Use of the line filters class B shown below allows 230 V SINAMICS V20 converters without an integrated filter to achieve EN 61800?3 Category C1 when used with a screened output cable of 5 m. Note that the 230 V filtered converters of frame sizes FSB and FSC can achieve EN 61800?3 Category C2 when used with a screened output cable of 25 m without an external filter.
Use of the line filters class B shown below allows 400 V SINAMICS V20 converters with or without an integrated filter to achieve EN 61800?3 Category C2 when used with a screened output cable of 25 m.
Selection and ordering data
Rated power
SINAMICS V20
Line filter class B for category C1, shielded motor cable length max. 5 m
kW
hp
Type 6SL3210-...
Frame size
Article No.
200 V ... 240 V 1 AC converters
0.12
0.16
5BB11-2UV1
FSAA
6SL3203-0BB21-8VA0
0.25
0.33
5BB12-5UV1
FSAA
0.37
0.5
5BB13-7UV1
FSAA
0.55
0.75
5BB15-5UV1
FSAB
0.75
1.0
5BB17-5UV1
FSAB
Rated power
SINAMICS V20
Line filter class B for category C2, shielded motor cable length max. 25 m
kW
hp
Type 6SL3210-...
Frame size
Article No.
200 V ... 240 V 1 AC converters
1.1
1.5
5BB21-1 . V0
FSB
–
1.5
2.0
5BB21-5 . V0
FSB
2.2
3.0
5BB22-2 . V0
FSC
3.0
4.0
5BB23-0 . V0
FSC
–
Rated power
SINAMICS V20
Line filter class B for category C2, shielded motor cable length max. 25 m