Mode of Operation | |
Measuring principle | Vibrating point level switch |
Input | |
Measured variable | High, low and demand |
Measuring frequency | 200 Hz |
Output | |
Relays | DPDT relay |
Relay delay | From loss of vibration: approximately 1 second |
| From resumption of vibration: approximately 1 ... 2 s |
Signal delay | Probe uncovered to covered: approximately 1 s |
| Probe covered to uncovered: approximately 1 ... 2 s |
Relay fail-safe | High or low, switch selectable |
Alarm output | Relay 8 A at 250 V AC, non-inductive |
| Relay 5 A at 30 V DC, non-inductive |
Sensitivity | High or low, switch selectable |
Rated operating conditions | |
Installation conditions | |
| Indoor/outdoor |
Ambient conditions | |
| -40 ... +60 °C (-40 ... +140 °F) |
| III |
| 2 |
Medium conditions | |
| -40 ... +150 °C (-40 ... +302 °F) |
- Max. threaded bushing temperature
| 60 °C (140 °F) |
- Max. enclosure surface temperature (Category 2D)
| 90 °C (194 °F) |
- Max. extension surface temperature (Category 1D)
| 150 °C (302 °F) |
| Max. 10 bar g (145 psi g) European Pressure Directive 2014/68/EU: Category 1 |
Minimum material density | Approx. 30 g/l (1.9 lb/ft3) |
Design | |
Material | |
| Epoxy coated aluminum |
Process connection | - Thread 1?" NPT [(Taper), ANSI/ASME B1.20.1],
R 1?" [(BSPT), EN 10226] - Thread R 1?" [(BSPT),
EN 10226], ?" NPT [(Taper), ANSI/ASME B1.20.1], sliding sleeve [min. length 500 mm (19.69 inch)] - Thread material:
stainless steel 304 (1.4301) or 316L (1.4404) depending on configuration
|
Tine material | Stainless steel 316L (1.4404) |
Degree of protection | IP66/Type 4/NEMA 4 |
Conduit entry | 2 x M20 x 1.5 or 2 x ?" NPT |
Weight | Standard version, no extensions: approx. 1.7 kg (3.7 lb) |
Power supply | - 19 ... 230 V AC, +10 %, 50 ... 60 Hz, 8 VA
- 19 ... 40 V DC, +10 %, 1.5 W
|
Certificates and approvals | - CSA/FM General Purpose
- CE
- CSA/FM Dust Ignition Proof
- RCM
- ATEX II 1/2 D
- IECex
|