S7-400F/FH meet the following safety requirements:
Mode of operationThe safety functions of the S7-400F/FH are contained in the F program of the CPU and in the safety-related signal modules (F-modules). The signal modules monitor output and input signals by means of discrepancy analyses and test signal injections. The CPU checks the proper operation of the controller with regular self-tests, command tests, and logical and chronological program execution checks. In addition, the I/O is checked by means of sign-of-life requests. If a fault is diagnosed in the system, the system is brought to a safe state. F-Runtime license The S7 F-Runtime license must be loaded onto the CPU S7-400H to operate the S7-400F/FH. One license is required for each S7-400F/FH. ProgrammingThe S7-400F/FH is programmed in the same way as the other SIMATIC S7 systems. The user program for non-safety-related plant sections is created with time-tested programming tools such as STEP 7. S7 F Systems option package The option package "S7 F Systems" is required for programming the safety-related program sections. The package contains all the necessary functions and blocks for creating the F program. The following software packages must be loaded onto the PG/PC for S7 F Systems to run:
For the F program with the safety functions, special function blocks from the F library are called up with CFC and interconnected. The CFC simplifies the configuring, programming and the acceptance testing of the system. Programmers can concentrate fully on the safety-related application without having to use additional tools. |
| Каталог 2018 | Каталог 2017 | Каталог 2016 | Каталог 2015 | Каталог 2014 | Каталог 2013 | Каталог 2012 | Сертификат | Контакты | Карта сайта | Поиск |