SINAMICS SL150- SINAMICS SL150 replaces the SIMOVERT D
- Thyristor?based power unit allows power ratings of up to 36 MVA
- Either an open or star connection
- 2 ? 950 6?pulse parallel connection for high power ratings with 12?pulse line harmonics
Air cooling *) | Supply voltage | Motor voltage | Power |
|---|
(V) | (V) | (MVA) |
|---|
Single 6?pulse connection | Open connection | 1180 | 1700 | 3.2 ... 9.4 | Star connection | 3 ? 950 | 1515 | 2.9 ... 8.4 | 3 ? 1360 | 2190 | 6.3 ... 8.7 | 2 ? 6-pulse parallel connection | Open connection | 2 ? 1180 | 1700 | 10.6 ... 16.9 | Star connection | 6 ? 950 | 1515 | 9.4 ... 15.1 | 6 ? 1360 | 2190 | 11.4 ... 15.7 | 12?pulse parallel connection | Open connection | 2 ? 1180 | 2 ? 1700 | 11.8 ... 18.8 | Star connection | 6 ? 950 | 2 ? 1515 | 10.5 ... 16.8 | 6 ? 1360 | 2 ? 2190 | 12.5 ... 17.4 |
*) Air-cooled, capable of a 200 % overload for up to 60 sec. Water cooling **) | Supply voltage | Motor voltage | Power |
|---|
(V) | (V) | (MVA) |
|---|
12?pulse series connection | Star connection | 2 ? 1310 | 4000 | 12 ... 18 | 2 ? 6?pulse parallel connection | Star connection | 2 ? 2620 | 2 ? 4000 | 24 ... 36 |
**) Water?cooled, capable of a 150 % overload for up to 60 sec.
|
|