SIPLUS SM 1222 digital output module

Article number

6AG1222-1BF32-2XB0

6AG1222-1BF32-4XB0

6AG1222-1BH32-2XB0

6AG1222-1BH32-4XB0

SIPLUS S7-1200 SM 1222 8DQ

SIPLUS S7-1200 SM 1222 8DQ

SIPLUS S7-1200 SM 1222 16DQ

SIPLUS S7-1200 SM 1222 16DQ

General information

 

 

 

 

Product type designation

SM 1222 DQ 8x24VDC

SM 1222 DQ 8x24VDC

SM 1222 DQ 16x24VDC

SM 1222 DQ 16x24VDC

Input current

 

 

 

 

from backplane bus 5 V DC, max.

120 mA

120 mA

140 mA

140 mA

Power loss

 

 

 

 

Power loss, typ.

1.5 W

1.5 W

2.5 W

2.5 W

Digital outputs

 

 

 

 

Number of digital outputs

8

8

16

16

  • ? in groups of

1

1

1

1

Short-circuit protection

No; to be provided externally

No; to be provided externally

No; to be provided externally

No; to be provided externally

Limitation of inductive shutdown voltage to

typ. (L+) -48 V

typ. (L+) -48 V

typ. (L+) -48 V

typ. (L+) -48 V

Switching capacity of the outputs

 

 

 

 

  • ? with resistive load, max.

0.5 A

0.5 A

0.5 A

0.5 A

  • ? on lamp load, max.

5 W

5 W

5 W

5 W

Output voltage

 

 

 

 

  • ? Rated value (DC)

24 V

24 V

24 V

24 V

  • ? for signal "0", max.

0.1 V; with 10 kOhm load

0.1 V; with 10 kOhm load

0.1 V; with 10 kOhm load

0.1 V; with 10 kOhm load

  • ? for signal "1", min.

20 V DC

20 V DC

20 V DC

20 V DC

Output current

 

 

 

 

  • ? for signal "1" rated value

0.5 A

0.5 A

0.5 A

0.5 A

  • ? for signal "0" residual current, max.

10 µA

10 µA

10 µA

10 µA

Output delay with resistive load

 

 

 

 

  • ? "0" to "1", max.

50 µs

50 µs

50 µs

50 µs

  • ? "1" to "0", max.

200 µs

200 µs

200 µs

200 µs

Total current of the outputs (per group)

 

 

 

 

horizontal installation

 

 

 

 

  • up to 50 °C, max.

4 A; Current per mass

4 A; Current per mass

8 A; Current per mass

8 A; Current per mass

Relay outputs

 

 

 

 

Switching capacity of contacts

 

 

 

 

  • with inductive load, max.

0.5 A

0.5 A

0.5 A

0.5 A

  • on lamp load, max.

5 W

5 W

5 W

5 W

  • with resistive load, max.

0.5 A

0.5 A

0.5 A

0.5 A

Cable length

 

 

 

 

  • ? shielded, max.

500 m

500 m

500 m

500 m

  • ? unshielded, max.

150 m

150 m

150 m

150 m

Interrupts/diagnostics/status information

 

 

 

 

Alarms

Yes

Yes

Yes

Yes

Diagnostic functions

Yes

Yes

Yes

Yes

Alarms

 

 

 

 

  • ? Diagnostic alarm

Yes

Yes

Yes

Yes

Diagnostic messages

 

 

 

 

  • ? Monitoring the supply voltage

Yes

Yes

Yes

Yes

Diagnostics indication LED

 

 

 

 

  • ? for status of the outputs

Yes

Yes

Yes

Yes

  • ? for maintenance

Yes

Yes

Yes

Yes

Potential separation

 

 

 

 

Potential separation digital outputs

 

 

 

 

  • ? between the channels, in groups of

1

1

1

1

  • ? between the channels and backplane bus

500 V AC

500 V AC

500 V AC

500 V AC

Degree and class of protection

 

 

 

 

Degree of protection acc. to EN 60529

  • ? IP20

Yes

Yes

Yes

Yes

Standards, approvals, certificates

 

 

 

 

CE mark

Yes

Yes

Yes

Yes

Ambient conditions

 

 

 

 

Free fall

 

 

 

 

  • ? Fall height, max.

0.3 m; five times, in product package

0.3 m; five times, in product package

0.3 m; five times, in product package

0.3 m; five times, in product package

Ambient temperature during operation

 

 

 

 

  • ? min.

-40 °C; = Tmin; Startup @ -25 °C

-20 °C; = Tmin; Startup @ 0 °C

-40 °C; = Tmin; Startup @ -25 °C

-20 °C; = Tmin; Startup @ 0 °C

  • ? max.

70 °C; = Tmax; Tmax > +60 °C number of simultaneously activated outputs 4 (no adjacent points) for horizontal mounting position

60 °C; = Tmax

70 °C; = Tmax; Tmax > +60 °C number of simultaneously activated outputs 8 (no adjacent points) for horizontal mounting position

60 °C; = Tmax

Extended ambient conditions

 

 

 

 

  • ? relative to ambient temperature-atmospheric pressure-installation altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Relative humidity

 

 

 

 

  • With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

Resistance

 

 

 

 

  • against biologically active substances / conformity with EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

  • against chemically active substances / conformity with EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • against mechanically active substances / conformity with EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Connection method

 

 

 

 

required front connector

Yes

Yes

Yes

Yes

Mechanics/material

 

 

 

 

Enclosure material (front)

  • ? Plastic

Yes

Yes

Yes

Yes

Dimensions

 

 

 

 

Width

45 mm

45 mm

45 mm

45 mm

Height

100 mm

100 mm

100 mm

100 mm

Depth

75 mm

75 mm

75 mm

75 mm

Weights

 

 

 

 

Weight, approx.

180 g

180 g

220 g

220 g


Article number

6AG1222-1HF32-2XB0

6AG1222-1HF32-4XB0

6AG1222-1HH32-2XB0

6AG1222-1HH32-4XB0

SIPLUS S7-1200 SM 1222 8DQ RLY

SIPLUS S7-1200 SM 1222 8DQ RLY

SIPLUS S7-1200 SM 1222 16DQ RLY

SIPLUS S7-1200 SM 1222 16DQ RLY

General information

 

 

 

 

Product type designation

SM 1222 DQ 8xRelay

SM 1222 DQ 8xRelay

SM 1222 DQ 16xRelay

SM 1222 DQ 16xRelay

Input current

 

 

 

 

from backplane bus 5 V DC, max.

120 mA

120 mA

135 mA

135 mA

Digital outputs

 

 

 

 

  • ? from load voltage L+, max.

11 mA/relay coil

11 mA/relay coil

11 mA/relay coil

11 mA/relay coil

Power loss

 

 

 

 

Power loss, typ.

4.5 W

4.5 W

8.5 W

8.5 W

Digital outputs

 

 

 

 

Number of digital outputs

8

8

16

16

  • ? in groups of

2

2

1

1

Short-circuit protection

No; to be provided externally

No; to be provided externally

No; to be provided externally

No; to be provided externally

Switching capacity of the outputs

 

 

 

 

  • ? with resistive load, max.

2 A

2 A

2 A

2 A

  • ? on lamp load, max.

30 W with DC, 200 W with AC

30 W with DC, 200 W with AC

30 W with DC, 200 W with AC

30 W with DC, 200 W with AC

Output voltage

 

 

 

 

  • ? Rated value (DC)

5 V DC to 30 V DC

5 V DC to 30 V DC

5 V DC to 30 V DC

5 V DC to 30 V DC

  • ? Rated value (AC)

5 V AC to 250 V AC

5 V AC to 250 V AC

5 V AC to 250 V AC

5 V AC to 250 V AC

Output current

 

 

 

 

  • ? for signal "1" permissible range, max.

2 A

2 A

2 A

2 A

Output delay with resistive load

 

 

 

 

  • ? "0" to "1", max.

10 ms

10 ms

10 ms

10 ms

  • ? "1" to "0", max.

10 ms

10 ms

10 ms

10 ms

Total current of the outputs (per group)

 

 

 

 

horizontal installation

 

 

 

 

  • up to 50 °C, max.

10 A; Current per mass

10 A; Current per mass

10 A; Current per mass

10 A; Current per mass

Relay outputs

 

 

 

 

  • ? Number of relay outputs

8

8

16

16

  • ? Rated supply voltage of relay coil L+ (DC)

24 V

24 V

24 V

24 V

  • ? Number of operating cycles, max.

mechanically 10 million, at rated load voltage 100 000

mechanically 10 million, at rated load voltage 100 000

mechanically 10 million, at rated load voltage 100 000

mechanically 10 million, at rated load voltage 100 000

Switching capacity of contacts

 

 

 

 

  • with inductive load, max.

2 A

2 A

2 A

2 A

  • on lamp load, max.

30 W with DC, 200 W with AC

30 W with DC, 200 W with AC

30 W with DC, 200 W with AC

30 W with DC, 200 W with AC

  • with resistive load, max.

2 A

2 A

2 A

2 A

Cable length

 

 

 

 

  • ? shielded, max.

500 m

500 m

500 m

500 m

  • ? unshielded, max.

150 m

150 m

150 m

150 m

Interrupts/diagnostics/status information

 

 

 

 

Alarms

Yes

Yes

Yes

Yes

Diagnostic functions

Yes

Yes

Yes

Yes

Alarms

 

 

 

 

  • ? Diagnostic alarm

Yes

Yes

Yes

Yes

Diagnostic messages

 

 

 

 

  • ? Monitoring the supply voltage

Yes

Yes

Yes

Yes

Diagnostics indication LED

 

 

 

 

  • ? for status of the outputs

Yes

Yes

Yes

Yes

  • ? for maintenance

Yes

Yes

Yes

Yes

Potential separation

 

 

 

 

Potential separation digital outputs

 

 

 

 

  • ? between the channels

Relay, dry contact

Relay, dry contact

Relays

Relay, dry contact

  • ? between the channels, in groups of

2

2

4

4

  • ? between the channels and backplane bus

1500 V AC for 1 minute

1500 V AC for 1 minute

1500 V AC for 1 minute

1500 V AC for 1 minute

Permissible potential difference

 

 

 

 

between different circuits

750 V AC for 1 minute

750 V AC for 1 minute

750 V AC for 1 minute

750 V AC for 1 minute

Degree and class of protection

 

 

 

 

Degree of protection acc. to EN 60529

  • ? IP20

Yes

Yes

Yes

Yes

Standards, approvals, certificates

 

 

 

 

CE mark

Yes

Yes

Yes

Yes

Ambient conditions

 

 

 

 

Free fall

 

 

 

 

  • ? Fall height, max.

0.3 m; five times, in product package

0.3 m; five times, in product package

0.3 m; five times, in product package

0.3 m; five times, in product package

Ambient temperature during operation

 

 

 

 

  • ? min.

-40 °C; = Tmin; Startup @ -25 °C

-20 °C; = Tmin; Startup @ 0 °C

-40 °C; = Tmin; Startup @ -25 °C

-20 °C; = Tmin; Startup @ 0 °C

  • ? max.

70 °C; = Tmax; Tmax > +60 °C number of simultaneously activated outputs 4 (no adjacent points) for horizontal mounting position

60 °C; = Tmax

70 °C; = Tmax; Tmax > +60 °C number of simultaneously activated outputs 8 (no adjacent points) for horizontal mounting position

60 °C; = Tmax

Extended ambient conditions

 

 

 

 

  • ? relative to ambient temperature-atmospheric pressure-installation altitude

Tmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m); from 2 000 m max. 132 V AC

Tmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m); from 2 000 m max. 132 V AC

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

  • ? At cold restart, min.

-25 °C

Relative humidity

 

 

 

 

  • With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

Resistance

 

 

 

 

  • against biologically active substances / conformity with EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

  • against chemically active substances / conformity with EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • against mechanically active substances / conformity with EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Connection method

 

 

 

 

required front connector

Yes

Yes

Yes

Yes

Mechanics/material

 

 

 

 

Enclosure material (front)

  • ? Plastic

Yes

Yes

Yes

Yes

Dimensions

 

 

 

 

Width

45 mm

45 mm

45 mm

45 mm

Height

100 mm

100 mm

100 mm

100 mm

Depth

75 mm

75 mm

75 mm

75 mm

Weights

 

 

 

 

Weight, approx.

190 g

190 g

260 g

260 g


















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ
Êàòàëîã îáîðóäîâàíèÿ 2017
Siemens Industry Catalog Drive Technology Automation Technology Automation Systems SIMATIC Industrial Automation Systems Controllers LOGO! logic module Basic Controllers S7-1200 Central processing units I/O modules Digital modules SM 1221 digital input modules SB 1221 digital input modules SM 1222 digital output modules SB 1222 digital output modules SM 1223 digital input/output modules SB 1223 digital input/output modules SIPLUS digital modules SIPLUS SM 1221 digital input modules SIPLUS SB 1221 digital input modules SIPLUS SM 1222 digital output modules SIPLUS SB 1222 digital output modules SIPLUS SM 1223 digital input/output modules SIPLUS SB 1223 digital input/output modules Analog modules Special modules Communication Fail-safe digital inputs and outputs SIPLUS Fail-safe digital inputs and outputs Power supplies Operator control and monitoring Add-on products from third-party manufacturers Software Advanced Controllers Distributed Controllers Software Controllers Supplementary components I/O systems SIMATIC control systems Software for SIMATIC Controllers Programming devices Siemens Solution Partner SIMOTION Motion Control System SINUMERIK CNC Automation Systems System Cabling / Control Cabinets Automation software Operator control and monitoring systems SIMATIC HMI Identification systems Industrial Communication Industrial Controls Manufacturing Execution Systems (MES) SIMATIC IT PC-based Automation Process control systems Process instrumentation Process analytics SITOP power supplies Products for specific requirements Energy Building Technologies Low-Voltage Controls and Distribution Safety Systems - Safety Integrated Market-specific solutions Industry Services ... and everything else you need




  © ÎÎÎ "ÑÊ ÝÍÅÐÃÎ" 2007-2022
  (4872) 700-366  skenergo@mail.ru
ßíäåêñ.Ìåòðèêà