General information | | |
Product type designation | SM 1231 TC 4x16 bit | SM 1231 TC 8x16bit |
Supply voltage | | |
Rated value (DC) | | |
| Yes | Yes |
Input current | | |
Current consumption, typ. | 40 mA | 40 mA |
from backplane bus 5 V DC, typ. | 80 mA | 80 mA |
Power loss | | |
Power loss, typ. | 1.5 W | 1.5 W |
Analog inputs | | |
Number of analog inputs | 4; Thermocouples | 8; Thermocouples |
permissible input voltage for current input (destruction limit), max. | ± 35 V | ± 35 V |
permissible input voltage for voltage input (destruction limit), max. | +-35 V | +-35 V |
Technical unit for temperature measurement adjustable | Degrees Celsius/degrees Fahrenheit | Degrees Celsius/degrees Fahrenheit |
Input ranges | | |
| Yes | Yes |
| No | No |
| Yes; J, K, T, E, R, S, N, C, TXK/XK(L); voltage range: +/-80 mV | Yes; J, K, T, E, R & S, B, N, C, TXK/XK(L); voltage range: ±80 mV |
| No | No |
| No | No |
Input ranges (rated values), voltages | | |
| Yes | Yes |
Input ranges (rated values), thermocouples | | |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
Thermocouple (TC) | | |
Temperature compensation | | |
| No | No |
Analog value generation for the inputs | | |
Measurement principle | integrating | integrating |
Integration and conversion time/resolution per channel | | |
| 15 bit; + sign | 15 bit; + sign |
| No | No |
| 85 dB at 50 / 60 / 400 Hz | 85 dB at 50 / 60 / 400 Hz |
Smoothing of measured values | | |
| Yes | Yes |
Errors/accuracies | | |
Temperature error (relative to input range), (+/-) | 25 °C ±0.1%, to 55 °C ±0.2% total measurement range | 25 °C ±0.1%, to 55 °C ±0.2% total measurement range |
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.5 % | 0.5 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | | |
| 120 dB | 120 dB |
Interrupts/diagnostics/status information | | |
Alarms | Yes | Yes |
Diagnostic functions | Yes; Can be read out | Yes; Can be read out |
Alarms | | |
| Yes | Yes |
Diagnostic messages | | |
| Yes | Yes |
| Yes | Yes |
Diagnostics indication LED | | |
| Yes | Yes |
| Yes | Yes |
Degree and class of protection | | |
Degree of protection acc. to EN 60529 | | |
| Yes | Yes |
Standards, approvals, certificates | | |
CE mark | Yes | Yes |
CSA approval | Yes | Yes |
FM approval | Yes | Yes |
RCM (formerly C-TICK) | Yes | Yes |
Ambient conditions | | |
Free fall | | |
| 0.3 m; five times, in product package | 0.3 m; five times, in product package |
Ambient temperature during operation | | |
| -20 °C to +60 °C horizontal mounting, -20 °C to 50 °C vertical mounting, 95% humidity, non-condensing | -20 °C to +60 °C horizontal mounting, -20 °C to 50 °C vertical mounting, 95% humidity, non-condensing |
| -20 °C | -20 °C |
| 60 °C | 60 °C |
Pollutant concentrations | | |
| S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free |
Connection method | | |
required front connector | Yes | Yes |
Mechanics/material | | |
Enclosure material (front) | | |
| Yes | Yes |
Dimensions | | |
Width | 45 mm | 45 mm |
Height | 100 mm | 100 mm |
Depth | 75 mm | 75 mm |
Weights | | |
Weight, approx. | 180 g | 220 g |