Recommended line-side power components Selection and ordering data The following tables list recommendations for additional line-side components, such as fuses and circuit breakers. The values in the table take into account the overload capability of the inverter.
Notes for use in compliance with IEC standards:
3NA3 or 3NE1 fuses and 3RV motor starter protectors or 3VL circuit breakers are recommended for European countries.
Notes for use in compliance with UL regulations:
UL-listed fuses Class J, T, CC, G or CF (with rated voltage 250 V AC or 600 V AC) or 3NE1 (UL-compliant – corresponds to RU) are required for North America.
Short Circuit Current Rating (SCCR) according to UL Applies to industrial control panel installations to NEC Article 409 or UL 508A/508C
PM230: 65 kA (variants with IP20 degree of protection) PM240-2: 100 kA (200 V versions), 100 kA (400 V versions), 65 kA (690 V versions) (the value depends on the fuses and circuit breakers used) PM240: 65 kA PM250: 40 kA (frame size FSC), 42 kA (frame sizes FSD to FSF) Notes regarding installations in Canada:
Overvoltage protection devices in accordance with overvoltage category III and with the following ratings must be connected on the line side of the inverter:
Rated voltage 480 V (phase-phase) and 480 V (phase-ground) Voltage limit 4 kV (phase-phase) and 6 kV (phase-ground) All overvoltage protection devices used must comply with Canadian standards for industrial installations.
Further information, particularly regarding use in accordance with UL guidelines, is available athttps://support.industry.siemens.com/cs/document/109479152
Additional information about the line-side power components can be found in Catalogs LV 10, IC 10 and IC 10 AO as well as the Industry Mall.
Rated power 1)
PM230 Power Module degree of protection IP20 standard variant
IEC-compliant
UL/cUL-compliant
Fuse
Fuse
Fuse type Rated voltage 600 V AC
Type
Current
Type 3NE1 (RU)
Type 3NE1 (RU)
Current
kW
hp
6SL3210-...
Frame size
A
Article No.
Article No.
Class
A
380 ... 480 V 3 AC
0.37
0.5
1NE11-3 . L1
FSA
16
3NE1813-0
3NE1813-0
J
15
0.55
0.75
1NE11-7 . L1
FSA
16
3NE1813-0
3NE1813-0
J
15
0.75
1
1NE12-2 . L1
FSA
16
3NE1813-0
3NE1813-0
J
15
1.1
1.5
1NE13-1 . L1
FSA
16
3NE1813-0
3NE1813-0
J
15
1.5
2
1NE14-1 . L1
FSA
16
3NE1813-0
3NE1813-0
J
15
2.2
3
1NE15-8 . L1
FSA
16
3NE1813-0
3NE1813-0
J
15
3
4
1NE17-7 . L1
FSA
16
3NE1813-0
3NE1813-0
J
15
4
5
1NE21-0 . L1
FSB
25
3NE1815-0
3NE1815-0
J
25
5.5
7.5
1NE21-3 . L1
FSB
25
3NE1815-0
3NE1815-0
J
25
7.5
10
1NE21-8 . L1
FSB
25
3NE1815-0
3NE1815-0
J
25
11
15
1NE22-6 . L1
FSC
50
3NE1817-0
3NE1817-0
J
50
15
20
1NE23-2 . L1
FSC
50
3NE1817-0
3NE1817-0
J
50
18.5
25
1NE23-8 . L1
FSC
50
3NE1817-0
3NE1817-0
J
50
22
30
1NE24-5 . L0
FSD
63
3NE1818-0
3NE1818-0
–
–
30
40
1NE26-0 . L0
FSD
80
3NE1820-0
3NE1820-0
–
–
37
50
1NE27-5 . L0
FSE
100
3NE1021-0
3NE1021-0
–
–
45
60
1NE28-8 . L0
FSE
125
3NE1022-0
3NE1022-0
–
–
55
75
1NE31-1 . L0
FSF
160
3NE1224-0
3NE1224-0
–
–
75
100
1NE31-5 . L0
FSF
200
3NE1225-0
3NE1225-0
–
–
1) Rated power based on the rated output current I rated . The rated output current I rated is based on the duty cycle for low overload (LO).
Rated power 1)
PM230 Power Module degree of protection IP20 push-through variant
IEC-compliant
UL/cUL-compliant
Fuse
Fuse
Fuse type Rated voltage 600 V AC
Type
Current
Type 3NE1 (RU)
Type 3NE1 (RU)
Current
kW
hp
6SL3211-...
Frame size
A
Article No.
Article No.
Class
A
380 ... 480 V 3 AC
3
4
1NE17-7 . L1
FSA
16
3NE1813-0
3NE1813-0
J
15
7.5
10
1NE21-8 . L1
FSB
25
3NE1815-0
3NE1815-0
J
25
18.5
25
1NE23-8 . L1
FSC
50
3NE1817-0
3NE1817-0
J
50
1) Rated power based on the rated output current I rated . The rated output current I rated is based on the duty cycle for low overload (LO).
Rated power 1)
PM240-2 Power Module standard variant
IEC-compliant
UL/cUL-compliant
Fuse
Circuit breaker
Fuse type Rated voltage 250 V AC or 600 V AC
Type
Current
Current
kW
hp
6SL3210-...
Frame size
A
Article No.
Article No.
Class
A
200 ... 240 V 1 AC/3 AC
0.55
0.75
1PB13-0 . L0
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
15
0.75
1
1PB13-8 . L0
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
15
1.1
1.5
1PB15-5 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
1.5
2
1PB17-4 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
2.2
3
1PB21-0 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
3
4
1PB21-4 . L0
FSC
50
3NA3820
3RV1031-4HA10
J, T, CC, G, CF
50
4
5
1PB21-8 . L0
FSC
50
3NA3820
3RV1031-4HA10
J, T, CC, G, CF
50
200 ... 240 V 3 AC
5.5
7.5
1PC22-2 . L0
FSC
50
3NA3820
3RV1031-4HA10
J, T, CC, G, CF
50
7.5
10
1PC22-8 . L0
FSC
50
3NA3820
3RV1031-4HA10
J, T, CC, G, CF
50
11
15
1PC24-2UL0
FSD
63
3NE1818-0
3RV1041-4JA10
J
60
15
20
1PC25-4UL0
FSD
80
3NE1820-0
3RV1041-4KA10
J
70
18.5
25
1PC26-8UL0
FSD
100
3NE1021-0
3RV1041-4LA10
J
90
22
30
1PC28-0UL0
FSE
100
3NE1021-0
3VL1712-2DD33-.... *)
J
100
30
40
1PC31-1UL0
FSE
160
3NE1224-0
3VL1716-2DD33-.... *)
J
150
37
50
1PC31-3UL0
FSF
200
3NE1225-0
3VL3720-3DC33-.... *)
J
175
45
60
1PC31-6UL0
FSF
200
3NE1225-0
3VL3720-3DC33-.... *)
J
200
55
75
1PC31-8UL0
FSF
250
3NE1227-0
3VL3725-3DC33-.... *)
J
225
380 ... 480 V 3 AC
0.55
0.75
1PE11-8 . L1
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
10
0.75
1
1PE12-3 . L1
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
10
1.1
1.5
1PE13-2 . L1
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
15
1.5
2
1PE14-3 . L1
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
20
2.2
3
1PE16-1 . L1
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
30
3
4
1PE18-0 . L1
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
30
4
5
1PE21-1 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
5.5
7.5
1PE21-4 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
7.5
10
1PE21-8 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
11
15
1PE22-7 . L0
FSC
50
3NA3820
3RV1031-4HA10
J, T, CC, G, CF
50
15
20
1PE23-3 . L0
FSC
50
3NA3820
3RV1031-4HA10
J, T, CC, G, CF
50
18.5
25
1PE23-8 . L0
FSD
63
3NE1818-0
3RV1041-4JA10
J
60
22
30
1PE24-5 . L0
FSD
80
3NE1820-0
3RV1041-4KA10
J
70
30
40
1PE26-0 . L0
FSD
100
3NE1021-0
3RV1041-4LA10
J
90
37
50
1PE27-5 . L0
FSD
100
3NE1021-0
3RV1041-4MA10
J
100
45
60
1PE28-8 . L0
FSE
125
3NE1022-0
3VL1712-2DD33-.... *)
J
125
55
75
1PE31-1 . L0
FSE
160
3NE1224-0
3VL1716-2DD33-.... *)
J
150
75
100
1PE31-5 . L0
FSF
200
3NE1225-0
3VL3720-3DC33-.... *)
J
200
90
125
1PE31-8 . L0
FSF
250
3NE1227-0
3VL3725-3DC33-.... *)
J
225
110
150
1PE32-1 . L0
FSF
315
3NE1230-0
3VL4731-3DC36-.... *)
J
300
132
200
1PE32-5 . L0
FSF
350
3NE1331-0
3VL4740-3DC36-.... *)
J
350
500 ... 690 V 3 AC
11
10
1PH21-4 . L0
FSD
25
3NE1815-0
3RV1042-4BA10
J
20
15
15
1PH22-0 . L0
FSD
25
3NE1815-0
3RV1042-4EA10
J
25
18.5
20
1PH22-3 . L0
FSD
35
3NE1803-0
3RV1042-4EA10
J
30
22
25
1PH22-7 . L0
FSD
35
3NE1803-0
3VL1704-2DD33-.... *)
J
35
30
30
1PH23-5 . L0
FSD
50
3NE1817-0
3VL1705-2DD33-.... *)
J
45
37
40
1PH24-2 . L0
FSD
63
3NE1818-0
3VL1706-2DD33-.... *)
J
60
45
50
1PH25-2 . L0
FSE
80
3NE1820-0
3VL1708-2DD33-.... *)
J
80
55
60
1PH26-2 . L0
FSE
80
3NE1820-0
3VL1710-2DD33-.... *)
J
80
75
75
1PH28-0 . L0
FSF
100
3NE1021-0
3VL1712-2DD33-.... *)
J
100
90
100
1PH31-0 . L0
FSF
125
3NE1022-0
3VL1712-2DD33-.... *)
J
125
110
100
1PH31-2 . L0
FSF
160
3NE1224-0
3VL1716-2DD33-.... *)
J
150
132
125
1PH31-4 . L0
FSF
200
3NE1225-0
3VL3720-3DC33-.... *)
J
200
1) Rated power based on the rated output current I rated . The rated output current I rated is based on the duty cycle for low overload (LO).
*) See Catalog LV 10 for Article No. supplements.
Rated power 1)
PM240?2 Power Module push-through variant
IEC-compliant
UL/cUL-compliant
Fuse
Circuit breaker
Fuse type Rated voltage 250 V AC or 600 V AC
Type
Current
Current
kW
hp
6SL3211-...
Frame size
A
Article No.
Article No.
Class
A
200 ... 240 V 1 AC/3 AC
0.75
1
1PB13-8 . L0
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
15
2.2
3
1PB21-0 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
4
5
1PB21-8 . L0
FSC
50
3NA3820
3RV1031-4HA10
J, T, CC, G, CF
50
380 ... 480 V 3 AC
3
4
1PE18-0 . L1
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
30
7.5
10
1PE21-8 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
15
20
1PE23-3 . L0
FSC
50
3NA3820
3RV1031-4HA10
J, T, CC, G, CF
50
1) Rated power based on the rated output current I rated . The rated output current I rated is based on the duty cycle for low overload (LO).
Rated power 1)
PM240 Power Module
IEC-compliant
UL/cUL-compliant
Fuse
Circuit breaker
Fuse
Fuse type Rated voltage 600 V AC
Type
Current
Type 3NA3
Type 3NE1 (RU)
Current
kW
hp
6SL3224-...
Frame size
A
Article No.
Article No.
Article No.
Class
A
380 ... 480 V 3 AC
160
250
0XE41-3UA0
FSGX
355
3NA3254
3VL4740-.DC36-.... *)
3NE1333-2
–
–
200
300
0XE41-6UA0
FSGX
400
3NA3260
3VL5750-.DC36-.... *)
3NE1333-2
–
–
250
400
0XE42-0UA0
FSGX
630
3NA3372
3VL5750-.DC36-.... *)
3NE1436-2
–
–
1) Rated power based on the rated output current I rated . The rated output current I rated is based on the duty cycle for low overload (LO).
*) See Catalog LV 10 for Article No. supplements.
Rated power 1)
PM250 Power Module
IEC-compliant
UL/cUL-compliant
Fuse
Circuit breaker
Fuse
Fuse type Rated voltage 600 V AC
Type
Current
Type 3NA3
Type 3NE1 (RU)
Current
kW
hp
6SL3225-...
Frame size
A
Article No.
Article No.
Article No.
Class
A
380 ... 480 V 3 AC
7.5
10
0BE25-5AA1
FSC
20
3NA3807
3RV1031-4EA10
–
K5 2)
50
11
15
0BE27-5AA1
FSC
32
3NA3812
3RV1031-4FA10
–
K5 2)
50
15
20
0BE31-1AA1
FSC
35
3NA3814
3RV1031-4HA10
–
K5 2)
50
18.5
25
0BE31-5UA0
FSD
50
3NA3820
3RV1042-4KA10
–
–
–
0BE31-5AA0
3NE1817-0
–
–
22
30
0BE31-8UA0
FSD
63
3NA3822
3RV1042-4KA10
–
–
–
0BE31-8AA0
3NE1818-0
–
–
30
40
0BE32-2UA0
FSD
80
3NA3824
3RV1042-4MA10
–
–
–
0BE32-2AA0
3NE1820-0
–
–
37
50
0BE33-0UA0
FSE
100
3NA3830
3VL1712-.DD33-.... *)
–
–
–
0BE33-0AA0
3NE1021-0
–
–
45
60
0BE33-7UA0
FSE
125
3NA3832
3VL1716-.DD33-.... *)
–
–
–
0BE33-7AA0
3NE1022-0
–
–
55
75
0BE34-5UA0
FSF
160
3NA3836
3VL3720-.DC36-.... *)
–
–
–
0BE34-5AA0
3NE1224-0
J
150
75
100
0BE35-5UA0
FSF
200
3NA3140
3VL3725-.DC36-.... *)
–
–
–
0BE35-5AA0
3NE1225-0
J
200
90
125
0BE37-5UA0
FSF
250
3NA3144
3VL4731-.DC36-.... *)
–
–
–
0BE37-5AA0
3NE1227-0
J
250
1) Rated power based on the rated output current I rated . The rated output current I rated is based on the duty cycle for low overload (LO).
2) Any UL-listed fuse may be used, e.g. Class K5, Class J, etc.
*) See Catalog LV 10 for Article No. supplements.