Product designation | | - |
General technical data: | | |
Product component / input for analog temperature sensors | | Yes |
Type of connection | | 2- and 4-wire technology |
Number of analog inputs | | |
| | 4 |
| | 2 |
physical measuring principle | | Sigma delta modulation |
Measuring precision | | typical +-1 K, PT100 up to max. +-1.3 K |
A/D conversion time / at the analog input | ms | 120 |
Sensor current / typical | µA | 210 |
Galvanic isolation / between the channels / Note | | maximum voltage difference +- 1 V |
Surge voltage resistance / of the outputs / maximum | V | 15 |
Temperature drift per °C / typical | %/°C | 0.05 |
Offset temperature per K / maximum | K/K | 1 |
Temperature measurement deviation per K / maximum | K/K | 1 |
Type of electrical connection / for temperature sensors | | Screw connection with removable terminal |
Type of connectable conductor cross-sections | | |
| | |
| | 1x (0,5 ... 4 mm?), 2x (0,5 ... 2,5 mm?) |
| | 1x (0,5 ... 2,5 mm?), 2x (0,5 ... 1,5 mm?) |
| | 1x (20 ... 12), 2x (20 ... 16) |
Temperature measuring range | | |
| °C | 0 ... 400 |
| °C | 0 ... 400 |
| °C | 0 ... 400 |
| °C | 0 ... 400 |
| °C | 0 ... 400 |
Galvanic isolation / between the outputs and system interface | | Yes |
Number of status displays | | 3 |
Display version / as status display by LED | | continuous light: ready, flashing light: no connection to basic device |
Design of the power supply | | Supply via base unit |
Diagnostics function / Cable break | | Yes |
Installation/ mounting/ dimensions: | | |
Width | mm | 22.5 |
Height | mm | 102 |
Depth | mm | 115 |