Inverse frequency shift capacitive level detection
Input
Measured variable
Change in picoFarad (pF)
Output
Solid-state output
Output
Galvanically isolated
Protection
Against reversed polarity (bipolar)
Max. switching voltage
30 V (DC)
30 V peak (AC)
Max. load current
82 mA
Voltage drop
< 1 V, typical at 50 mA
Time delay (pre or post switching)
Programmable by user (0 ... 100 s)
Fail-safe mode
Min. or max.
Connection
Removable terminal block
Accuracy
Resolution
Min. sensitivity (pF)
1 % change in actual capacitance
Max. temperature error
0.2 % of actual capacitance value
Rated operating conditions1)
Installation conditions
Location
Indoor/outdoor
Ambient conditions
Ambient temperature
-40 ... +85 °C (-40 ... +185 °F)2)
Medium conditions
Liquids, bulk solids, slurries, interfaces, and applications with viscous materials
Relative dielectric constant ?r
Min. 1.5
Process temperature
Rod/Cable version
-40 ... +200 °C (-40 ... +392 °F)2)
High Temperature version
-40 ... +400 °C (-40 ... +752 °F)
Process pressure3)
-1 ... +35 bar g (-14.6 ... +511 psi g)
Design
Material (enclosure)
Powder-coated aluminum with gasket
Degree of protection
Standard: Type 4/NEMA 4/IP65 Optional: Type 4/NEMA 4/IP68
Cable inlet
2 x M20 x 1.5 thread (option: 2 x ?" NPT conduit entry including 1 plugged entry)
Controls and displays
Local display
LCD
Configuration
Locally, using 3 button keypad (for standalone operation)
Remotely, using SIMATIC PDM (for installation on a network)
Power supply
Bus voltage (at process connection)
Standard: 12 ... 30 V DC
Intrinsically Safe: 12 ... 24 V DC
Current consumption
12.5 mA
Certificates and approvals
General Purpose
CSA, FM, CE, RCM
Dust Ignition Proof
ATEX II 1/2 D, 2 D IP6X T100 °C
Flameproof Enclosure With IS Probe
ATEX II 1/2 G EEx d[ia] IIC T6 ... T4 ATEX II 1/2 D T100 °C
Dust Ignition Proof With IS Probe
CSA/FM Class II, Div. 1, Groups E, F, G CSA/FM Class III T4
Intrinsically Safe4)
ATEX II 1 G EEx ia IIC T6 ... T4 ATEX II 1/2 D, 2 D IP6X T100 °C
CSA/FM Class I, Div. 1, Groups A, B, C, D CSA/FM Class II, Div. 1, Groups E, F, G CSA/FM Class III T4
Non-incendive
CSA/FM Class I, Div. 2, Groups A, B, C, D CSA/FM Class II, Div. 2, Groups F, G CSA/FM Class III T4 or T6
Explosion Proof with IS Probe
CSA/FM Class I, Div. 1, Groups A, B, C, D CSA/FM Class II, Div. 1, Groups E, F, G CSA/FM Class III T4
Marine
Lloyds Register of Shipping, Categories ENV1, ENV2, and ENV5
Others
Pattern Approval (China)
Communication
PROFIBUS PA (IEC 61158 CPF3 CP3/2)
Bus physical layer: IEC 61158-2 MBP-(IS)
Device profile: PROFIBUS PA profile for Process Control Devices Version 3.0, Class B
FISCO field device
1) When operation is in areas classified as hazardous, observe restrictions according to relevant certificate. See also Pressure/Temperature curves starting on page 5/57.
2) Thermal isolator is used if process connection temperature exceeds 85 °C (185 °F)
3) Pressure rating of process seal is temperature dependent. See Pressure/Temperature curves starting on page 5/57.RC
4) Barrier or Intrinsically Safe power supply required for Intrinsically Safe protection
Design: Probe
Rod version
High Temperature version
Cable version
Length
Min. 250 mm (9.8 inch), max. 1 000 mm (40 inch)
Min. 250 mm (9.8 inch), max. 1 000 mm (40 inch)
Min. 1 000 mm (40 inch), max. 25 000 mm (984 inch)
Sensor wetted parts
PFA (no insulation on active probe), 316L stainless steel, PEEK isolators