WinCC Logging
 

WinCC Logging for Runtime Advanced

 

The values specified are maximum values

Number of logs

100

Archivable data

Process values, alarms

Cyclical trigger for archiving process values (variables)

1 s

Max. number of entries per log
(incl. sequence log)

500.000 1)

Log types

Circular logs,
sequence logs (max. 400 per log)

Data storage format

CSV (Comma Separated Variable),
RDB (Runtime Data Base),
Microsoft SQL database (database not included in scope of delivery)



1) Dependent on memory medium used

 

WinCC Logging for Runtime Professional

 

The values specified are maximum values

Number of logs per single-user station/server

100

Archivable data

Process values, alarms

Measured values per second, max.

Server/single-user station: 5 000 per sec.

Log tags per single-user station/server

8.000 2)

Log types

Circular log with and without long-term logging

Data storage format

Microsoft SQL 2008 database



2) Dependent on the Logging PowerPack used for the log tags. 500 log tags are contained in the basis version.