 2nd interface

Plug-in interface modules

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

Physics

RS 485 / PROFIBUS

Functionality

 

  • ? MPI

No

  • ? PROFIBUS DP master

Yes

  • ? PROFIBUS DP slave

Yes

DP master

 

  • ? Number of DP slaves, max.

125

4. Interface

 

Interface type

Pluggable interface module (IF), technical data as for 2nd interface

Plug-in interface modules

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

Isochronous mode

 

Isochronous operation (application synchronized up to terminal)

Yes; For PROFIBUS only

Communication functions

 

PG/OP communication

Yes

Data record routing

Yes

Global data communication

 

  • ? supported

Yes

S7 basic communication

 

  • ? supported

Yes

S7 communication

 

  • ? supported

Yes

S5 compatible communication

 

  • ? supported

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Standard communication (FMS)

 

  • ? supported

Yes; Via CP and loadable FB

Open IE communication

 

  • ? ISO-on-TCP (RFC1006)

Via CP 443-1 and loadable FB

Web server

 

  • ? supported

No

Number of connections

 

  • ? overall

120

Standards, approvals, certificates

 

Use in hazardous areas

 

  • ? ATEX

ATEX II 3G Ex nA IIC T4 Gc

Ambient conditions

 

Ambient temperature during operation

 

  • ? min.

0 °C

  • ? max.

60 °C

Configuration

 

Know-how protection

 

  • ? User program protection/password protection

Yes

  • ? Block encryption

Yes; With S7 block Privacy

Dimensions

 

Width

50 mm

Height

290 mm

Depth

219 mm

Weights

 

Weight, approx.

900 g


Order number

6ES7414-3FM07-0AB0

CPU414F-3 PN/DP, 4 MB, 3 INTERFACES

General information

 

Product type designation

CPU414F-3 PN/DP

Engineering with

 

  • ? Programming package

STEP 7 V5.5 or higher with HSP 262

Supply voltage

 

Rated value (DC)

  • ? 24 V DC

No; Power supply via system power supply

Power loss

 

Power loss, typ.

6.5 W

Memory

 

Work memory

 

  • ? integrated

4 Mbyte

  • ? integrated (for program)

2 Mbyte

  • ? integrated (for data)

2 Mbyte

Load memory

 

  • ? expandable FEPROM, max.

64 Mbyte

  • ? integrated RAM, max.

512 kbyte

  • ? expandable RAM, max.

64 Mbyte

CPU processing times

 

for bit operations, typ.

18.75 ns

for word operations, typ.

18.75 ns

for fixed point arithmetic, typ.

18.75 ns

for floating point arithmetic, typ.

37.5 ns

Counters, timers and their retentivity

 

S7 counter

 

  • ? Number

2 048

IEC counter

 

  • ? present

Yes

S7 times

 

  • ? Number

2 048

IEC timer

 

  • ? present

Yes

Data areas and their retentivity

 

Flag

 

  • ? Number, max.

8 kbyte; Size of bit memory address area

Address area

 

I/O address area

 

  • ? Inputs

8 kbyte

  • ? Outputs

8 kbyte

Process image

 

  • ? Inputs, adjustable

8 kbyte

  • ? Outputs, adjustable

8 kbyte

Time of day

 

Clock

 

  • ? Hardware clock (real-time)

Yes

Operating hours counter

 

  • ? Number

16

Interfaces

 

Interfaces/bus type

1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports), 1 x PROFIBUS DP (optionally pluggable)

Number of RS 485 interfaces

1; Combined MPI / PROFIBUS DP

Number of other interfaces

1; PROFIBUS DP with IF 964-DP (plug-in option; MLFB: 6ES7964-2AA04-0AB0)

1. Interface

 

Interface type

Integrated

Physics

RS 485 / PROFIBUS + MPI

Functionality

 

  • ? MPI

Yes

  • ? PROFIBUS DP master

Yes

  • ? PROFIBUS DP slave

Yes

DP master

 

  • ? Number of DP slaves, max.

32

2. Interface

 

Interface type

PROFINET

Physics

Ethernet RJ45

Interface types

 

  • ? Number of ports

2

Functionality

 

  • ? PROFINET IO Controller

Yes

  • ? PROFINET IO Device

Yes

  • ? PROFINET CBA

Yes

  • ? PROFIBUS DP master

No

  • ? PROFIBUS DP slave

No

3. Interface

 

Interface type

Pluggable interface module (IF)

Plug-in interface modules

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

Physics

RS 485 / PROFIBUS

Functionality

 

  • ? MPI

No

  • ? PROFIBUS DP master

Yes

  • ? PROFIBUS DP slave

Yes

DP master

 

  • ? Number of DP slaves, max.

96

Isochronous mode

 

Isochronous operation (application synchronized up to terminal)

Yes; Via PROFIBUS DP or PROFINET interface

Communication functions

 

PG/OP communication

Yes

Data record routing

Yes

Global data communication

 

  • ? supported

Yes

S7 basic communication

 

  • ? supported

Yes

S7 communication

 

  • ? supported

Yes

S5 compatible communication

 

  • ? supported

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Standard communication (FMS)

 

  • ? supported

Yes; Via CP and loadable FB

Open IE communication

 

  • ? TCP/IP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

62

  • ? ISO-on-TCP (RFC1006)

Yes; Via integrated PROFINET interface or CP 443-1 Adv. and loadable FBs

  • Number of connections, max.

62

  • ? UDP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

62

Web server

 

  • ? supported

Yes

Number of connections

 

  • ? overall

64

Standards, approvals, certificates

 

Use in hazardous areas

 

  • ? ATEX

ATEX II 3G Ex nA IIC T4 Gc

Ambient conditions

 

Ambient temperature during operation

 

  • ? min.

0 °C

  • ? max.

60 °C

Configuration

 

Know-how protection

 

  • ? User program protection/password protection

Yes

  • ? Block encryption

Yes; With S7 block Privacy

Dimensions

 

Width

50 mm

Height

290 mm

Depth

219 mm

Weights

 

Weight, approx.

900 g


Order number

6ES7416-2FN05-0AB0

6ES7416-3FS07-0AB0

CPU 416F-2, MPI, PROFIBUS, 5.6 MB

CPU416F-3 PN/DP, 16 MB, 3 INTERFACES

General information

 

 

Product type designation

CPU 416F-2

CPU416F-3 PN/DP

Engineering with

 

 

  • ? Programming package

STEP 7 V5.3 SP2 or higher with hardware update, Distributed Safety V5.2 SP2 or higher

STEP 7 V5.5 or higher with HSP 262

Supply voltage

 

 

Rated value (DC)

  • ? 24 V DC

No; Power supply via system power supply

No; Power supply via system power supply

Power loss

 

 

Power loss, typ.

4.5 W

6.5 W

Memory

 

 

Work memory

 

 

  • ? integrated

5.6 Mbyte

16 Mbyte

  • ? integrated (for program)

2.8 Mbyte

8 Mbyte

  • ? integrated (for data)

2.8 Mbyte

8 Mbyte

Load memory

 

 

  • ? expandable FEPROM, max.

64 Mbyte

64 Mbyte

  • ? integrated RAM, max.

1 Mbyte

1 Mbyte

  • ? expandable RAM, max.

64 Mbyte

64 Mbyte

CPU processing times

 

 

for bit operations, typ.

30 ns

12.5 ns

for word operations, typ.

30 ns

12.5 ns

for fixed point arithmetic, typ.

30 ns

12.5 ns

for floating point arithmetic, typ.

90 ns

25 ns

Counters, timers and their retentivity

 

 

S7 counter

 

 

  • ? Number

2 048

2 048

IEC counter

 

 

  • ? present

Yes

Yes

S7 times

 

 

  • ? Number

2 048

2 048

IEC timer

 

 

  • ? present

Yes

Yes

Data areas and their retentivity

 

 

Flag

 

 

  • ? Number, max.

16 kbyte; Size of bit memory address area

16 kbyte; Size of bit memory address area

Address area

 

 

I/O address area

 

 

  • ? Inputs

16 kbyte

16 kbyte

  • ? Outputs

16 kbyte

16 kbyte

Process image

 

 

  • ? Inputs, adjustable

16 kbyte

16 kbyte

  • ? Outputs, adjustable

16 kbyte

16 kbyte

Time of day

 

 

Clock

 

 

  • ? Hardware clock (real-time)

Yes

Yes

Operating hours counter

 

 

  • ? Number

16

16

Interfaces

 

 

Interfaces/bus type

1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports), 1 x PROFIBUS DP (optionally pluggable)

Number of RS 485 interfaces

2; Combined MPI / PROFIBUS DP and PROFIBUS DP

1; Combined MPI / PROFIBUS DP

Number of other interfaces

1; PROFIBUS DP with IF 964-DP (plug-in option; MLFB: 6ES7964-2AA04-0AB0)

1. Interface

 

 

Interface type

Integrated

Integrated

Physics

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

Functionality

 

 

  • ? MPI

Yes

Yes

  • ? PROFIBUS DP master

Yes

Yes

  • ? PROFIBUS DP slave

Yes

Yes

DP master

 

 

  • ? Number of DP slaves, max.

32

32

2. Interface

 

 

Interface type

Integrated

PROFINET

Physics

RS 485 / PROFIBUS

Ethernet RJ45

Interface types

 

 

  • ? Number of ports

2

Functionality

 

 

  • ? PROFINET IO Controller

Yes

  • ? PROFINET IO Device

Yes

  • ? PROFINET CBA

Yes

  • ? PROFIBUS DP master

Yes

No

  • ? PROFIBUS DP slave

Yes

No

DP master

 

 

  • ? Number of DP slaves, max.

125

3. Interface

 

 

Interface type

Pluggable interface module (IF)

Plug-in interface modules

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

Physics

RS 485 / PROFIBUS

Functionality

 

 

  • ? MPI

No

  • ? PROFIBUS DP master

Yes

  • ? PROFIBUS DP slave

Yes

DP master

 

 

  • ? Number of DP slaves, max.

125

Isochronous mode

 

 

Isochronous operation (application synchronized up to terminal)

Yes; For PROFIBUS only

Yes; Via PROFIBUS DP or PROFINET interface

Communication functions

 

 

PG/OP communication

Yes

Yes

Data record routing

Yes

Yes

Global data communication

 

 

  • ? supported

Yes

Yes

S7 basic communication

 

 

  • ? supported

Yes

Yes

S7 communication

 

 

  • ? supported

Yes

Yes

S5 compatible communication

 

 

  • ? supported

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Standard communication (FMS)

 

 

  • ? supported

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Open IE communication

 

 

  • ? TCP/IP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

94

  • ? ISO-on-TCP (RFC1006)

Via CP 443-1 and loadable FB

Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs

  • Number of connections, max.

94

  • ? UDP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

94

Web server

 

 

  • ? supported

No

Yes

Number of connections

 

 

  • ? overall

64

96

Standards, approvals, certificates

 

 

Use in hazardous areas

 

 

  • ? ATEX

ATEX II 3G Ex nA IIC T4 Gc

ATEX II 3G Ex nA IIC T4 Gc

Ambient conditions

 

 

Ambient temperature during operation

 

 

  • ? min.

0 °C

0 °C

  • ? max.

60 °C

60 °C

Configuration

 

 

Know-how protection

 

 

  • ? User program protection/password protection

Yes

Yes

  • ? Block encryption

Yes; With S7 block Privacy

Dimensions

 

 

Width

25 mm

50 mm

Height

290 mm

290 mm

Depth

219 mm

219 mm

Weights

 

 

Weight, approx.

700 g

900 g


Order number

6ES7412-5HK06-0AB0

6ES7414-5HM06-0AB0

6ES7416-5HS06-0AB0

6ES7417-5HT06-0AB0

CPU412-5H PN/DP, 1MB F. S7-400H/F/FH

CPU414-5H PN/DP, 4MB F. S7-400H/F/FH

CPU416-5H PN/DP, 16MB F. S7-400H/F/FH

CPU417-5H PN/DP, 32MB F. S7-400H/F/FH

General information

 

 

 

 

Product type designation

CPU 412-5H PN/DP

CPU 414-5H PN/DP

CPU 416-5H PN/DP

CPU 417-5H PN/DP

Engineering with

 

 

 

 

  • ? Programming package

As of STEP 7 V5.5 SP2 with HF1

As of STEP 7 V5.5 SP2 with HF1

As of STEP 7 V5.5 SP2 with HF1

As of STEP 7 V5.5 SP2 with HF1

Supply voltage

 

 

 

 

Rated value (DC)

  • ? 24 V DC

No; Power supply via system power supply

No; Power supply via system power supply

No; Power supply via system power supply

No; Power supply via system power supply

Power loss

 

 

 

 

Power loss, typ.

7.5 W

7.5 W

7.5 W

7.5 W

Memory

 

 

 

 

Work memory

 

 

 

 

  • ? integrated

1 Mbyte

4 Mbyte

16 Mbyte

32 Mbyte

  • ? integrated (for program)

512 kbyte

2 Mbyte

6 Mbyte

16 Mbyte

  • ? integrated (for data)

512 kbyte

2 Mbyte

10 Mbyte

16 Mbyte

Load memory

 

 

 

 

  • ? expandable FEPROM, max.

64 Mbyte

64 Mbyte

64 Mbyte

64 Mbyte

  • ? integrated RAM, max.

512 kbyte

512 kbyte

1 Mbyte

1 Mbyte

  • ? expandable RAM, max.

64 Mbyte

64 Mbyte

64 Mbyte

64 Mbyte

CPU processing times

 

 

 

 

for bit operations, typ.

31.25 ns

18.75 ns

12.5 ns

7.5 ns

for word operations, typ.

31.25 ns

18.75 ns

12.5 ns

7.5 ns

for fixed point arithmetic, typ.

31.25 ns

18.75 ns

12.5 ns

7.5 ns

for floating point arithmetic, typ.

62.5 ns

37.5 ns

25 ns

15 ns

Counters, timers and their retentivity

 

 

 

 

S7 counter

 

 

 

 

  • ? Number

2 048

2 048

2 048

2 048

IEC counter

 

 

 

 

  • ? present

Yes

Yes

Yes

Yes

S7 times

 

 

 

 

  • ? Number

2 048

2 048

2 048

2 048

IEC timer

 

 

 

 

  • ? present

Yes

Yes

Yes

Yes

Data areas and their retentivity

 

 

 

 

Flag

 

 

 

 

  • ? Number, max.

8 192 byte

8 192 byte

16 384 byte

16 384 byte

Address area

 

 

 

 

I/O address area

 

 

 

 

  • ? Inputs

8 kbyte

8 kbyte

16 kbyte

16 kbyte

  • ? Outputs

8 kbyte

8 kbyte

16 kbyte

16 kbyte

Process image

 

 

 

 

  • ? Inputs, adjustable

8 kbyte

8 kbyte

16 kbyte

16 kbyte

  • ? Outputs, adjustable

8 kbyte

8 kbyte

16 kbyte

16 kbyte

Time of day

 

 

 

 

Clock

 

 

 

 

  • ? Hardware clock (real-time)

Yes

Yes

Yes

Yes

Operating hours counter

 

 

 

 

  • ? Number

16

16

16

16

Interfaces

 

 

 

 

Number of RS 485 interfaces

2

2

2

2

Number of other interfaces

2; Fiber-optic interface

2; Fiber-optic interface

2; Fiber-optic interface

2; Fiber-optic interface

1. Interface

 

 

 

 

Interface type

Integrated

Integrated

Integrated

Integrated

Physics

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

Functionality

 

 

 

 

  • ? MPI

Yes

Yes

Yes

Yes

  • ? PROFIBUS DP master

Yes

Yes

Yes

Yes

  • ? PROFIBUS DP slave

No

No

No

No

DP master

 

 

 

 

  • ? Number of DP slaves, max.

32

32

32

32

2. Interface

 

 

 

 

Interface type

PROFINET

PROFINET

PROFINET

PROFINET

Physics

Ethernet RJ45

Ethernet RJ45

Ethernet RJ45

Ethernet RJ45

Interface types

 

 

 

 

  • ? Number of ports

2

2

2

2

Functionality

 

 

 

 

  • ? PROFINET IO Controller

Yes

Yes

Yes

Yes

  • ? PROFINET IO Device

No

No

No

No

  • ? PROFINET CBA

No

No

No

No

  • ? PROFIBUS DP master

No

No

No

No

  • ? PROFIBUS DP slave

No

No

No

No

3. Interface

 

 

 

 

Interface type

Integrated

Integrated

Integrated

Integrated

Physics

RS 485 / PROFIBUS

RS 485 / PROFIBUS

RS 485 / PROFIBUS

RS 485 / PROFIBUS

Functionality

 

 

 

 

  • ? PROFIBUS DP master

Yes

Yes

Yes

Yes

  • ? PROFIBUS DP slave

No

No

No

No

DP master

 

 

 

 

  • ? Number of DP slaves, max.

64

96

125

125

4. Interface

 

 

 

 

Interface type

Pluggable synchronization submodule (FO)

Pluggable synchronization submodule (FO)

Pluggable synchronization submodule (FO)

Pluggable synchronization submodule (FO)

Plug-in interface modules

Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

5. Interface

 

 

 

 

Interface type

Pluggable synchronization submodule (FO)

Pluggable synchronization submodule (FO)

Pluggable synchronization submodule (FO)

Pluggable synchronization submodule (FO)

Plug-in interface modules

Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

Isochronous mode

 

 

 

 

Isochronous operation (application synchronized up to terminal)

No

No

No

No

Communication functions

 

 

 

 

PG/OP communication

Yes

Yes

Yes

Yes

Data record routing

Yes

Yes

Yes

Yes

S7 routing

Yes

Yes

Yes

Yes

Global data communication

 

 

 

 

  • ? supported

No

No

No

No

S7 basic communication

 

 

 

 

  • ? supported

No

No

No

No

S7 communication

 

 

 

 

  • ? supported

Yes

Yes

Yes

Yes

S5 compatible communication

 

 

 

 

  • ? supported

Yes; (via CP max. 10 and FC AG_SEND and FC AG_RECV)

Yes; (via CP max. 10 and FC AG_SEND and FC AG_RECV)

Yes; (via CP max. 10 and FC AG_SEND and FC AG_RECV)

Yes; (via CP max. 10 and FC AG_SEND and FC AG_RECV)

Standard communication (FMS)

 

 

 

 

  • ? supported

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Open IE communication

 

 

 

 

  • ? TCP/IP

Yes; via integrated PROFINET interface and loadable FBs

Yes; via integrated PROFINET interface and loadable FBs

Yes; via integrated PROFINET interface and loadable FBs

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

46

62

94

118

  • ? ISO-on-TCP (RFC1006)

Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs

Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs

Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs

Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs

  • Number of connections, max.

46

62

94

118

  • ? UDP

Yes; via integrated PROFINET interface and loadable FBs

Yes; via integrated PROFINET interface and loadable FBs

Yes; via integrated PROFINET interface and loadable FBs

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

46

62

94

118

Web server

 

 

 

 

  • ? supported

No

No

No

No

Number of connections

 

 

 

 

  • ? overall

48

64

96

120

Configuration

 

 

 

 

Know-how protection

 

 

 

 

  • ? User program protection/password protection

Yes

Yes

Yes

Yes

  • ? Block encryption

Yes; With S7 block Privacy

Yes; With S7 block Privacy

Yes; With S7 block Privacy

Yes; With S7 block Privacy

Dimensions

 

 

 

 

Width

50 mm

50 mm

50 mm

50 mm

Height

290 mm

290 mm

290 mm

290 mm

Depth

219 mm

219 mm

219 mm

219 mm

Weights

 

 

 

 

Weight, approx.

995 g

995 g

995 g

995 g


















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ
Êàòàëîã îáîðóäîâàíèÿ 2017
Siemens Industry Catalog Drive Technology Automation Technology Automation Systems Operator control and monitoring systems SIMATIC HMI Identification systems Industrial Communication Introduction Industrial Ethernet PROFINET Introduction Drive Systems Controller Modular controllers SIMATIC S7-1200 SIMATIC S7-1500 SIMATIC S7-300 SIMATIC S7-400 Central processing units Standard CPUs Fail-safe CPUs High-availability CPUs Distributed controllers PC-based controllers Embedded Controller Embedded bundles Communication for SIMATIC S7-1500 System interfacing / SIMATIC S7 / Communication for SIMATIC S7-300 System interfacing / SIMATIC S7 / Communication for SIMATIC S7-400 System interfacing for PG/PC/IPC / Communication for PC-based systems SIMATIC PCS 7 process control systems Distributed I/O Motion Control Systems CNC Controls Operator panels Industrial PC Switching and Protection Devices for Power Distribution Power Monitoring SENTRON Measuring Devices Configuring, Visualizing and Controlling with SIMATIC Configuring, Visualizing and Controlling with SENTRON Industrial Identification Systems Network Components Industrial Controls SITOP power supplies Software and Tools Network management and diagnostics Technology Components PROFIBUS AS-Interface IO-Link Industrial Wireless Communication Industrial Remote Communication Industrial Security Industrial Controls Manufacturing Execution Systems (MES) SIMATIC IT PC-based Automation Process control systems Process instrumentation Process analytics SITOP power supplies Products for specific requirements Energy Building Technologies Low-Voltage Controls and Distribution Safety Systems - Safety Integrated Market-specific solutions Industry Services ... and everything else you need




  © ÎÎÎ "ÑÊ ÝÍÅÐÃÎ" 2007-2022
  (4872) 700-366  skenergo@mail.ru
ßíäåêñ.Ìåòðèêà