General information | | | |
Product designation | HCS716I BGT swivel frame | HCS716I BGT subframe without flange | HCS716I BGT subframe narrow version |
Installation type/mounting | | | |
Mounting type | in a hinged frame | Control cabinet backplane |
Type of ventilation | Self ventilation or forced ventilation |
Supply voltage | | | |
Rated value (AC) | 230 V |
Relative negative tolerance | 18 % |
Relative positive tolerance | 15 % |
Line frequency | | | |
| 50 Hz |
| 60 Hz |
| 5 % |
Mains buffering | | | |
| 20 ms |
| 1 s |
Resistance thermometer (RTD) | | | |
| Connector, 2-pole |
| 1x (0.2 ... 2.5 mm?) |
| 1x (0.25 ... 2.5 mm?) |
| 24 ... 12 |
Power | | | |
Active power input | 15 W |
Hardware configuration | | | |
Type of power output connectable | LA716 / LA716I / LA716I HP |
Power capacity per rack with fan, max. | 176 kW | 59 kW |
Power capacity per rack without fan, max. | 67 kW | 22 kW |
Slots | | | |
| 12 | 4 |
Interfaces | | | |
Interfaces/bus type | PROFIBUS DP |
PROFIBUS DP | | | |
| 12 Mbit/s |
| 9-pin sub D socket |
Protocols | | | |
PROFIBUS DP | Yes |
Interrupts/diagnostics/status information | | | |
Number of status displays | 2 |
LED status display | LED green = status indicator, LED red = fault indicator |
Isolation | | | |
Overvoltage category | III |
EMC | | | |
EMC interference emission | in accordance with EN 61000-6-4:2007 + A1:2011 |
Electrostatic discharge acc. to IEC 61000-4-2 | 4 kV contact discharge / 8 kV air discharge |
Field-related interference acc. to IEC 61000-4-3 | 10 V/m (80 ... 1 000 MHz), 3 V/m (1.4 ... 2.0 GHz), 1 V/m (2.0 ... 2.7 GHz) |
Conducted interference due to burst acc. to IEC 61000-4-4 | 2 kV voltage supply cables / 2 kV signal cables |
Conducted interference due to surge acc. to IEC 61000-4-5 | On supply lines: 1 kV symmetrical, 2 kV asymmetrical, PROFIBUS cable asymmetrical 1 kV |
Conducted interference due to high-frequency radiation acc. to IEC 61000-4-6 | 10 V in the frequency range 0.15 ... 80 MHz, Mmdulation 80 % AM at 1 kHz, evaluation criterion A |
Degree and class of protection | | | |
IP degree of protection | IP00 |
Standards, approvals, certificates | | | |
Certificate of suitability | CE, KCC |
Degree of pollution | 2 |
Device tag according to DIN EN 81346-2 | K |
Ambient conditions | | | |
Ambient temperature during operation | | | |
| 0 °C |
| 55 °C |
Ambient temperature during storage/transportation | | | |
| -40 °C |
| 70 °C |
| -40 °C |
| 70 °C |
Air pressure acc. to IEC 60068-2-13 | | | |
| 860 hPa |
| 1 080 hPa |
| 660 hPa |
| 1 080 hPa |
| 2 000 m |
Relative humidity | | | |
| 95 % |
Vibrations | | | |
| 10 ... 58 Hz / 0.15 mm, 58 ... 150 Hz / 1 g |
| 5 ... 9 Hz / 3.5 mm, 9 ... 500 Hz / 1 g |
Shock testing | | | |
| 15 g / 11 ms / 3 shocks/axis |
| 25 g / 6 ms / 1 000 shocks/axis |
Dimensions | | | |
Width | 483 mm | 510 mm | 202.7 mm |
Height | 265.5 mm | 310 mm | 309.5 mm |
Depth | 350 mm | 330 mm | 287 mm |