General information | | |
Product brand name | SICLOCK |
Product type designation | TC100 | TC400 |
Product designation | Central plant clock |
Installation type/mounting | | |
Mounting type | DIN rail 35 mm or 19 inch rack |
Supply voltage | | |
Supply voltage (DC) | 24 V |
Relative negative tolerance | 15 % |
Relative positive tolerance | 20 % |
Mains buffering | | |
| 3 ms |
Input current | | |
Continuous rated current, max. | 0.5 A | 0.7 A |
Operating current of fuse protection at input, slow-blow | 1 A |
Output current | | |
Design of outputs for supply of the antenna | 20 mA to 40 mA at 48 V |
Power | | |
Power consumption, max. | 9 W | 15 W |
Power loss | | |
Power loss, typ. | 6 W | 7.5 W |
Time of day | | |
Design of the inputs | 1x GPS1000 / DCFRS time input 48 V / 40 mA | 2x GPS1000 / DCFRS time input 48 V / 40 mA |
Clock | | |
| 50 µs |
| 1 000 µs |
| 200 ns |
| 0.0001 % |
| 0.000001 % |
| 0.0004 % |
| 50 µs |
Digital outputs | | |
Relay outputs | | |
| |
| 1 |
| 1 |
Switching capacity of contacts | | |
| 0.06 A |
Interfaces | | |
Number of industrial Ethernet interfaces | 1 | 4 |
Number of 20 mA interfaces (TTY) | |
| | 2 |
Number of RS 422 interfaces | |
| | 1 |
Industrial Ethernet | | |
| 10 Mbit/s |
| 100 Mbit/s |
Interface types | | |
RJ 45 (Ethernet) | | |
| Yes |
Protocols | | |
Bus protocol/transmission protocol | (S)NTP, DCF77 | (S)NTP, DCF77, pulses, cycles, message frames |
Potential separation | | |
between Ethernet and electronics | Yes |
Degree and class of protection | | |
IP degree of protection | IP20 |
Equipment protection class | III (according to EN 60536) |
Standards, approvals, certificates | | |
Standard for EMC | EN 55022 Class A, FCC Class, EN 55024 |
Standard for ambient influences | |
| EN 60721-3-3 class 3KS |
| EN 60721-3-2 class 2K4 |
| IEC 60068-2-78, IEC 60068-2-30 |
| IEC 60068-2-78, IEC 60068-2-30 |
Ambient conditions | | |
Ambient temperature during operation | | |
| 0 °C |
| 55 °C |
| 10 °C |
Ambient temperature during storage/transportation | | |
| -40 °C |
| 70 °C |
| 20 °C |
| -40 °C |
| 70 °C |
Air pressure acc. to IEC 60068-2-13 | | |
| 795 hPa |
| 1 080 hPa |
| -1 000 m |
| 2 000 m |
Relative humidity | | |
| 10 % |
| 95 % |
| 10 % |
| 95 % |
Mechanics/material | | |
Service life | | |
| 10 y | 12 y |
| 10 y | 12 y |
| 6 y |
Dimensions | | |
Width | 180 mm |
Height | 89 mm |
Depth | 47 mm |