General information | |
Engineering with | |
| STEP 7 V5.5 or higher |
Supply voltage | |
Rated value (DC) | 24 V |
Power loss | |
Power loss, typ. | 5.5 W |
Memory | |
Work memory | |
| 192 kbyte |
| 64 kbyte |
Load memory | |
| 8 Mbyte |
CPU processing times | |
for bit operations, typ. | 0.06 µs |
for word operations, typ. | 0.12 µs |
for fixed point arithmetic, typ. | 0.16 µs |
for floating point arithmetic, typ. | 0.59 µs |
Counters, timers and their retentivity | |
S7 counter | |
| 256 |
IEC counter | |
| Yes |
S7 times | |
| 256 |
IEC timer | |
| Yes |
Data areas and their retentivity | |
Flag | |
| 256 byte |
Address area | |
I/O address area | |
| 2 048 byte |
| 2 048 byte |
Process image | |
| 2 048 byte |
| 2 048 byte |
Time of day | |
Clock | |
| Yes |
Operating hours counter | |
| 1 |
1. Interface | |
Interface type | PROFINET |
Physics | Ethernet |
Interface types | |
| 3; RJ45 |
Functionality | |
| No |
| Yes; Also simultaneously with IO-Device functionality |
| Yes; Also simultaneously with IO Controller functionality |
| Yes |
| No |
| No |
| No |
PROFINET IO Controller | |
Services | |
| 128 |
| 64 |
| 128 |
| 128 |
2. Interface | |
Interface type | External interface via master module 6ES7138-4HA00-0AB0 |
Physics | RS 485 |
Functionality | |
| No |
| No |
| No |
| No |
| Yes |
| No |
DP master | |
| 32; Per station |
Isochronous mode | |
Isochronous operation (application synchronized up to terminal) | No |
Communication functions | |
PG/OP communication | Yes |
Data record routing | Yes; With DP master module |
Global data communication | |
| No |
S7 basic communication | |
| Yes; I blocks |
S7 communication | |
| Yes |
Open IE communication | |
| Yes; via integrated PROFINET interface and loadable FBs |
| 8 |
| Yes; via integrated PROFINET interface and loadable FBs |
| 8 |
| Yes; via integrated PROFINET interface and loadable FBs |
| 8 |
Web server | |
| Yes |
Number of connections | |
| 12 |
Ambient conditions | |
Ambient temperature during operation | |
| -40 °C; = Tmin |
| 70 °C; = Tmax |
Extended ambient conditions | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
| -25 °C |
Relative humidity | |
| 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) |
Resistance | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Programming | |
Programming language | |
| Yes |
| Yes |
| Yes |
| Yes; Optional |
| Yes; Optional |
| Yes; Optional |
| Yes; Optional |
Know-how protection | |
| Yes |
| Yes; With S7 block Privacy |
Dimensions | |
Width | 120 mm; DP master module: 35 mm |
Height | 119.5 mm |
Depth | 75 mm |
Weights | |
Weight, approx. | 320 g; DP master module: Approx. 100 g |