Supply voltage | | |
Rated value (DC) | 24 V | 24 V |
Reverse polarity protection | Yes | Yes |
Input current | | |
from supply voltage L+, max. | 120 mA | 80 mA; Typ. 20 mA |
from backplane bus 3.3 V DC, max. | 10 mA | 10 mA |
Power loss | | |
Power loss, typ. | 1.2 W | 1.2 W |
Memory | | |
Standard blocks | 5 100 byte; S_SEND 2700, S_RCV 2400, S_XON 2600, S_RTS 2600, S_V24 2700, S_VSTAT 1800, S_VSET 1800 | 11 100 byte; Modbus: S_SEND 2700, S_RCV 2400, S_MODB 6000; USI: S_SEND 2700, S_RCV 2400, S_USST 1900, S_USSR 2600, S_USSI 1500 |
Interfaces | | |
Number of interfaces | 1 | 1 |
Interface physics, RS 232C (V.24) | Yes; RS 232C signals: 8 (TxD, RxD, RTS, CTS, DTR, DSR, DCD, PE) | Yes; RS 232C signals: 8 (TxD, RxD, RTS, CTS, DTR, DSR, DCD, PE) |
Interface (physical) RS 422/485 (X.27) | Yes; RS-422 signals: 5 (TxD(A), RxD(A), TxD(B), RxD(B), PE); RS-485 signals: 3 (R/T(A), R/T(B), PE) | Yes; RS-422 signals: 5 (TxD(A), RxD(A), TxD(B), RxD(B), PE); RS-485 signals: 3 (R/T(A), R/T(B), PE) |
RS 232, cable length shielded, max. | 15 m | 15 m |
RS 422/RS 485, cable length shielded, max. | 1 200 m | 1 200 m |
Point-to-point | | |
Integrated protocol driver | | |
| Yes | |
| Yes | |
| | Yes |
| | 115.2 kbit/s; half duplex: 110, 300, 600, 1 200, 2 400, 4 800, 9 600, 19 200, 38 400, 57 600, 76 800, 115 200 bps |
| | Yes |
| | 115.2 kbit/s; half duplex: 110, 300, 600, 1 200, 2 400, 4 800, 9 600, 19 200, 38 400, 57 600, 76 800, 115 200 bps |
Transmission rate, RS 422/485 | | |
| 115.2 kbit/s; half duplex: 110, 300, 600, 1 200, 2 400, 4 800, 9 600, 19 200, 38 400, 57 600, 76 800, 115 200 bps | |
| 115.2 kbit/s; Full duplex: 110, 300, 600, 1 200, 2 400, 4 800, 9 600, 19 200, 38 400, 57 600, 76 800, 115 200 bps | |
Transmission speed, RS 232 | | |
| 115.2 kbit/s; half duplex: 110, 300, 600, 1 200, 2 400, 4 800, 9 600, 19 200, 38 400, 57 600, 76 800, 115 200 bps | |
| 115.2 kbit/s; Full duplex: 110, 300, 600, 1 200, 2 400, 4 800, 9 600, 19 200, 38 400, 57 600, 76 800, 115 200 bps | |
Character frame (adjustable) | | |
| 7 or 8 | 8 |
| 1 or 2 | 1 or 2 (USS only 1) |
| 10 | 10 or 11 (USS only 11 bits) |
| none, odd, even, any | none, odd, even (USI even only) |
Data quantity per PLC sampling cycle | | |
| 32 byte; with IM151-1 Standard as of 6ES7 151-1AA04-0AB0; with IM151-1 High Feature as of 6ES7 151-1BA01-0AB0; otherwise 8 bytes | 32 byte; with IM151-1 Standard as of 6ES7 151-1AA04-0AB0; with IM151-1 High Feature as of 6ES7 151-1BA01-0AB0; otherwise 8 bytes |
| 32 byte; with IM151-1 Standard as of 6ES7 151-1AA04-0AB0; with IM151-1 High Feature as of 6ES7 151-1BA01-0AB0; otherwise 8 bytes | 32 byte; with IM151-1 Standard as of 6ES7 151-1AA04-0AB0; with IM151-1 High Feature as of 6ES7 151-1BA01-0AB0; otherwise 8 bytes |
Interrupts/diagnostics/status information | | |
Diagnostics indication LED | | |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
Potential separation | | |
Potential separation interface | | |
| Yes | Yes |
| Yes | Yes |
Ambient conditions | | |
Ambient temperature during operation | | |
| -25 °C; = Tmin | -25 °C; = Tmin |
| 70 °C; = Tmax | 70 °C; = Tmax |
Ambient temperature during storage/transportation | | |
| -40 °C | -40 °C |
| 70 °C | 70 °C |
Extended ambient conditions | | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | | |
| 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) | 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) |
Resistance | | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Dimensions | | |
Width | 15 mm | 15 mm |
Height | 81 mm | 81 mm |
Depth | 52 mm | 52 mm |
Weights | | |
Weight, approx. | 50 g | 50 g |