Input | |
Measured variable | Absolute pressure |
Span (fully adjustable) or nominal measuring range, max. operating pressure (in accordance with 97/23/EC Pressure Equipment Directive) and max. test pressure (pursuant to DIN 16086) | HART | PROFIBUS PA and FOUNDATION Fieldbus | |
Span | Nominal measuring range | Max. perm. operating pressure MAWP (PS) |
8.3 ... 250 mbar 0.83 ... 25 kPa a 3 ... 100 inH2O a | 250 mbar 25 kPa a 100 inH2O a | 32 bar a 3.2 MPa a 464 psia |
43 ... 1300 mbar 4.3 ... 130 kPa a 17 ... 525 inH2O a | 1300 mbar 130 kPa a 525 inH2O a | 32 bar a 3.2 MPa a 464 psia |
160 ... 5000 mbar a 16 ... 500 kPa a 2.32 ... 72.52 psia | 5000 mbar a 500 kPa a 72.52 psia | 32 bar a 3.2 MPa a 464 psia |
1 ... 30 bar a 0.1 .... 3 MPa a 14.5 ... 435 psia | 30 bar a 3 MPa a 435 psia | 160 bar a 16 MPa a 2320 psia |
5.3 ... 100 bar a 0.5 ... 10 MPa 76.9 ... 1450 psia | 100 bar a 10 MPa 1450 psia | 160 bar a 16 MPa a 2320 psia |
Low measuring limit | |
- Measuring cell with silicone oil filling
| 0 mbar a/0 kPa a/0 psia |
- Measuring cell with inert liquid
| |
- for process temperature -20 °C < ? ? +60 °C
(-4 °F < ? ? +140 °F)
| 30 mbar a/3 kPa a/0.44 psia |
- for process temperature 60 °C < ? ? +100 °C (max. 85 °C for measuring cell 30 bar) (140 °F < ? ? +212 °C (max. 185 °C for measuring cell 435 psi))
| 30 mbar a + 20 mbar a . ( ? - 60 °C)/°C 3 kPa a + 2 kPa a . ( ? - 60 °C)/°C 0.44 psi a + 0.29 psi a . ( ? - 108 °F)/°F |
Upper measuring limit | 100% of the max. measuring span (for oxygen measurement max. 100 bar/10 MPa/ 1450 psi and 60 °C ambient temperature/process temperature) |
Start of scale | Between the measuring limits (continuously adjustable) |
Output | HART | PROFIBUS PA/FOUNDATION Fieldbus |
Output signal | 4 ... 20 mA | Digital PROFIBUS PA and FOUNDATION Fieldbus signal |
- Lower limit (fully adjustable)
| 3.55 mA, factory preset to 3.84 mA | - |
- Upper limit (fully adjustable)
| 23 mA, factory preset to 20.5 mA or optionally set to 22.0 mA | - |
Load | | |
| RB ? (UH - 10.5 V)/0.023 A in ?, UH: Power supply in V | - |
| RB = 230 ... 500 ? (SIMATIC PDM) or RB = 230 ... 1100 ? (HART Communicator) | - |
Physical bus | - | IEC 61158-2 |
Protection against polarity reversal | Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage. |
Electrical damping (step width 0.1 s) | Set to 2 s (0 ... 100 s) |
Measuring accuracy | According to IEC 60770-1 |
Reference conditions | - Rising characteristic curve
- Start of scale 0 bar
- Seal diaphragm stainless steel
- Silicone oil filling
- Room temperature 25 °C (77 °F)
|
Measuring span ratio r (spread, Turn-Down) | r = maximum measuring span/set measuring span or nominal measuring range |
Error in measurement at limit setting including hysteresis and reproducibility | |
| |
| ? 0.1 % |
| ? 0.2 % |
Influence of ambient temperature (in percent per 28 °C (50 °F)) | |
- 250 mbar a/25 kPa a/3.6 psia
| ? (0.15 · r + 0.1) % |
- 1300 mbar a/130 kPa a/18.8 psia
5 bar a/500 kPa a/72.5 psia 30 bar a/3000 kPa a/435 psia 100 bar a/10 MPa a/1450 psia
| ? (0.08 · r + 0.16) % |
Long-term stability (temperature change ±30 °C (±54 °F)) | ? (0.25 · r) % in 5 years |
Effect of mounting position (in pressure per change of angle) | ? 0.7 mbar/0.07 kPa/0.001015 psi per 10° incline (zero point correction is possible with position error compensation) |
Effect of auxiliary power (in percent per voltage change) | 0.005 % per 1 V |
Measured-value resolution for PROFIBUS PA and FOUNDATION Fieldbus | 3 · 10-5 of nominal measuring range |
Rated conditions | |
Degree of protection according to IEC 60529 | IP66 (optional IP66/IP68), NEMA 4X |
Temperature of medium | |
- Measuring cell with silicone oil filling
| -40 ... +100 °C (-40 ... +212 °F) -20 ... +100 °C (-4 ... +212 °F) with 30 bar measuring cell |
- Measuring cell with inert fill fluid
| -20 ... +100 °C (-4 ... +212 °F) |
- In conjunction with dust explosion protection
| -20 ... +60 °C (-4 ... +140 °F) |
Ambient conditions | |
| |
- Transmitter
(with 4-wire connection, observe temperature values of supplementary 4-wire electronics)
| -40 ... +85 °C (-40 ... +185 °F) |
| -30 ... +85 °C (-22 ... +185 °F) |
| -50 ... +85 °C (-58 ... +185 °F) |
| |
| Relative humidity 0 ... 100 % Condensation permissible, suitable for use in the tropics |
- Electromagnetic compatibility
| |
- Emitted interference and interference immunity
| According to IEC 61326 and NAMUR NE 21 |
Design | |
Weight (without options) | ? 4.5 kg (? 9.9 lb) |
Enclosure material | Low-copper die-cast aluminum, GD-AlSi 12 or stainless steel precision casting, mat. no. 1.4408 |
Wetted parts materials | |
| Stainless steel, mat. no. 1.4404/316L or Hastelloy C276, mat. no. 2.4819, Monel, mat. no. 2.4360, tantalum or gold |
- Process flanges and sealing screw
| Stainless steel, mat. no. 1.4408, Hastelloy C4, mat. no. 2.4602 or Monel, mat. no. 2.4360 |
| FPM (Viton) or optionally: PTFE, FEP, FEPM and NBR |
Measuring cell filling | Silicone oil or inert fill fluid (for oxygen measurement, maximum pressure 100 bar (1450 psi) at 60 °C (140 °F)) |
Process connection | ?-18 NPT and flange connection with mounting thread M10 to DIN 19213 or 7/16-20 UNF to IEC 61518 |
Material of mounting bracket | |
| Sheet-steel, mat. no. 1.0330, chrome-plated |
| Sheet stainless steel, mat. no. 1.4301 (SS 304) |
Power supply UH | HART | PROFIBUS PA/FOUNDATION Fieldbus |
Terminal voltage on transmitter | 10.5 ... 45 V DC 10.5 ... 30 V DC in intrinsically-safe mode | - |
Auxiliary power | | Bus-powered |
Separate supply voltage | - | Not necessary |
Bus voltage | | |
| - | 9 ... 32 V |
- With intrinsically-safe operation
| - | 9 ... 24 V |
Current consumption | | |
| - | 12.5 mA |
- Start-up current ? basic current
| - | Yes |
- Max. current in event of fault
| - | 15.5 mA |
Fault disconnection electronics (FDE) available | - | Yes |
Certificates and approvals | HART | PROFIBUS PA/FOUNDATION Fieldbus |
Classification according to pressure equipment directive (PED 2014/68/EU) | For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 4, paragraph 3 (sound engineering practice) |
Explosion protection | |
| PTB 13 ATEX 2007 X |
| Ex II 1/2 G Ex ia/ib IIC T4/T5/T6 Ga/Gb |
- Permissible ambient temperature
| -40 ... +85 °C (-40 ... +185 °F) temperature class T4; -40 ... +70 °C (-40 ... +158 °F) temperature class T5; -40 ... +60 °C (-40 ... +140 °F) temperature class T6 |
| To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW; Ri = 300 ? | FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W |
- Effective internal inductance/capacitance
| Li = 0.4 mH, Ci = 6 nF | Li = 7 ?H, Ci = 1.1 nF |
| PTB 99 ATEX 1160 |
| Ex II 1/2 G Ex d IIC T4/T6 Gb |
- Permissible ambient temperature
| -40 ... +85 °C (-40 ... +185 °F) temperature class T4; -40 ... +60 °C (-40 ... +140 °F) temperature class T6 |
| To circuits with operating values: UH = 10.5 ... 45 V DC | To circuits with operating values: UH = 9 ... 32 V DC |
- Dust explosion protection for zone 20
| PTB 01 ATEX 2055 |
| Ex II 1 D Ex ta IIIC T120°C Da Ex II 1/2 D Ex ta/tb IIIC T120°C Da/Db |
- Perm. Ambient temperature
| -40 ... +85 °C (-40 ... +185 °F) |
| 120 °C (248 °F) |
| To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 ? | FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W |
- Effective internal inductance/capacitance
| Li = 0.4 mH, Ci = 6 nF | Li = 7 ?H, Ci = 1.1 nF |
- Dust explosion protection for zone 21/22
| PTB 01 ATEX 2055 |
| Ex II 2 D Ex tb IIIC T120°C Db |
| To circuits with operating values: UH = 10.5 ... 45 V DC; Pmax = 1.2 W | To circuits with operating values: UH = 9 ... 32 V DC; Pmax = 1 W |
- Type of protection "n" (zone 2)
| PTB 13 ATEX 2007 X |
| Ex II 2/3 G Ex nA IIC T4/T5/T6 Gc Ex II 2/3 G Ex ic IIC T4/T5/T6 Gc |
| Um = 45 V | Um = 32 V |
| To circuits with operating values: Ui = 45 V | FISCO supply unit: Uo = 17.5 V, Io = 570 mA Linear barrier: Uo = 32 V, Io = 132 mA, Po = 1 W |
- Effective internal inductance/capacitance
| Li = 0.4 mH, Ci = 6 nF | Li = 7 ?H, Ci = 1.1 nF |
- Explosion protection acc. to FM
| Certificate of Compliance 3008490 |
- Marking (XP/DIP) or (IS); (NI)
| CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III |
- Explosion protection to CSA
| Certificate of Compliance 1153651 |
| CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III |