PLC and Motion Control performance |
Maximum number of axes | 32 |
Minimum PROFIBUS cycle clock | 1 ms |
Minimum PROFINET send cycle clock (C240 PN only) | 0.5 ms |
Minimum servo/interpolator clock cycle | 0.5 ms |
Memory |
RAM (Random Access Memory) | 67 MB |
RAM disk (load memory) | 29 MB |
Retentive memory | 107 KB |
Persistent memory (user data on MMC) | 48 MB |
Communication |
Ethernet interfaces | 1 |
PROFIBUS interfaces | 2 |
PROFINET interfaces (C240 PN only) | - 1 interface with 3 ports
- Supports PROFINET IO with IRT and RT
- Can be configured as PROFINET IO controller and/or device
|
General technical specifications |
Supply voltage | |
| 24 V DC |
| 20.4 ... 28.8 V |
Current consumption, typ. | 1.2 A |
Inrush current, typ. | 8.0 A |
Power loss | 15 W |
Permissible ambient temperature | |
| -40 ... +70 °C (-40 ... +158 °F) |
| 0 ... 55 °C (32 ... 131 F) |
Permissible relative humidity (without condensation) | 5 ... 95 % |
Atmospheric pressure | 700 ... 1060 hPa |
Degree of protection acc. to EN 60529 (IEC 60529) | IP20 |
Dimensions (W ? H ? D) | 200 x 125 x 118 mm (7.87 ? 4.92 ? 4.65 in) |
Weight | |
| 1150 g (2.54 lb) |
| 16 g (0.56 oz) |
Relay outputs | 5 (C240) 1 (C240 PN) |
of which for | |
- Controller enable (C240 only)
| 4 |
| 1 |
Electrical specifications | |
- Operational voltage, max.
| 50 V DC |
| 1 A |
| 30 W |
Operating cycles | |
| 3 x 106 |
Drive interfaces (C240 only) | 4 |
Can be optionally used for analog, stepper or hydraulic drives, alternatively also as standard analog outputs | |
When used as an analog output | |
| ±10.5 V |
| 16 bits, including sign |
| No |
| ? 3 kOhm |
| 35 m (115 ft) |
When used as a pulse output for stepper drives | |
- Output voltage for "1" signal, IO = -20 mA
| 3,7 V |
- Output voltage for "0" signal, IO = 20 mA, max.
| 1 V |
| 55 ? |
| 50 m (164 ft) |
| 750 kHz |
Integrated digital inputs | 18 |
of which with special functions for: | |
- Measuring input (C240 only)
| 2 |
- BERO connection
(can also be used as measuring input with C240, can only be used as measuring input with C240 PN)
(all inputs can be used as standard inputs) | 4 |
Input voltage | |
| 24 V DC |
| 11 ... 30 V |
| -3 ... +5 V |
Galvanic isolation | |
| 18 |
Input current | |
- For signal "1", min. / typ.
| 6 mA/8 mA |
Input delay ?(at rated value of input voltage) | |
| 6 µs/15 µs |
| 40 µs/150 µs |
Connection of 2-wire BERO | Yes |
- Permitted quiescent current
| 2 mA |
Integrated digital outputs | 8 |
- of which for fast cam output, max.
| 8 |
Rated load voltage | DC 24 V |
| 20.4 ... 28.8 V |
Output voltage | |
| L+ |
Galvanic isolation in groups of | 8 |
Output current | |
- For signal "1", minimum current per channel
| 5 mA |
| 0,5 mA |
Residual current, max. | 2 mA |
Derated loading | |
| 4 A |
| 2 A |
Switching frequency of the outputs | |
| 100 Hz |
| 2 Hz |
Lamp load | 5 W |
Purge energy/channel | 400 mJ (not simultaneous) |
Output delay, typ. | 150 µs |
Short-circuit protection | Yes |
Encoder inputs, max. (C240 only) Optionally for incremental or absolute encoder Can be used alternatively as up/down counter | 4 |
Incremental encoder inputs | |
| 5 V |
| 5 V/0.3 A |
| No |
| 1 MHz |
| |
| 10 m (32 ft) |
| 25 m (82 ft) |
| 35 m (115 ft) |
Inputs, SSI absolute encoder | |
| 5 V synchronous serial, single- or multi-turn |
| 24 V/0.3 A |
| No |
| 187.5/375/750/1500 kbit/s |
| 25 bit |
| |
| 250 m (820 ft) |
| 10 m (32 ft) |
Monitoring | |
- Short-circuit of the sensor supply
| Yes |
| Yes |
Additional technical specifications |
Real-time clock bufferting | |
| 4 weeks |
| 1 h |
Approvals, according to | |
| cULus |
| cULus |
| RCM (formerly C-Tick) |
| KCC |
- Russia, Belarus, Kazakhstan
| EAC |