At 24 V DC without taking into account the digital outputs and DRIVE-CLiQ supply
0.2 A
Conductor cross-section, max.
2.5 mm2
Fuse protection, max.
20 A
Digital inputs
Voltage
-3 … +30 V
Low level (an open digital input is interpreted as "low")
-3 … +5 V
High level
15 … 30 V
Current consumption at 24 V DC, typ.
10 mA
Delay times of digital inputs 1), approx.
L > H
50 ?s
H > L
100 ?s
Conductor cross-section, max.
1.5 mm2
Digital outputs
(continuously short-circuit-proof)
Voltage
24 V DC
Total current of digital outputs, max.
1000 mA
Delay times of digital outputs 1)
typ.
150 ?s with 0.5 A resistive load
max.
500 ?s
Conductor cross-section, max.
1.5 mm2
Analog inputs
As voltage input
Voltage range
-10 … +10 V
Internal resistance Ri
100 k?
As current input
Current range
4 … 20 mA, -20 … +20 mA, 0 … 20 mA
Internal resistance Ri
250 ?
Resolution 2)
11 bits + sign
Conductor cross-section, max.
1.5 mm2
Analog outputs
(continuously short-circuit-proof)
Voltage range
-10 … +10 V
Load current, max.
-3 … +3 mA
Current range
4 … 20 mA, -20 … +20 mA, 0 … 20 mA
Load resistance, max.
500 ? for outputs in the range -20 … +20 mA
Resolution
11 bits + sign
Conductor cross-section, max.
1.5 mm2
Relay outputs
(changeover contacts)
Load current, max.
8 A
Switching voltage, max.
250 V AC, 30 V DC
Switching capacity, max.
At 250 V AC
2000 VA (cos ? = 1) 750 VA (cos ? = 0.4)
At 30 V DC
240 W (resistive load)
Required minimum current
100 mA
Conductor cross-section, max.
2.5 mm2
Power loss
< 10 W
PE connection
M4 screw
Dimensions
Width
50 mm
Height
150 mm
Depth
111 mm
Weight, approx.
0.87 kg
Approvals
cULus (File No.: 164110)
1) The specified delay times refer to the hardware. The actual reaction time depends on the time slice in which the digital input is processed.
2) If the analog input is to be operated in the signal processing sense with a continuously variable input voltage, the sampling frequency fa = 1/ttime slice must be at least twice the value of the highest signal frequency fmax.