SIPLUS SM 1223 digital input/output module

Article number

6AG1223-1BH32-2XB0

6AG1223-1BH32-4XB0

6AG1223-1PH32-2XB0

6AG1223-1PH32-4XB0

SIPLUS S7-1200 SM 1223 8DI/8DQ

SIPLUS S7-1200 SM 1223 8DI/8DQ

SIPLUS S7-1200 SM 1223 8DI/8DQ RLY

SIPLUS S7-1200 SM 1223 8DI/8DQ RLY

General information

 

 

 

 

Product type designation

SM 1223 DI 8x24 VDC, DQ 8x24 VDC

SM 1223 DI 8x24 VDC, DQ 8x24 VDC

SM 1223 DI 8x24 VDC, DQ 8xRelay

SM 1223 DI 8x24 VDC, DQ 8xRelay

Supply voltage

 

 

 

 

Rated value (DC)

  • ? 24 V DC

Yes

Yes

Yes

Yes

Input current

 

 

 

 

from backplane bus 5 V DC, max.

145 mA

145 mA

145 mA

145 mA

Digital inputs

 

 

 

 

  • ? from load voltage L+ (without load), max.

4 mA; per channel

4 mA; per channel

4 mA/input 11 mA/relay

4 mA/input 11 mA/relay

Output voltage

 

 

 

 

Power supply to the transmitters

 

 

 

 

  • ? present

Yes

Yes

Yes

Yes

Power loss

 

 

 

 

Power loss, typ.

2.5 W

2.5 W

5.5 W

5.5 W

Digital inputs

 

 

 

 

Number of digital inputs

8

8

8

8

  • ? in groups of

2

2

2

2

Input characteristic curve in accordance with IEC 61131, type 1

Yes

Yes

Yes

Yes

Number of simultaneously controllable inputs

 

 

 

 

all mounting positions

 

 

 

 

  • up to 40 °C, max.

8

8

8

8

horizontal installation

 

 

 

 

  • up to 40 °C, max.

8

8

8

8

  • up to 50 °C, max.

8

8

8

8

vertical installation

 

 

 

 

  • up to 40 °C, max.

8

8

8

8

Input voltage

 

 

 

 

  • ? Type of input voltage

DC

DC

DC

DC

  • ? Rated value (DC)

24 V

24 V

24 V

24 V

  • ? for signal "0"

5 V DC at 1 mA

5 V DC at 1 mA

5 V DC at 1 mA

5 V DC at 1 mA

  • ? for signal "1"

15 V DC at 2.5 mA

15 V DC at 2.5 mA

15 V DC at 2.5 mA

15 V DC at 2.5 mA

Input current

 

 

 

 

  • ? for signal "0", max. (permissible quiescent current)

1 mA

1 mA

1 mA

1 mA

  • ? for signal "1", min.

2.5 mA

2.5 mA

2.5 mA

2.5 mA

  • ? for signal "1", typ.

4 mA

4 mA

4 mA

4 mA

Input delay (for rated value of input voltage)

 

 

 

 

for standard inputs

 

 

 

 

  • parameterizable

Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

for interrupt inputs

 

 

 

 

  • parameterizable

Yes

Yes

Yes

Yes

Cable length

 

 

 

 

  • ? shielded, max.

500 m

500 m

500 m

500 m

  • ? unshielded, max.

300 m

300 m

300 m

300 m

Digital outputs

 

 

 

 

Number of digital outputs

8

8

8

8

  • ? in groups of

1

1

2

2

Short-circuit protection

No; to be provided externally

No; to be provided externally

No; to be provided externally

No; to be provided externally

Limitation of inductive shutdown voltage to

L+ (-48 V)

L+ (-48 V)

Switching capacity of the outputs

 

 

 

 

  • ? with resistive load, max.

0.5 A

0.5 A

2 A

2 A

  • ? on lamp load, max.

5 W

5 W

30 W with DC, 200 W with AC

30 W with DC, 200 W with AC

Output voltage

 

 

 

 

  • ? Rated value (DC)

24 V

24 V

5 V DC to 30 V DC

5 V DC to 30 V DC

  • ? Rated value (AC)

5 V AC to 250 V AC

5 V AC to 250 V AC

  • ? for signal "0", max.

0.1 V; with 10 kOhm load

0.1 V; with 10 kOhm load

  • ? for signal "1", min.

20 V DC

20 V DC

Output current

 

 

 

 

  • ? for signal "1" permissible range, max.

0.5 A

0.5 A

2 A

2 A

  • ? for signal "0" residual current, max.

10 µA

10 µA

Output delay with resistive load

 

 

 

 

  • ? "0" to "1", max.

50 µs

50 µs

10 ms

10 ms

  • ? "1" to "0", max.

200 µs

200 µs

10 ms

10 ms

Total current of the outputs (per group)

 

 

 

 

horizontal installation

 

 

 

 

  • up to 50 °C, max.

4 A; Current per mass

4 A; Current per mass

10 A; Current per mass

10 A; Current per mass

Relay outputs

 

 

 

 

  • ? Number of relay outputs

8

8

  • ? Rated supply voltage of relay coil L+ (DC)

24 V

24 V

  • ? Number of operating cycles, max.

mechanically 10 million, at rated load voltage 100 000

mechanically 10 million, at rated load voltage 100 000

Switching capacity of contacts

 

 

 

 

  • with inductive load, max.

0.5 A

0.5 A

2 A

2 A

  • on lamp load, max.

5 W

5 W

30 W with DC, 200 W with AC

30 W with DC, 200 W with AC

  • with resistive load, max.

0.5 A

0.5 A

2 A

2 A

Cable length

 

 

 

 

  • ? shielded, max.

500 m

500 m

500 m

500 m

  • ? unshielded, max.

150 m

150 m

150 m

150 m

Interrupts/diagnostics/status information

 

 

 

 

Alarms

Yes

Yes

Yes

Yes

Diagnostic functions

Yes

Yes

Yes

Yes

Alarms

 

 

 

 

  • ? Diagnostic alarm

Yes

Yes

Yes

Yes

Diagnostic messages

 

 

 

 

  • ? Monitoring the supply voltage

Yes

Yes

Yes

Yes

Diagnostics indication LED

 

 

 

 

  • ? for status of the inputs

Yes

Yes

Yes

Yes

  • ? for status of the outputs

Yes

Yes

Yes

Yes

  • ? for maintenance

Yes

Yes

Yes

Yes

Potential separation

 

 

 

 

Potential separation digital inputs

 

 

 

 

  • ? between the channels, in groups of

2

2

2

2

Potential separation digital outputs

 

 

 

 

  • ? between the channels

Relays

Relays

  • ? between the channels, in groups of

1

1

2

2

  • ? between the channels and backplane bus

500 V AC

500 V AC

1500 V AC for 1 minute

1500 V AC for 1 minute

Permissible potential difference

 

 

 

 

between different circuits

750 V AC for 1 minute

750 V AC for 1 minute

Degree and class of protection

 

 

 

 

Degree of protection acc. to EN 60529

  • ? IP20

Yes

Yes

Yes

Yes

Standards, approvals, certificates

 

 

 

 

CE mark

Yes

Yes

Yes

Yes

Ambient conditions

 

 

 

 

Free fall

 

 

 

 

  • ? Fall height, max.

0.3 m; five times, in product package

0.3 m; five times, in product package

0.3 m; five times, in product package

0.3 m; five times, in product package

Ambient temperature during operation

 

 

 

 

  • ? min.

-40 °C; = Tmin; Startup @ -25 °C

-20 °C; = Tmin; Startup @ 0 °C

-40 °C; = Tmin; Startup @ -25 °C

-20 °C; = Tmin; Startup @ 0 °C

  • ? max.

70 °C; = Tmax; Tmax > +60 °C number of simultaneously activated outputs 4, inputs 4 (no adjacent points) for horizontal mounting position

60 °C; = Tmax

70 °C; = Tmax; Tmax > +60 °C number of simultaneously activated outputs 4, inputs 4 (no adjacent points) for horizontal mounting position

60 °C; = Tmax

Extended ambient conditions

 

 

 

 

  • ? relative to ambient temperature-atmospheric pressure-installation altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

  • ? At cold restart, min.

-25 °C

Relative humidity

 

 

 

 

  • With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

Resistance

 

 

 

 

  • against biologically active substances / conformity with EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

  • against chemically active substances / conformity with EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • against mechanically active substances / conformity with EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Connection method

 

 

 

 

required front connector

Yes

Yes

Yes

Yes

Mechanics/material

 

 

 

 

Enclosure material (front)

  • ? Plastic

Yes

Yes

Yes

Yes

Dimensions

 

 

 

 

Width

45 mm

45 mm

45 mm

45 mm

Height

100 mm

100 mm

100 mm

100 mm

Depth

75 mm

75 mm

75 mm

75 mm

Weights

 

 

 

 

Weight, approx.

210 g

210 g

230 g

230 g


Article number

6AG1223-1PL32-2XB0

6AG1223-1PL32-4XB0

6AG1223-1BL32-2XB0

6AG1223-1BL32-4XB0

SIPLUS S7-1200 SM 1223 16DI/16DQ RLY

SIPLUS S7-1200 SM 1223 16DI/16DQ RLY

SIPLUS S7-1200 SM 1223 16DI/16DQ

SIPLUS S7-1200 SM 1223 16DI/16DQ

General information

 

 

 

 

Product type designation

SM 1223 DI 16x24 VDC, DQ 16xRelay

SM 1223 DI 16x24 VDC, DQ 16xRelay

SM 1223 DI 16x24 VDC, DQ 16x24 VDC

SM 1223 DI 16x24 VDC, DQ 16x24 VDC

Supply voltage

 

 

 

 

Rated value (DC)

  • ? 24 V DC

Yes

Yes

Yes

Yes

Input current

 

 

 

 

from backplane bus 5 V DC, max.

180 mA

180 mA

185 mA

185 mA

Digital inputs

 

 

 

 

  • ? from load voltage L+ (without load), max.

4 mA/input 11 mA/relay

4 mA/input 11 mA/relay

4 mA; per channel

4 mA; per channel

Output voltage

 

 

 

 

Power supply to the transmitters

 

 

 

 

  • ? present

Yes

Yes

Yes

Yes

Power loss

 

 

 

 

Power loss, typ.

10 W

10 W

4.5 W

4.5 W

Digital inputs

 

 

 

 

Number of digital inputs

16

16

16

16

  • ? in groups of

2

2

2

2

Input characteristic curve in accordance with IEC 61131, type 1

Yes

Yes

Yes

Yes

Number of simultaneously controllable inputs

 

 

 

 

all mounting positions

 

 

 

 

  • up to 40 °C, max.

16

16

16

16

horizontal installation

 

 

 

 

  • up to 40 °C, max.

16

16

16

16

  • up to 50 °C, max.

16

16

16

16

vertical installation

 

 

 

 

  • up to 40 °C, max.

16

16

16

16

Input voltage

 

 

 

 

  • ? Type of input voltage

DC

DC

DC

DC

  • ? Rated value (DC)

24 V

24 V

24 V

24 V

  • ? for signal "0"

5 V DC at 1 mA

5 V DC at 1 mA

5 V DC at 1 mA

5 V DC at 1 mA

  • ? for signal "1"

15 V DC at 2.5 mA

15 V DC at 2.5 mA

15 V DC at 2.5 mA

15 V DC at 2.5 mA

Input current

 

 

 

 

  • ? for signal "0", max. (permissible quiescent current)

1 mA

1 mA

1 mA

1 mA

  • ? for signal "1", min.

2.5 mA

2.5 mA

2.5 mA

2.5 mA

  • ? for signal "1", typ.

4 mA

4 mA

4 mA

4 mA

Input delay (for rated value of input voltage)

 

 

 

 

for standard inputs

 

 

 

 

  • parameterizable

Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

for interrupt inputs

 

 

 

 

  • parameterizable

Yes

Yes

Yes

Yes

Cable length

 

 

 

 

  • ? shielded, max.

500 m

500 m

500 m

500 m

  • ? unshielded, max.

300 m

300 m

300 m

300 m

Digital outputs

 

 

 

 

Number of digital outputs

16

16

16

16

  • ? in groups of

4

4

1

1

Short-circuit protection

No; to be provided externally

No; to be provided externally

No; to be provided externally

No; to be provided externally

Limitation of inductive shutdown voltage to

L+ (-48 V)

L+ (-48 V)

Switching capacity of the outputs

 

 

 

 

  • ? with resistive load, max.

2 A

2 A

0.5 A

0.5 A

  • ? on lamp load, max.

30 W with DC, 200 W with AC

30 W with DC, 200 W with AC

5 W

5 W

Output voltage

 

 

 

 

  • ? Rated value (DC)

5 V DC to 30 V DC

5 V DC to 30 V DC

24 V

24 V

  • ? Rated value (AC)

5 V AC to 250 V AC

5 V AC to 250 V AC

  • ? for signal "0", max.

0.1 V; with 10 kOhm load

0.1 V; with 10 kOhm load

  • ? for signal "1", min.

20 V DC

20 V DC

Output current

 

 

 

 

  • ? for signal "1" permissible range, max.

2 A

2 A

0.5 A

0.5 A

  • ? for signal "0" residual current, max.

10 µA

10 µA

Output delay with resistive load

 

 

 

 

  • ? "0" to "1", max.

10 ms

10 ms

50 µs

50 µs

  • ? "1" to "0", max.

10 ms

10 ms

200 µs

200 µs

Total current of the outputs (per group)

 

 

 

 

horizontal installation

 

 

 

 

  • up to 50 °C, max.

8 A; Current per mass

8 A; Current per mass

8 A; Current per mass

8 A; Current per mass

Relay outputs

 

 

 

 

  • ? Number of relay outputs

16

16

  • ? Rated supply voltage of relay coil L+ (DC)

24 V

24 V

  • ? Number of operating cycles, max.

mechanically 10 million, at rated load voltage 100 000

mechanically 10 million, at rated load voltage 100 000

Switching capacity of contacts

 

 

 

 

  • with inductive load, max.

2 A

2 A

0.5 A

0.5 A

  • on lamp load, max.

30 W with DC, 200 W with AC

30 W with DC, 200 W with AC

5 W

5 W

  • with resistive load, max.

2 A

2 A

0.5 A

0.5 A

Cable length

 

 

 

 

  • ? shielded, max.

500 m

500 m

500 m

500 m

  • ? unshielded, max.

150 m

150 m

150 m

150 m

Interrupts/diagnostics/status information

 

 

 

 

Alarms

Yes

Yes

Yes

Yes

Diagnostic functions

Yes

Yes

Yes

Yes

Alarms

 

 

 

 

  • ? Diagnostic alarm

Yes

Yes

Yes

Yes

Diagnostic messages

 

 

 

 

  • ? Monitoring the supply voltage

Yes

Yes

Diagnostics indication LED

 

 

 

 

  • ? for status of the inputs

Yes

Yes

Yes

Yes

  • ? for status of the outputs

Yes

Yes

Yes

Yes

  • ? for maintenance

Yes

Yes

Yes

Yes

Potential separation

 

 

 

 

Potential separation digital inputs

 

 

 

 

  • ? between the channels, in groups of

2

2

2

2

Potential separation digital outputs

 

 

 

 

  • ? between the channels

Relays

Relays

  • ? between the channels, in groups of

4

4

1

1

  • ? between the channels and backplane bus

1500 V AC for 1 minute

1500 V AC for 1 minute

500 V AC

500 V AC

Permissible potential difference

 

 

 

 

between different circuits

750 V AC for 1 minute

750 V AC for 1 minute

Degree and class of protection

 

 

 

 

Degree of protection acc. to EN 60529

  • ? IP20

Yes

Yes

Yes

Yes

Standards, approvals, certificates

 

 

 

 

CE mark

Yes

Yes

Yes

Yes

Ambient conditions

 

 

 

 

Free fall

 

 

 

 

  • ? Fall height, max.

0.3 m; five times, in product package

0.3 m; five times, in product package

0.3 m; five times, in product package

0.3 m; five times, in product package

Ambient temperature during operation

 

 

 

 

  • ? min.

-40 °C; = Tmin; Startup @ -25 °C

-20 °C; = Tmin; Startup @ 0 °C

-40 °C; = Tmin; Startup @ -25 °C

-20 °C; = Tmin; Startup @ 0 °C

  • ? max.

70 °C; = Tmax; Tmax > +60 °C number of simultaneously activated outputs 8, inputs 8 (no adjacent points) for horizontal mounting position

60 °C; = Tmax

70 °C; = Tmax; Tmax > +60 °C number of simultaneously activated outputs 8, inputs 8 (no adjacent points) for horizontal mounting position

60 °C; = Tmax

Extended ambient conditions

 

 

 

 

  • ? relative to ambient temperature-atmospheric pressure-installation altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Relative humidity

 

 

 

 

  • With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

Resistance

 

 

 

 

  • against biologically active substances / conformity with EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

  • against chemically active substances / conformity with EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • against mechanically active substances / conformity with EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Connection method

 

 

 

 

required front connector

Yes

Yes

Yes

Yes

Mechanics/material

 

 

 

 

Enclosure material (front)

  • ? Plastic

Yes

Yes

Yes

Yes

Dimensions

 

 

 

 

Width

70 mm

70 mm

70 mm

70 mm

Height

100 mm

100 mm

100 mm

100 mm

Depth

75 mm

75 mm

75 mm

75 mm

Weights

 

 

 

 

Weight, approx.

350 g

350 g

310 g

310 g


















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ
Êàòàëîã îáîðóäîâàíèÿ 2017
Siemens Industry Catalog Drive Technology Automation Technology Automation Systems Operator control and monitoring systems SIMATIC HMI Identification systems Industrial Communication Industrial Controls Manufacturing Execution Systems (MES) SIMATIC IT PC-based Automation Process control systems Process instrumentation Process analytics SITOP power supplies Products for specific requirements Automation technology for extreme conditions SIMATIC industrial automation systems Controllers SIPLUS LOGO! logic module Basic Controller S7-1200 SIPLUS central processing units SIPLUS I/O modules SIPLUS digital modules SIPLUS SM 1221 digital input modules SIPLUS SB 1221 digital input modules SIPLUS SM 1222 digital output modules SIPLUS SB 1222 digital output modules SIPLUS SM 1223 digital input/output modules SIPLUS SB 1223 digital input/output modules SIPLUS analog modules SIPLUS communication SIPLUS Fail-safe digital inputs and outputs SIPLUS extreme RAIL digital modules SIPLUS extreme RAIL analog modules SIPLUS extreme RAIL communication SIPLUS power supplies SIPLUS operator control and monitoring Advanced Controller Distributed Controller SIPLUS IO systems SIMOTION Motion Control System Process control systems Operator control and monitoring systems Industrial communication Industrial controls Power supplies SIPLUS add-ons Telecontrol Systems for Comprehensive Applications IO systems for heating elements Automatic door controls Condition Monitoring Systems Time synchronization Energy Building Technologies Low-Voltage Controls and Distribution Safety Systems - Safety Integrated Market-specific solutions Industry Services ... and everything else you need




  © ÎÎÎ "ÑÊ ÝÍÅÐÃÎ" 2007-2022
  (4872) 700-366  skenergo@mail.ru
ßíäåêñ.Ìåòðèêà